Mitsubishi Electric PURY-P200 Service Handbook page 187

City multi r410a
Table of Contents

Advertisement

(5) Intelligent power module (IPM)
Measure resistances between each terminal of IPM with tester, and use the results for troubleshooting
Notes on measurement
• Make sure the polarity before the measurement. (On the tester, black normally indicates plus.)
• Make sure that the resistance is not open (∞Ω) or not shorted (to 0Ω).
• For the resistance, the margin of error is allowed.
• The result that is more than double or half than the result that is measured at the same measurement point
is not allowed.
Tester restriction
• Use the tester whose internal electrical power source is 1.5V or greater.
• Use the dry-battery-powered tester.
(✻The accurate diode-specific resistance cannot be measured with the button-battery-powered card tester,
as the applied voltage is low.)
• Use the range that measures low resistance as much as possible.
The more accurate resistance can be measured.
• External view
• Judgement value
Black
(+)
P
N
Red
(–)
P
N
U
5~200Ω
5~200Ω
V
W
5~200Ω
(6) Diode stack
Measure resistances between each terminal of diode stack with tester, and use the results for troubleshooting.
Refer to (5) " Intelligent power module (IPM) " for notes on measurement and tester restriction.
1
2
1
2
3
U
V
W
16
10
7
4
1
U
V
5~200Ω 5~200Ω
5~200Ω
3
+
• Internal circuit diagram
3
2
Pre-Driver
N
1
6
5
Pre-Driver
P
4
9
8
Pre-Driver
B
7
11
13
Pre-Driver
10
14
Pre-Driver
W
15
Pre-Driver
12
Over heating
16
protection circuit
• Judgement value
Black
(+)
+ (P)
Red
(–)
+ (P)
- (N)
~ (1)
~ (2)
~ (3)
- 184 -
P
U
V
W
B
N
Temperature sensor
- (N)
~ (1)
~ (2)
5~200Ω 5~200Ω
5~200Ω
5~200Ω
5~200Ω
~ (3)
5~200Ω

Hide quick links:

Advertisement

Table of Contents
loading