4.25.5 Frequency setting by pulse train input (Pr. 291, Pr. 384 to Pr. 386)

The inverter speed can be set by inputting pulse train from terminal JOG.
Parameter
Name
Number
291
Pulse train input selection
Input pulse division
384
scaling factor
Frequency for zero input
385
pulse
Frequency for maximum
386
input pulse
(1) Pulse train input selection (Pr. 291)
· Setting any of "1, 11, 21, 100" in Pr. 291 Pulse train input selection and a value other than "0" in Pr. 384 Input pulse
division scaling factor switches terminal JOG to pulse train input terminal and frequency setting of the inverter can be
performed. (The initial value is JOG signal)
Pulse train input of maximum of 100k pulse/s is enabled.
· Output specifications (high speed pulse train output or FM output) of terminal FM can be selected using Pr. 291.
Connection with an open collector output system
pulse generator
Sink logic
PC
Pull up resistance
*
JOG
SD
Connection with an open collector output system
pulse generator
Source logic
PC
JOG
Pull down resistance
*
SD
Initial
Setting
Value
0
0
1 to 250
0Hz
0 to 400Hz
50Hz
0 to 400Hz
Inverter
24V power
2kΩ
Inverter
2kΩ
24V power
Special operation and frequency control
Range
0
Terminal JOG
1
Pulse train input
0
Pulse train input invalid
Indicates division scaling factor to the input pulse and the
frequency resolution to the input pulse changes according
to the value.
Set the frequency when the input pulse is 0 (bias).
Set the frequency when the input pulse is maximum
(gain).
Connection with a complimentary output system
pulse generator
Sink logic
PC
JOG
SD
Connection with a complimentary output system
pulse generator
Source logic
PC
JOG
SD
Description
Inverter
2kΩ
Inverter
2kΩ
4
365