Mitsubishi Electric FR-A740-00023 Instruction Manual page 190

Fr-a700 series
Table of Contents

Advertisement

Selection and protection of a motor
REMARKS
⋅ When performing offline auto tuning, set "3, 7, 8, 13, 17, 18, 23, 33, 43, 53" in Pr. 71.
(Refer to page 181 for offline auto tuning)
⋅ For the 00170 and 00250, the Pr. 0 Torque boost and Pr. 12 DC injection brake operation voltage settings are automatically changed
according to the Pr. 71 setting as follows.
Standard Motor Setting
Pr. 71
0, 2, 3 to 8, 20, 23, 24, 40, 43, 44
Pr. 0
Pr. 12
(2) Use two types motors (Pr. 450)
⋅ Set Pr. 450 Second applied motor to use two types motors with one inverter.
⋅ When "9999" (initial value) is set, no function is selected.
≠ 9999, turning the RT signal on makes the following parameter valid.
⋅ When Pr. 450
Function
Applied motor
Control method selection
Motor capacity
Number of motor poles
Motor excitation current
Motor rated voltage
Rated motor frequency
Motor constant (R1)
REMARKS
⋅ The RT signal acts as the second function selection signal and makes the other second functions valid.
⋅ The RT signal is assigned to the terminal RT in the initial setting. By setting "3" in any of Pr. 178 to Pr. 189 (input terminal function
selection), you can assign the RT signal to the other terminal.
CAUTION
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Make
setting after confirming the function of each terminal.
Set this parameter correctly according to the motor used.
Incorrect setting may cause the motor to overheat and burn.
♦ Parameters referred to ♦
Pr. 0 Torque boost
Refer to page 138
Pr. 12 DC injection brake operation voltage
Pr. 80 Motor capacity, Pr. 81 Number of motor poles, Pr. 453 Second motor capacity, Pr. 454 Number of second motor poles
Pr. 82 to Pr. 84, Pr. 90 to Pr. 94, Pr. 96, Pr. 455 to Pr. 463, Pr. 859, Pr. 860 (Motor constant)
Pr. 95 Online auto tuning selection, Pr. 574 Second motor online auto tuning
Pr. 451 Second motor control method selection, Pr. 800 Control method selection
Pr. 100 to Pr. 109 (Adjustable 5 points V/F)
180
Constant Torque Motor Setting
1, 13 to 18, 50, 53, 54
3%
4%
RT Signal
RT Signal
ON (second
OFF (first
motor)
motor)
Pr. 450
Pr. 71
Pr. 451
Pr. 800
Pr. 453
Pr. 80
Pr. 454
Pr. 81
Pr. 455
Pr. 82
Pr. 456
Pr. 83
Pr. 457
Pr. 84
Pr. 458
Pr. 90
CAUTION
Refer to page 194
Refer to page 159
2%
2%
Function
Motor constant (R2)
Motor constant (L1)
Motor constant (L2)
Motor constant (X)
Auto tuning setting/status
Online auto tuning selection
Torque current
Refer to page 181
Refer to page 191
Refer to page 87
RT Signal
RT Signal
ON (second
OFF (first
motor)
motor)
Pr. 459
Pr. 91
Pr. 460
Pr. 92
Pr. 461
Pr. 93
Pr. 462
Pr. 94
Pr. 463
Pr. 96
Pr. 574
Pr. 95
Pr. 860
Pr. 859
(Refer to page 226)
Refer to page 140

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents