Mitsubishi Electric FR-A700 Instruction Manual page 209

Fr-a700 series to 03460-na/09620-na/00330-n4/00170-n4
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

(4) Tune second applied motor
· When you want to switch two motors with one inverter, set the second motor in Pr. 450 Second applied motor.(Initial
setting is without second applied motor. (Refer to page 185))
Perform tuning using Pr. 574 Second motor online auto tuning.
Pr. 574 Second motor online auto tuning is made valid when the RT signal turns on.
Parameter
Number
Used as rated motor current and electronic thermal relay
51
parameters.
450
Applied motor
Motor capacity (down to one rank lower than the inverter
453
capacity, note that the capacity should be 0.4kW or more)
454
Number of motor poles
REMARKS
· The RT signal acts as the second function selection signal and makes the other second functions valid. (Refer to page 232.)
The RT signal is assigned to the terminal RT in the initial setting. By setting "3" in any of Pr. 178 to Pr. 189 (input terminal function
selection), you can assign the RT signal to the other terminal.
CAUTION
· Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Make
setting after confirming the function of each terminal.
♦ Parameters referred to ♦
Pr. 9 Electronic thermal O/L relay
Pr. 71 Applied motor
Refer to page 185
Pr. 80 Motor capacity
Refer to page 92
Pr. 81 Number of motor poles
Pr. 96 Auto tuning setting/status
Pr. 178 to Pr. 189 (input terminal function selection)
Pr. 190 to Pr .196 (output terminal function selection)
Description
Refer to page 181
Refer to page 92
Refer to page 187
Refer to page 228
Refer to page 236
Selection and protection of a motor