Mitsubishi Electric FR-A700 Instruction Manual page 204

Fr-a700 series to 03460-na/09620-na/00330-n4/00170-n4
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Selection and protection of a motor
(5) Method to set the motor constants without using the offline auto tuning data
The Pr. 92 and Pr. 93 motor constants may either be entered in [Ω] or in [mH]. Before starting operation, confirm which
motor constant unit is used.
• To enter the Pr. 92 and Pr. 93 motor constants in [Ω]
<Operating procedure>
1) Set Pr. 71 according to the motor used.
Standard motor
Setting
Constant-torque motor
2) In the parameter setting mode, read the following parameters and set desired values.
Iq = torque current, I
2
Iq =
I
- I
100
Parameters
Number
Motor excitation current
82
(no load current)
90
Motor constant (r1)
91
Motor constant (r2)
92
Motor constant (x1)
93
Motor constant (x2)
94
Motor constant (xm)
859
Torque current
3)Refer to the following table and set Pr. 83 and Pr. 84 .
Parameter
Number
83
Motor rated voltage
84
Rated motor frequency
* The initial value differs according to the voltage level. (200V/400V)
REMARKS
· When "9999" is set in Pr. 82, Pr. 90 to Pr. 94, Pr. 859, Mitsubishi motor (SF-JR, SF-HR,SF-JRCA, SF-HRCA, SF-V5RU) constants
are used.
CAUTION
· If "star connection" is mistaken for "delta connection" or vice versa during setting of Pr. 71, advanced magnetic flux vector
control, real sensorless vector control and vector control cannot be exercised properly.
194
Star Connection
Motor
rated current, I
no load current
100 =
0 =
2
0
Name
02150 (01100) or less
02880 (01440) or more
02150 (01100) or less
02880 (01440) or more
02150 (01100) or less
02880 (01440) or more
02150 (01100) or less
02880 (01440) or more
02150 (01100) or less
02880 (01440) or more
02150 (01100) or less
02880 (01440) or more
02150 (01100) or less
02880 (01440) or more
Name
Delta Connection
Motor
5
6
15
16
Setting Range
200V class (400V class)
0 to 500A, 9999
0 to 3600A, 9999
0 to 50Ω, 9999
0 to 400mΩ, 9999
0 to 50Ω, 9999
0 to 400mΩ, 9999
0 to 50Ω, 9999
0 to 3600mΩ, 9999
0 to 50Ω, 9999
0 to 3600mΩ, 9999
0 to 500Ω, 9999
0 to 100Ω, 9999
0 to 500A, 9999
0 to 3600A, 9999
Setting Range
0 to 1000V
10 to 120Hz
Setting
Increments
0.01A
0.1A
0.001Ω
0.01mΩ
0.001Ω
0.01mΩ
0.001Ω
0.01mΩ
0.001Ω
0.01mΩ
0.01Ω
0.01A
0.1A
Setting
Initial
Increments
Value
0.1V
400V
0.01Hz
Hz
Initial
Value
9999
9999
9999
9999
9999
9999
9999

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a720-00030Fr-a740-00015

Table of Contents