System Overview Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 1. System Overview System Architecture 8 to 24 zones ( Pre mie r 24 1 Output Module Pre mie r 2 4 4 ke ypads Pre mie r 2 4...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual System Overview • LCDLP 2.5 Amp power supply • Premier Elite 168 LCDL with a built in Proximity Tag Reader • FMK/SMK 8 fully programmable Double Pole or End Of Line zones •...
System Overview Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Keys • For use with an analogue telephone line (REN = 1) ICONS UK English English Com2400 B B • Multi-protocol communicator supporting Fast Format, Contact C...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation 3. Installation Installation Sequence Control Panel Before attempting to install the alarm system, read this section. Once Mounting you have an overall understanding of the installation sequence, Mount the control panel on a flat, plumb wall using at least three carefully work through each step.
Page 8
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Premier Elite 24 Control Panel Layout Polymer E x pan s io n L/M R /R L o ad D e fau lts 0 . 75 A 0 . 3A...
Page 9
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation Control Panel Layout Metal All Models (168 shown) Mains Terminal Tamper B lock & C able E ntry S witch C able E ntry 2.5 Amp Mains PS U 2.
Page 10
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Premier Elite 24 PCB Layout E xpans ion L /M R /R Tamper Tamper Dis able L oa d D efa ults 0. 75 A 0 .3 A U S E WIT H...
Page 11
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation 21: Load Defaults Button Press and hold this button whilst applying power to the control panel to load the factory default settings. Press and hold this button for 7...
Page 12
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Premier Elite 24-W & 48-W PCB Layout B AR C ODE D igi Mode m Ta m per D is a ble 0 .7 5A 0. 3A F it f or...
Page 13
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation 19: RICOCHET™ Eng keypad connection An engineer’s keypad (LCD keypad and interface lead) can be temporarily plugged onto this connector allow system programming and testing. Set the keypad address switches to all 20: RICOCHET™Firmware Flash Port...
Page 14
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Premier Elite 48/88/168 PCB Layout B o x Tamp Programming Po rt US E W IT H T E XE C O M P S U O NLY L /M...
Page 15
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation 18: Communication Ports Com Port 1 is a serial communications port and can be used for connecting a PC running Wintex or any supported serial device to the control panel (see page 94 for details).
Page 16
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Premier Elite 640 PCB Layout C om 3 B o x Tamp J p1 13. 7V D C 2.5A m ax J p2 US E W IT H 1 00 mV = 1 Am p...
Page 17
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation 18: Communication Ports 1&2 22: Battery Kick-start Button Com Port 1 is a serial communications port and can be used for When powering up the panel without AC Mains present, this button connecting a PC running Wintex or any supported serial device to the must be pressed in order to connect the battery.
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Power Supply Ratings If installing to EN50131 or PD6662, the system standby times in the event of a mains power failure vary depending on the grade and how AC fail is signalled: ...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation Connecting AC Mains The AC Mains supply is connected to a 3 way ‘Euro Type’ fused terminal block, which is fitted with a 3.15A medium/slow blow fuse. All other wiring MUST be carried out before AC mains is connected to the control panel.
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Whichever method of wiring configuration is used, ensure that the Connecting Devices to the Network voltage between the ‘+’ and ‘–’ terminals at each device is no lower than 10.0V when the system is running on the standby battery.
Page 21
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation Figure 1: Network Connections (250m without additional power supply). 250 m Premier Premier Premier Premier K eypad K eypad Zone E xpander K eypad Ne tw or k Ne tw or k...
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Zone Numbering Remote Keypads The table below shows the zone allocation when the keypads are Keypad Layout installed: Tamp er Ou tput Zones Zones S peak er S witc h...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation established correctly. Please refer to the relevant section in this 8XP-W & 32XP-W V2.xx> document to Learn Devices to the system. Learning Premier Elite SmartKey™ Ricochet MT2 On Ricochet MT2 systems Premier Elite SmartKey™ should only be The Premier Elite Series™...
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 1: Engineers Keypad Connection 9: Heartbeat LED An engineer’s keypad (Premier/Elite LCD keypad and interface lead) Flashes steadily to indicate that the receiver is functioning correctly. If can be temporarily plugged onto this connector to allow system the light is ON or OFF all the time, then there could be a hardware programming and testing.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation 8XE Zone Expander (24 Only) 8XP Zone Expander The 8XE Zone Expander has: Expander Layout • 8 fully programmable zones E ngineers Network Tamper K eypad • Aux 12V Output...
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Zone Numbering (24/48/88/168) Star and Daisy Jumper Option The table below shows the zone allocation when the expanders are The PCB has a jumper JP3 which allows you to select either STAR installed: (S) or DAISY (D) wiring configuration.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation iProx Module OP16 Output Expander iProx Layout Output Module Layout O ptio n & Ad dre s s S witches Internal Sounder Aux 12V Tamper Networ k and Tam per...
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Output Module Numbering Installation The table below shows the output allocation when the output Before attempting to install the RM8 Relay Module, isolate ALL power modules are installed, from the control panel (AC Mains and Battery). Do not continue if there is power still present on the control panel.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation Zone and Output Numbering 24/48/88/168 Expander Zones Keypad Zones Zones Zones Address Zones Zones Address (Network 1) (Network 2) Network 1 Network 2 9 - 16 73 - 80...
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Zone and Output Numbering 640 Expander Zones Zones Zones Zones Zones Zones Zones Zones Zones Address Network 1 Network 2 Network 3 Network 4 Network 5 Network 6 Network 7...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation Triple End Of Line (TEOL) Zone Connections Use this wiring configuration when connecting PIR devices with that Any zones that are not being used must be linked out or require Anti Mask and Fault detection.
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 60IXD Zone Expander Cable Length Maximum Number of Biscuits 100m The 60iXD expander provides the following facilities: 200m • Two iD loops each supporting up to 30 biscuits 400m •...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation (S) Strb – Auxiliary/Fault Connections Strobe output, switches to 0V in alarm and is rated at 500mA. Normally connected to strobe -ve on the sounder (where applicable, The Aux/Fault terminals allow the control panel to monitor the tamper connect the strobe +ve to +12V).
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Panel Outputs Digicom Outputs 1 - 8 The control panel has five programmable outputs, which can be used The control panel has eight programmable outputs, which can be to drive auxiliary devices such as LED’s, sounders or relays etc. (see used for connecting to a stand-alone communicator (see page 77 for page 76 for details).
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation 2-Wire Smoke Detector Panel Output 1 can be used for connecting up to 10, 12V 2-Wire smoke detectors. Remote LED C ontrol (Optional) Panel + V In + V In...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation The control panel end of the connector should be attached with the Plug-on Communicators red lead on the left most pin of the digi modem connector. The Com300 is a multi format 8-channel digital communicator/300- baud modem for use with a standard analogue telephone line.
SIM cards purchase only used to power the Premier Elite ComGSM when using APNProgrammer Texecom DO NOT supply SIM cards. These will need to be sourced locally, and care should be taken to source SIM cards in the country ...
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Aerial Siting You should check and confirm that the signal strength is still the same as recorded during the site survey. ALWAYS do a site survey to find an area of strong signal before installation.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation For Upload/Download via Wintex edit the Account/Panel Premier 48/88/168/640 & Premier Elite 24/48/88/168/640 SMS Control Commands Operation Command Example Details and fill in the IP address you have been given and “5678 arm s”...
Installation Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation AV Module General Before connecting the AV Module, isolate ALL power from the control The installation of the ComIP module requires a basic understanding panel (AC mains and battery), do not continue if there is still power of networking and TCP/IP protocol.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Installation Commissioning PRINT-Com The control panel must be programmed correctly in order for the The PRINT-Com has two connectors. The 25-way D-type connector module to function as expected. The following section covers the...
Commissioning and Troubleshooting Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 4. Commissioning and Troubleshooting Commissioning Trouble-Shooting Once ALL connections have been made to the control panel and Control Panel power is ready to be applied, you should read this section before No Power to unit (mains only) continuing.
Page 43
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Commissioning and Troubleshooting Expander Operation Expander does not operate at all The system will not allow me to arm • • Check that the expander is wired correctly from the control...
Commissioning and Troubleshooting Premier Elite 24, 48, 88, 168 & 640 Installation Manual There are no ATS (Alarm Transmission Reset and Service Messages o ah ailale System) paths available. e a When the system requires attention because of a potential problem, The Standby Battery has not been the display will show one of three service messages.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Programming 5. Programming the Control Panel Introduction a Jan All engineers should read this section carefully so as to familiarise E nter En gineer s C ode themselves with the programming of the control panel.
Programming the Control Panel Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Programming Menu Guide Main Menu Sub Menu Main Menu Sub Menu Zone Setup Learn/Delete Ricochet Engineer Utils View Event Log 1 R 9 Device Do Bell Test ...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Programming the Control Panel Programming Text Log Off Engineer Text is programmed in a similar way to mobile phones. Characters Whenever the Engineer Programming menu is exited by pressing are selected by pressing the corresponding key the appropriate twice, the display will look like this: ...
Zone Setup Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 5.1 Zone Setup E o elec:- Zone ep E nter zone number Zone anel e.g. 004 = Zone 004 Eny/Ei Use hotkeys 1 - 8 to s elec t...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Zone Setup Ricochet Devices MT2 Option Switches In this mode only option switch 3 should be on. Introduction The firmware upgrade now requires that Ricochet™ devices are learned through the Zone Setup Menu, and Premier Elite SmartKey™ are learned through the User Setup menu, the "Configure Radio"...
Zone Setup Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 9 - Fire Zone Types Normally used for monitoring smoke detectors. This zone type will cause a Fire alarm with distinctive fire tone if it is activated when the Each zone must be programmed before it is recognised by the system/area is armed or disarmed.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Zone Setup Zone Attributes 1 Zone Attributes 2 Attributes can be assigned to a zone to alter its operation i.e. a Guard Select attributes by pressing keys 1 to 8 (a letter on the display zone with the ‘Access’...
Zone Setup Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Attributes for Moment or Latch Keys Zone Areas 24/48/88/168 Select attributes by pressing keys 1 to 8 (a letter on the display The 24 can be divided into two separate areas of protection, the 48 can...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Zone Setup • Exp O/P 1-2* Remote Test Enable • Exp O/P 3-4* • Exp O/P 5-6* Any zone with this attribute will be tested when the remote test •...
Area Programming Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 5.2 Area Programming Timers The area bell timers in options 5, 6 and 8 below are only active when system config option 5 is switched to ‘Area Bell Time’.
P Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Area Programming Suite Arm Modes Area Options 24/48/88/168 E o elec:- E o elec:- ea ogaing ea ogaing ea ogaing ea ogaing ies ies ea ogaing ea ogaing ea pions ie ...
Page 58
Area Programming Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual These options control how various features affect each area. Any number of areas can be assigned to each option. If ‘Anti-code Reset’ is enabled (option 14) the assigned areas...
Page 59
P Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Area Programming • • If the selected area is fully armed and an Intruder alarm occurs in Zones with the ‘Double Knock’ attribute will use the multiple that area, Intruder alarm events (for that area) are reported to the knock value set up in system options for zone activations (see Alarm Receiving Centre after any programmed ‘Digi delay’...
Page 60
Area Programming Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual which activation of a further two zones that are not on the entry route 38 - AC Fail Eng Reset must occur before the Alarm Confirmation output will activate Each area can be programmed for Engineer or User reset following an AC Mains Fail.
P Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Area Programming Time Arm Area Area Text E o elec:- E o elec:- ea ogaing ea ogaing ea ogaing ea ogaing ies ies ea ogaing ea ogaing ea e...
Global Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 5.3 Global Options 9 - Auto Arm Delay System Timers When an area assigned to ‘Auto Arm Areas’ is disarmed (see page 59 for details) this timer is started. Every time a detector in that area is activated, the timer is restarted.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Global Options 25 - Keypad PA Delay System Config. When keypad ‘option 6’ is programmed as ‘PA Delayed’ (see page 73 for details), and a keypad PA alarm (1 & 3) is activated, this timer starts.
Page 64
Global Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 05 Global Bell Time 15 - Hide Exit Errors When all areas are armed, the system uses the ‘Global Bell Delay’ and If a user tries to arm an area and there are zones activated, the exit ‘Global Bell Duration’...
Page 65
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Global Options 23 - User Code Pulse EN50131 Enabled Entering a user code which has an associated user output will cause Keypad display ‘blanking’ is enabled i.e. the keypad will only display the output to activate for the duration of the door strike timer.
Page 66
Global Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 44 – FOB Batt Warn 53 – Enable PD6662:2010 When during arming if a low fob battery event is received the arming The panel will be defaulted to operate according to PD6662:2010...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Global Options number is defined on the product label where applicable by LS1, LS2 System Options or LS3. The 640 has all languages listed available in the control panel. 24/48/88/168 E...
Keypad Setup Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 5.4 Keypad Setup E o elec:- Keypad ep Use keys 1 - 8 to s elec t a k eypad and pres s 0 to toggle between networks e.g.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Keypad Setup Keypad Areas Keypad Speaker Volume Keypads can be assigned to any number of areas, assigning a This option controls the volume level of advisory tones from keypad to an area determines: loudspeakers connected to the keypads.
Expander Setup Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 5.5 Expander Setup E o elec:- Epande ep Us e keys 1 - 8 to select a n expander a nd pres s 0 to toggle between networks e.g.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Expander Setup Expander Areas Expander Speaker Volume Expanders can be assigned to any number of areas, assigning an This option controls the volume level of advisory tones from expander to an area determines:...
System Outputs Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 5.6 System Outputs E o elec:- yse ps yse ps anel ps Us e keys 1 - 8 to s elect a n ea:4 EHIJK output type or us e the S C R OL L key to s earc h e.g.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual System Outputs Available Outputs Output Group - System Various sets of programmable outputs can be found on the control Select an output type from the following options: panel, keypads, expanders and output modules.
Page 78
System Outputs Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 18 - UDL Lockout 37 - Custom4 Stage AB This output type activates when an attempt is made to upload/download This output type operates when ‘Custom Output 4’ Stage A or B with incorrect site details more than three times and deactivates after 4 activates and deactivates when ‘Custom Output 4’...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual System Outputs 16 - Ready Output Group - Area This output type activates when all zones in the selected area are secure and deactivates when any zone in the selected area is Any number of areas can be assigned to each output type.
Page 80
System Outputs Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 35 - 24Hr Zones Omit 54 - Zone Warning This output type activates when a zone programmed as ‘24Hr Audible’ This output type activates when ‘Custom’ zone type in the selected or ‘24Hr Silent’...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual System Outputs 70 – Confirmed PA These output types activate for the duration of the ‘Door Strike’ timer If an area is in PA alarm this output type activates when one of the when a valid User code (assigned to the same door) is entered and following happens.
System Outputs Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Custom Outputs Custom outputs are NOT physical outputs they are ‘Software outputs that can be configured to operate under certain conditions. Once configured these outputs can then be assigned to a physical output (see system outputs 22-27 and 32-37, page 78 for details).
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual UDL/Digi Options 5.7 UDL/Digi Options Reset Digi MSN/Pre-Dial No. E o elec:- E o elec:- U/igi pions U/igi pions U/igi pions U/igi pions ese igi ese igi P res s R E S E T to res et the...
UDL & Digi Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Program Digi E o elec:- U/igi pions U/igi pions ese igi U/igi pions oga igi oocol: isaled S ta rt Us e keys 0 - 4 to...
Page 85
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual UDL & Digi Options From previous page if F as t F ormat protocol is s elected Us e keys 1 - 8 to s elec t Pres s NO to edit...
Page 86
UDL & Digi Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual From previous page if C onta ct ID, S IA L evel II, E a s yC om Pager or S MS Mes s aging protocols are s elected...
Page 87
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual UDL & Digi Options The plug-on communicator can be programmed to dial up to 3 sets The following option is only displayed if Contact ID, SIA of Alarm Receiving Centre (ARC) information. Each ‘Set’ consists of the...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual UDL & Digi Options Area Accounts 640 E o elec:- U/igi pions U/igi pions ese igi U/igi pions ea ccons ea ccon: ------ Us e the S C R O LL key to search for areas .
UDL & Digi Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual UDL Options E o elec:- U/igi pions U/igi pions ese igi U/igi pions Us e k eys 0 - 9 to enter U pions the telephone number...
Page 91
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual UDL & Digi Options The system has the following UDL download options: D - Call Defeat The modem will answer incoming calls as follows: Download Call Back Number 1 This is the telephone number that is dialled by the modem when ‘Call- •...
UDL & Digi Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Setup Modules E o elec:- U/igi pions U/igi pions ese igi U/igi pions Us e k eys 0 - 9 to enter adio/ pion the telephone number...
Page 93
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual UDL & Digi Options The following options are used when a Paknet Radio-Pad is ComIP Gateway connected to the control panel in order to achieve DUAL This is the Gateway IP Address that the IP Module communicates SIGNALLING to an Alarm Receiving Centre, when a MODEM through.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual UDL & Digi Options Initial Setup DualCom® Inside (48 Only) Please follow the instructions in INS176 to install the equipment and initiate the power up sequence. When applying power for the first Aerial Siting time, the factory default settings must be loaded.
UDL & Digi Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual • Select “Enable communicator” EMIZON 21 TCD Panel IP Setup Introduction The control panel communicates to the ARC via the EMIZON TCD. The EMIZON 21 TCD is compatible with all Premier Elite Control The TCD’s primary signalling path is via an IP network;...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual UDL & Digi Options Programming the Control Panel WebWayOne Digi Options WebWayOne integration with the control panels provides the • Enable communicator must be ticked following features 7 functions:- •...
Page 98
UDL & Digi Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual ARC's “Account No:” should match the ARC Site/Chip ID and tick the relevant trigger event boxes relevant to the premises. • Connect Via IP Checked •...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual UDL & Digi Options Programming Chiron IRIS For both Alarms and Wintex upload/download the following should be programmed. The Chiron IRIS Touch range of communicators offers a way of transmitting alarm signals to an Alarm Receiving Centre (ARC) over...
UDL & Digi Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Zone Alarm Reporting Codes The Reporting codes for Contact ID and SIA are fully configurable, however these codes can only be changed using Wintex downloading software.
Page 101
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual UDL & Digi Options Zone Type Event Reporting Group Contact ID Auxiliary Alarm Alarm Tamper Alarm Restore Restore Omit Omit/Reinstate Reinstate Omit/Reinstate 24Hr Tamper Alarm Alarm Tamper Alarm Restore Restore...
Page 102
UDL & Digi Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Non-Zone Event Types The default Non-Zone Event codes are as follows: Type Event Reporting Group Contact ID Keypad Medical Alarm Priority Alarm Keypad No * Restore...
Page 103
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual UDL & Digi Options Type Event Reporting Group Contact ID Low Battery Alarm Maintenance Restore Restore System Power Up Alarm Maintenance Restore Not Reported System Over Voltage Alarm Maintenance Restore...
Page 104
UDL & Digi Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Type Event Reporting Group Contact ID NVM Defaults Loaded Alarm Not Reported Zone No Restore Not Reported Zone No First Knock Alarm Not Reported Restore Not Reported...
Page 105
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual UDL & Digi Options Type Event Reporting Group Contact ID Test Call Passed Alarm Not Reported Restore Not Reported Test Call Failed Alarm Not Reported Restore Not Reported Zone Fault...
Page 106
UDL & Digi Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Tamper Fault ID *** Reset ID **** Panel ID is transmitted as follows: Reset ID is transmitted as follows: Device Device Panel Panel (RR) Engineer Keypad ID is transmitted as follows:...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Setup Users 5.8 Setup Users Activa te the R adio F OB to Use eoe ciae eice as s ign it to the us er II E o elec:- esen...
Setup Users Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Default User Codes User Types When the control panel is first powered up and the factory default The User type determines which functions are available to the user i.e.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Setup Users User Functions and Options The table below shows the options that are available to each user. All users that have access to the ‘Arming Menu’ have the ability to ‘View Zone Status’, ‘Set Chime Areas’, ‘View Act. Faults’ and ‘View Act.
Engineer Utilities Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual R - Call Rem. PC User Options 1 The selected user has access to the ‘Call Remote PC’ option, allowing them to initiate a call to a remote upload/download PC.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Engineer Utilities choose which zones (and therefore expander) the Premier Elite User Name Text SmartKey™ will use for its routeing, LED and Aux functions can also be changed within the “Setup Users” menu.
Engineer Utilities Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 5.9 Engineer Utilities The control panel has three Event Logs, which are time and date View Event Log stamped. The first log which is a system log, records all events that occur on the system, i.e.
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Engineer Utilities Event Log Descriptions Log Event Description ### ARM FAILED An exit fault from Zone ### has caused the system to fail to arm ### Flt Alarm Zone ### has detected a Fault condition...
Page 114
Engineer Utilities Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Log Event Description PSUTam## Alarm An expander input programmed as PSU Monitor control panel has detected a Tamper condition QUICK Armed Quick Arm from keypad #,# R/Bat ## Alarm...
Engineer Utilities Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Example Ricochet Diagnostics (MT2 Only) In this example Zone 9 can see the Zone hoc devices as detailed below, use the scroll This menu displays information about the live system, and is split into _E...
Page 123
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Engineer Utilities Ricochet Diagnostics Menu E o elec:- Enginee Uils Enginee Uils ie Een og Us e to s c roll to R ic oc het Diag E o ease Zone ...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Standards 6. Specifications Control Panels Identifying the Control Panel Maximum Current Available 0.75A charge 1.0A 0.3A charge 1.9A Rated Output Rated Output (Amps) Battery Battery Arrangement Charge Type Code Description 1 x 7Ah 0.3A...
Page 126
Specifications Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual 0.3A charge 1.0A Power Supply Type A Rated Output Rated Input: 220V - 240V @50/60Hz; 1A Rated Output (Amps) Battery Battery Rated Output Current@40°C: 2.5A MAX Arrangement Charge 1 x 7Ah 0.3A...
Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual Standards Maximum Ripple Voltage: 0.5V pk-pk Siren Outputs Bell Trigger 1A switched to 0V Battery type: sealed lead acid, 18Ah, Maximum recharge time 72h Strobe Trigger 1A switched to 0V Battery Low Voltage Signal: 9.5V...
Specifications Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual any combination of the two Remote Keypads Zones 8 DP or EOL zones Electrical 60IXD 60 iD zones (2 loops) Operating Voltage 10 - 13.7VDC EOL Resistor Values (Alternatives Available)
As the control panel is not a complete alarm system but only a part thereof, Texecom cannot accept responsibility or liability for any damages whatsoever based on a claim that the control panel failed to function correctly.
Texecom Limited, Bradwood Court, St. Crispin Way, Haslingden, Lancashire BB4 4PW, England. Technical Support: UK Customers Tel: 08456 300 600 (Calls charged at local rate from a BT landline. Calls from other networks may vary.) International Customers Tel: +44 1706 233875 Email: techsupport@texe.com...