ABB SPA-ZC 402 Installation And Commissioning Manual

ABB SPA-ZC 402 Installation And Commissioning Manual

Spa tcp bridge

Advertisement

Ethernet Adapter
SPA-ZC 402
SPA-ZC 402
SPA/TCP Bridge
Installation and Commissioning Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB SPA-ZC 402

  • Page 1 Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA/TCP Bridge Installation and Commissioning Manual...
  • Page 3: Table Of Contents

    4.4. Connecting to SPA-ZC 402........19 4.4.1. Changing computer's IP address ....19 4.4.2. Checking connection to SPA-ZC 402 ....20 5. Engineering ............23 5.1. Overview of engineering ........... 23 5.2. Application notes ............. 23 5.3. Creating project ............24 5.4.
  • Page 4 Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS756019 SPA/TCP Bridge Installation and Commissioning Manual 7. Technical data ............35 7.1. Interfaces ............... 35 7.2. Test and conditions ..........36 8. Maintenance and service ......... 39 8.1. LED indicators............39 8.2. Communication settings ..........39 8.3.
  • Page 5: Copyrights

    This document and parts thereof must not be reproduced or copied without written permission from ABB Oy, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose.
  • Page 7: Introduction

    This manual This manual provides thorough information on the SPA-ZC 402 Ethernet Adapter and the central concepts related to it. SPA-ZC 402 Ethernet is used for connecting any Intelligent Electronic Devices (IED), which provides fibre-optic SPA bus, to the SPA/TCP Bridge. In the manual you find information on SPA-ZC 402 and its components, an introduction to engineering tasks and a description of the basic operations.
  • Page 8: Product Documentation

    1MRS756019 SPA/TCP Bridge Installation and Commissioning Manual 1.4. Product documentation Name of the manual Document ID SPA-ZC 402 configuration CD 1MRS151049 CAP 505 User's Guide 1MRS752292-MUM SPA-ZF Optical glass fibres, multimode granded 1MRS755371 index type Plastic-core fibre-optic cables, Features and...
  • Page 9: Revision History

    1MRS756019 Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA/TCP Bridge Installation and Commissioning Manual 1.6. Revision history Version Date History 30.06.2006 Document created 20.05.2009 SPA-ZC 402 2.1.2 additions...
  • Page 11: Safety Information

    1MRS756019 Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA/TCP Bridge Installation and Commissioning Manual Safety information Non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation. National and local electrical safety regulations must always be followed.
  • Page 13: Product Overview

    Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA/TCP Bridge Installation and Commissioning Manual Product overview SPA-ZC 402 is used to connect IEDs with the SPA protocol over the TCP/IP network using the same Ethernet link. COM600 REF 610 A090000 Fig. 3.-1...
  • Page 14: Features

    SPA/TCP Bridge Installation and Commissioning Manual Media converters: RuggedCom RMC-100-MM IMC McBasic MM1300 Allied Telesyn AT-MC302-20 More tested devices can be found on the ABB web site http://www.abb.com/substationautomation. 3.1. Features SPA-ZC 402 has the following features: Auxiliary power supply Support of communication over TCP/IP Only one SPA client can be configured to poll SPA events from the device.
  • Page 15: Transmission Control Protocol (Tcp)

    1MRS756019 Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA/TCP Bridge Installation and Commissioning Manual 3.2. Transmission Control Protocol (TCP) The Transmission Control Protocol (TCP) is the most commonly used protocol for exchanging data between communication devices using Ethernet. Unlike UDP, the TCP protocol guarantees reliable transmission between applications.
  • Page 17: Installation

    4.2. Installing communication cable Connect the fibre-optic SPA bus cable between IED and SPA-ZC 402. Connect the LAN cable to the LAN connector of SPA-ZC 402. The other end of the cable is connected to the Ethernet switch. 4.2.1. Auxiliary power connection...
  • Page 18: Installing Communication Engineering Tool For Spa-Zc 40X

    Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS756019 SPA/TCP Bridge Installation and Commissioning Manual 4.3.2. Installing Communication Engineering Tool for SPA-ZC 40x 1. Uninstall the previous version. 2. Close all the open programs and insert the Communication Engineering Tool (CET) for SPA-ZC 40x installation CD to the CD-ROM drive of your PC.
  • Page 19: Uninstalling Communication Engineering Tool For Spa-Zc 40X

    To connect SPA-ZC 402, the used computer and SPA-ZC 402 must use the same address space. To change the computer's IP address space to be the same as in SPA-ZC 402: 1. Open the Network Connections in Control Panel. 2. Type, for example, the following IP address to the IP address box: 192.168.2.1.
  • Page 20: Checking Connection To Spa-Zc 402

    Fig. 4.4.1.-1 Changing IP address 4.4.2. Checking connection to SPA-ZC 402 Check the connection to SPA-ZC 402 by using the ping command: 1. Open the Run dialog. 2. Type cmd to the Open box, see Fig. 4.4.2.-1. A060242 Fig. 4.4.2.-1 Starting command prompt 3.
  • Page 21 4. Type ping 192.168.2.10, see Fig. 4.4.2.-2. Fig. 4.4.2.-2 Pinging SPA-ZC 402 SPA-ZC 402responds to the ping command if the computer and SPA-ZC 402 are on the same network. 5. If SPA-ZC 402 responds with the IP address, the connection is established...
  • Page 23: Engineering

    5.1. Overview of engineering The engineering and maintenance of SPA-ZC 402 is done by using CET for SPA-ZC 40x functions. The device's communication structure is described in the Project Explorer dialog. The structure is built by using device objects. These objects have communication properties that can be accessed through the Object Properties dialog.
  • Page 24: Creating Project

    Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS756019 SPA/TCP Bridge Installation and Commissioning Manual Direct connection via serial cable or fibre (conventional usage of SPA bus) Conventional modem connection, when used as a direct connection, running on the SPA protocol only...
  • Page 25: Restarting

    Creating a new project 5.4. Restarting Use this function to restart the SPA-ZC 402 at runtime. 1. Select IED and Tools > Reset Tool to open the restart panel, see Fig. 5.4.-1 2. Click Reset. The results are reported to the UI text box.
  • Page 26: Building Object Tree

    Fig. 5.5.-1 shows an example of the object tree when it has been built. In the example tree you can see the SPA-ZC 402 object and its child objects as devices and data objects. Indentation is used to indicate the parent-child relationship between the objects.
  • Page 27: Adding Device Object

    1MRS756019 Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA/TCP Bridge Installation and Commissioning Manual 3. Logical Node objects 4. Data objects 5.5.1. Adding Device object To build the object tree: 1. Add a SPAZC40x_SPA Device object in the communication structure by selecting the project name.
  • Page 28: Configuring By Using Imported Cid File

    5.6. Configuring by using imported CID file If you have to configure several SPA-ZC 402 with the similar settings, it is possible to import a previously generated CID file and change the communication addresses, typically by changing the IP address.
  • Page 29: Uplink Network Settings

    SNTP Servers SPA-ZC 402 uses SNTP as its own real-time clock. The time is used to synchronize an IED with SPA. The secondary SNTP server is used if the primary SNTP server for some reason drops off the network.
  • Page 30: Communication Parameters For Spa

    Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS756019 SPA/TCP Bridge Installation and Commissioning Manual Subnet mask The Subnet mask address defines which addresses have access to the default gateway. TCP-Keepalive The status of the TCP/IP connection is monitored by transmitting keep alive- messages at configured intervals.
  • Page 31: Downloading Configuration

    1. Select the SPAZC40x_SPA Device object and right-click to select the CID Export. 2. If you download configuration to SPA-ZC 402 the first time, change the IP address from default address (192.168.2.10) to new IP address according to the planned network structure.
  • Page 32 Fig. 5.8.-1 Downloading the device's configuration If SPA-ZC 402 is connected to a system where the connection to it can be obtained, the Export function tries to determine the SPA-ZC 402 version and exports the export file accordingly. If the connection is disabled, prompt the correct version to be exported, see Fig.
  • Page 33: Commissioning

    ZC40x:XX, the SPA/TCP connection to the device is working. After that, try to send a >nnnRF:XX message, where nnn is the SPA address of the slave device connected to the serial port of SPA-ZC 402. In the reply you receive the slave’s type string.
  • Page 35: Technical Data

    See fibre-optic guides: SPA-ZF Optical glass fibres, multimode graded index type Plastic-core fibre-optic cables, features and instructions for mounting For more information, see Section 1.4. Product documentation. Diagnostic LEDs SPA-ZC 402 common diagnostic LEDs Power Diagnostic Green Yellow LAN diagnostic LEDs...
  • Page 36: Test And Conditions

    110-220 VDC, 100-240 VAC POWER LINK DIAG ETHERNET – Use M5 mounting screws A040027B Fig. 7.1.-1 Dimensions of the SPA-ZC 402 module Table 7.1.-1 Dimensions and weight Type Dimensions [mm] Weight [g] SPA-ZC 402 190 x 115 x 35 7.2.
  • Page 37: General Requirements

    1MRS756019 Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA/TCP Bridge Installation and Commissioning Manual General requirements Table 7.2.-1 Environmental test and conditions Recommended service temperature range -10...+55˚C (continuous) Limited temperature range (short-term) -40...+85˚C Transport and storage temperature range -40...+70˚C according to the IEC 60068-2-48...
  • Page 38 According to the IEC 60255-21-1, class I Shock and bump test According to the IEC 60255-21-2, class I Table 7.2.-4 Auxiliary power supplies Type SPA-ZC 402 xxxA SPA-ZC 402 xxxC Input voltage AC 110/120/220/240 V Input voltage DC 110/125/220 V...
  • Page 39: Maintenance And Service

    SPA-ZC 402 SPA/TCP Bridge Installation and Commissioning Manual Maintenance and service If the SPA-ZC 402 module or a part of it is found to be faulty, the normal service operation is to replace the entire module. 8.1. LED indicators Table 8.1.-1...
  • Page 40 Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS756019 SPA/TCP Bridge Installation and Commissioning Manual SNTP servers:10.58.125.150 127.0.0.1 SW_SPATYPE: SPA-ZC40x SW_NUMBER: 1MRS118533 SW_BUILD: 110 SW_REVISION: B Compiler DATE_TIME: Nov 28 2005 12:38:02 To use the IP Query Tool: 1. Select Tools > IP Query Tool to start the tool, see Fig. 8.3.-1.
  • Page 41: Identification

    8.4. Identification If contacting the Customer Service, it is necessary to send the following information by request: Version information of Communication Engineering Tool (CET) for SPA-ZC Select Help > About to view the version information. SPA-ZC 402 version information...
  • Page 42: Obtaining Error Logs

    Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS756019 SPA/TCP Bridge Installation and Commissioning Manual The version information can be read from the device's label. If the device is updated afterwards, use CET's IP query to get the correct version information from the device memory. For more information about IP query, refer to Section 8.3.
  • Page 43: Ordering Information

    SPA-ZC 402 configuration CD Engineering tool, Communication Engineering Tool (CET) for SPA-ZC 40x Order at least one SPA-ZC 402 configuration CD with your delivery to get the Communication Engineering Tool. The SPA-ZC 402 package does not include the configuration CD by default.
  • Page 45: Terminology

    Intelligent Electronic Device Also known as IED. Devices containing advanced logics such as meters, protection and control relays and trip units. Snap-in Connector type for plastic fibre cable Data communication protocol developed by ABB...
  • Page 47: Abbreviations

    1MRS756019 Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA/TCP Bridge Installation and Commissioning Manual Abbreviations Abbreviation Description Change detect; compact disk Communication Engineering Tool Configured IED description Data object instance Electromagnetic compatibility File transfer protocol Intelligent electronic device Internet protocol Local area network...
  • Page 52 ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa FINLAND +358 10 2211 +358 10 224 1080 www.abb.com/substationautomation...