2. Introduction ................13 2.1. SPA-ZC 400 Product Overview ...........13 2.2. Introduction to IEC 61850 standard ..........14 2.3. SPA-ZC 400-BB and SPA-ZC 400-MM Product Overview ..14 2.4. SPA-ZC 400 Features ..............15 2.5. Ordering information ..............16 2.5.1. SPA-ZC 400 product package .........16 3.
Page 4
6. Maintenance and service ............57 6.1. General about service ..............57 6.1.1. LED indicators ..............57 6.2. SPA-ZC 400 communication settings ......... 57 7. Technical reference ..............59 7.1. About this section ............... 59 7.2. ACSI conformance statement ............ 60 7.2.1.
Page 5
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.9. Complex measured value (CMV) .......77 7.3.3.10.Sampled value (SAV) .........78 7.3.3.11.WYE ..............79 7.3.3.12.Delta (DEL) ............80 7.3.3.13.Sequence (SEQ) ..........81 7.3.3.14.Harmonic Value (HMV) ........81 7.3.3.15.Harmonic value for WYE (HWYE) .....83 7.3.3.16.Harmonic value for DEL (HDEL) ......84 7.3.3.17.Controllable single point (SPC) ......85...
This document and parts thereof must not be reproduced or copied without written permission from ABB Oy, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose.
This section provides you with general information on installing the SPA-ZC 400 components. Chapter 4. Engineering In this section you will find an overview of engineering tasks of SPA-ZC 400. Chapter 5. Technical data This section provides you the SPA-ZC 400 technical data.
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 1.5. Document conventions The following conventions are used for the presentation of material: • The words in names of screen elements (for example, the title in the title bar of a dialog, the label for a field of a dialog box) are initially capitalized.
1.6. Terminology The following is a list of terms associated with SPA-ZC 400 that you should be familiar with. The list contains terms that are unique to ABB or have a usage or definition that is different from standard industry usage.
Substation Configuration description Language SNTP Simple Network Time Protocol 1.8. Related documents Name of the manual Document ID SPA-ZC 400 configuration CD 1MR151048 CAP 505 User’s Guide 1MRS752292-MUM SPA-ZF Optical glass fibres, 1MRS755371 multimode graded index type Plastic-core fibre optic cables,...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 1.9. Document revisions Version Date History 06.10.2004 Document created 1.10. Safety information Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected. National and local electrical safety regulations must always be followed.
Introduction 2.1. SPA-ZC 400 Product Overview SPA-ZC 400 is used to connect one RE_54_ device to the IEC 61850-8-1 Station bus. The IEC 61850 standard defines the IEC 61850 communication and engineering specifications. In addition to the IEC 61850-8 communication, SPA-ZC 400-BB and SPA-ZC 400-MM versions provide the simultaneous dual ®...
2.3. SPA-ZC 400-BB and SPA-ZC 400-MM Product Overview SPA-ZC 400-BB and SPA-ZC 400-MM versions have the same IEC 61850 functionality as described in Section 2.1. SPA-ZC 400 Product Overview. In addition, these versions include an optional fibre optic interface.
SPA • Support of SPA communication over TCP/IP All relay data can be routed through SPA-ZC 400. It is intended to route the process data (status, measurements and commands) through the IEC 61850-8-1 bus and the rest of the available data can be routed through SPA over TCP/IP.
• Engineering tool, Communication Engineering Tool (CET) for SPA-ZC 40x • Connectivity Packages for RE_54_ Order at least one SPA-ZC 400 configuration CD with your delivery to get the Communication Engineering Tool and the Connectivity Packages. SPA-ZC 400 packages do not include the configuration...
3.1. Mechanical Installation Connect the SPA-ZC 400 module to RE_54_ and screw SPA-ZC 400 to the 9-pin type D-connectors. Connect the fibre optic LAN cable to the LAN connector of SPA-ZC 400. The other end of the cable is connected to the IEC 61850-8 Station bus via Ethernet switch.
Page 20
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 4. Then the CET Installation program opens. In this dialog click Next, see Fig. 3.2.2.-2. With the Back button you can return to the previous dialog, and with the Cancel button exit the installation wizard. This applies to all the dialogs in the installation wizard.
Page 21
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 5. Read the License Agreement, then check the option I accept the license agreement and click Next to continue the installation, see Fig. 3.2.2.-3. If you check the option I do not accept the license agreement, the Next button is not available and you cannot continue the installation.
Page 22
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 6. Select the folder in which the application is to be installed, see Fig. 3.2.2.-4. • To select the default folder shown at the bottom of the dialog, click Next. • To select another folder, click Browse, choose the folder you want and click Next.
Page 23
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7. Both manuals are installed by default in your local hard drive, see Fig. 3.2.2.-5. By clicking Next you can continue the installation. • To install a manual, click the respective manual and select Will be installed on local hard drive.
Page 24
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 8. On this stage installation can begin, see Fig. 3.2.2.-6. Click Next to begin the installation. A040009 Fig. 3.2.2.-6 Ready to install...
Page 25
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 9. You can follow the progress of the installation in a dialog that also shows the directory path where the files are copied, see Fig. 3.2.2.-7. At this point, you can still cancel the installation by clicking Cancel.
Page 26
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 10.Then a dialog opens to show that the gateway has been successfully installed, see Fig. 3.2.2.-8. Close the dialog and finish the installation by clicking Finish. A040011 Fig. 3.2.2.-8 Installation complete 11.When clicking Finish the wizard also installs the Microsoft SQL Server...
3.3. Installing Connectivity Packages 1. Close all the open programs and insert the SPA-ZC 400 configuration CD to the CD-ROM drive of your PC. 2. Double-click the Connectivity Package installation program and select the relevant IED (.msi) to start the installation.
Page 28
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 4. Then the Connectivity Package Installation program opens. In this dialog click Next, see Fig. 3.3.-1. With the Back button you can return to the previous dialog, and with the Cancel button exit the installation wizard. This applies to all the dialogs in the installation wizard.
Page 29
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 5. Read the License Agreement, then check the option I accept the license agreement and click Next to continue the installation, see Fig. 3.3.-2. If you check the option I do not accept the license agreement, the Next button is not available and you cannot continue the installation.
Page 30
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 6. Select the folder in which the application is to be installed, see Fig. 3.3.-3. • To select the default folder shown at the bottom of the dialog, click Next. • To select another folder, click Browse, choose the folder you want and click Next.
Page 31
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7. On this stage installation can begin, see Fig. 3.3.-4. Click Next to begin the installation. A040019 Fig. 3.3.-4 Ready to install...
Page 32
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 8. You can follow the progress of the installation in a dialog, which also shows the directory path where the files are copied to, see Fig. 3.3.-5. At this point, you can still cancel the installation by clicking Cancel.
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 9. Then a dialog opens to show that the Connectivity Package has been successfully installed, see Fig. 3.3.-6. Close the dialog and finish the installation by clicking Finish. A040021 Fig. 3.3.-6 Installation complete 3.3.1.
Connectivity Package. 2. Configuring object properties, for example adding mapping to the SPA references in the IED (Intelligent Electronic Device). 3. Configuring communication addresses. 4. Exporting the configuration data to SPA-ZC 400 and to the IEC 61850 system configuration tool.
Ethernet Adapter Installation and Commissioning Manual 4.3. Creating project You need to start the SPA-ZC 400 Communication Engineering Tool (CET) to open and name a project, see Fig. 4.3.-1 and Fig. 4.3.-2. A040014 Fig. 4.3.-1 Creating a new CET project A040013 Fig.
The Fig. 4.5.-1 shows an example of how the object tree may look like when it has been built. In the example tree you can see the SPA-ZC 400 object and its child objects as devices and data objects. Indentation is used to indicate the parent-child relationship between the objects.
1. Right-click to select an IEC 61850 Device object (SPA-ZC 40x) and select New > Communication > Logical Device. This generates the mandatory logical device LD0, logical node LLN0 and its data structure for SPA-ZC 400. Logical device LD0 describes SPA-ZC 400 and includes the data objects for diagnostics and description.
Page 39
Installation and Commissioning Manual 2. Add a new Logical Device object (REF 541/3/5), see Fig. 4.5.2.-1.This is possible only after you have installed connectivity packages to your computer. The IED’s data model behind SPA-ZC 400 is described in the logical device LD1. A040024 Fig.
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual When the actual IEC 61850 data model is created the logical device name has two parts: • Device Object name • Logical Device name for example SPAZC40xLD0. 4.5.3. Importing IEC 61850 data object model of IED 1.
4.6. Configuring SPA-ZC 400 using imported CID file If you have to configure several SPA-ZC 400 with the similar IEC 61850 data object model, it is possible to import a previously generated CID file and change the communication addresses, typically by changing the IP address.
IED, SPA model and how the IED model can be converted to the IEC 61850 model. If this configuration method is used, it is recommended that you familiarize yourself with Connectivity Packages as an example. Contact ABB if you have unresolved problems.
Page 43
SPA point data properties that you can edit. SPA point data is written to the sAddr field in the CID file for the selected data object. SPA-ZC 400 uses this field to poll data and events from IED.
4.8. Configuring communication parameters SPA-ZC 400 communication parameters are located in the Device Properties. SPA-ZC 400 uses static IP addresses, which have to be defined in the planned network structure, see Fig. 4.8.-1. • IP Address IP address identifies SPA-ZC 400 in Local Area Network (LAN). All communication via SPA-ZC 400 uses this address.
SPA-ZC 400 needs also IED SPA address to access the SPA data. Every logical device has SPA Communication Parameters Object properties expect LD0, which describes the SPA-ZC 400. The SPA Address object property has to be the same as the configured SPA unit number in IED.
Page 46
SPA-ZC 400 with SNTP as it is defined in the IEC 61850-8-1 standard and SPA-ZC 400 is also synchronizing IED over SPA. • Disabled In this mode, you can only synchronize SPA-ZC 400 with SNTP and IED has a different source of time synchronization. • Read from device if supported When this operation mode is selected, the time for SPA-ZC 400 is read from IED over SPA.
Report control block (RCB) controls the spontaneous event reporting and client can modify report sending behaviour by setting RCB attributes. RCB attributes have suitable default values for following ABB products: COM 610 and MicroSCADA Pro IEC 61850-8-1 Client. RCBs locate always under the logical device LD0 and...
Page 48
Default value for Integrity Period is 0. If this attribute has value > 0 ms, SPA-ZC 400 sends a report with all data listed in linked data set with this period. By default this feature is not enabled because it generates unnecessary load to server and network.
Page 49
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual A040134 Fig. 4.10.-1 Report Control Block Buffered reporting needs mandatory Report Client definitions. Report Client definitions links certain RCB to certain client. Client can import the CID file to check what RCB instance it has to use. If Max property is defined to two, configuration must have two clients with buffered reporting.
CET asks if you are aware of it. If you accept the changed subnet, SPA-ZC 400 resets used IP address and takes the new address in to use. If you do not accept changes, SPA-ZC 400 uses the old IP address against the configuration.
You can see how the configuration process is progressing from the diagnostic LEDs. When the SPA-ZC 400 configuration is completed, then the green LED is on. If SPA-ZC 400 is online with the IEC 61850 client, you can check the general configuration status of SPA-ZC 400 from the data model LD0.LLN0.Health.stVal:...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual The q attribute quality bits of the properly updated data objects indicate GOOD or DEFAULTED. If this is not the case, SPA- ZC 400 and RE_54_ configurations are not equal. If all the data objects have INVALID quality, the SPA communication is not running.
RET 541/3/5 protection relays • D-type subminiature connector for IEC 61850 traffic • D-type subminiature connector for simultaneous dual port communication (optional, see Section 2.3. SPA-ZC 400-BB and SPA-ZC 400-MM Product Overview) IEC 61850 interface • Fibre optic LAN connector •...
Page 54
IEC 61850 MODBUS TCP DNP TCP 00-0C-02-B0-CC-00 POWER LINK DIAG SERVICE PIN 100 Base A040130 Fig. 5.1.-1 Dimensions of the SPA-ZC 400 module Table 5.1.-1 Dimensions and weight Type Dimensions [mm] Weight [g] SPA-ZC 400 195 x 50 x 26...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 5.2. Test and conditions Table 5.2.-1 Environmental test and conditions Recommended service temperature range -10...+55°C (continuous) Transport and storage temperature range -40...+70°C according to the IEC 60068-2-48 Dry heat test According to the IEC 60068-2-2...
Page 56
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 5.2.-2 Electromagnetic compatibility tests Electromagnetic emission tests According to the EN 55011 • Conducted, RF-emission (Mains terminal) EN 55011, class A, IEC 60255-25 Radiated RF-emission EN 55011, class A, IEC 60255-25...
Maintenance and service 6.1. General about service If the SPA-ZC 400 module or a part of it is found to be faulty, the normal service operation is to replace the entire module. For more details, refer to the ordering information.
Page 58
• SPA command timeout Spa command timeout should be < 1 second when LON interlocking is not in use. • SPA baud rate and SPA slave number Baud rate and slave number have to be according to the SPA-ZC 400 configuration.
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Technical reference 7.1. About this section This chapter defines the compliance to IEC 61850 in terms of service, modeling, engineering interfaces and also exceptions and local adaptations. The information gives you a detailed explanation of the IEC 61850 capabilities of a product.
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.2.2-1 ACSI models conformance statement (Continued) Client/ Server/ SPA-ZC 400/ Subscriber Publisher Comments If SVC (41/42) is supported Multicast SVC Not Supported Unicast SVC Not Supported Time Supported File Transfer Not Supported a.
Page 63
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.2.3-1 ACSI service conformance statement (Continued) Services Client Server SPA-ZC 400/ TP/MC Comments Data set GetDataSetValues Supported SetDataSetValues Not Supported CreateDataSet Not Supported DeleteDataSet Not Supported GetDataSetDirectory Supported Substitution SetDataValues...
Page 64
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.2.3-1 ACSI service conformance statement (Continued) Services Client Server SPA-ZC 400/ TP/MC Comments SetURCBValues Supported Logging Log control block GetLCBValues Not Supported SetLCBValues Not Supported QueryLogByTime Not Supported QueryLogByEntry Not Supported...
Page 65
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.2.3-1 ACSI service conformance statement (Continued) Services Client Server SPA-ZC 400/ TP/MC Comments GetUSCVCBValues Not Supported SetUSVCBValues Not Supported Control Select Supported SelectWithValue Supported Cancel Supported Operate Supported Command-Termination Supported...
Section 4.11. Downloading configuration and exporting CID file. Some of the data cannot be retrieved from the IED, but it is the default value in the SPA-ZC 400. 7.3.1. Common data attribute classes 7.3.1.1.
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.1.2. Analogue value Table 7.3.1.2-1 Analogue value AnalogueValue Type Definition Attribute Name AttributeType Value/ Value Range M/O/C SPA-ZC 400/ Comments INT32 integer value GC_1 Not Supported FLOAT 32 floating point value...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.1.5. Step position with transient indication Table 7.3.1.5-1 Step position with transient indication ValWithTrans Type Definition Attribute Name AttributeType Value/ Value Range M/O/C SPA-ZC 400/ Comments posVal INT8 -64 ... 63...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.2.1. Unit definition Table 7.3.2-3 Unit Unit Type Definition Attribute Name AttributeType Value/ Value Range M/O/C SPA-ZC 400/ Comments SIUnit ENUMERATED According to table in Supported Annex A multiplier ENUMERATED According to table in...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.3.3.1-1 Single point status (SPS) (Continued) SPS class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments subQ Quality PICS_SUBST Not Supported subID VISIBLE STRING64 PICS_SUBST Not Supported...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.3.3.2-1 Double point status (DPS) (Continued) DBS class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2) Supported...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.4. Protection activation information (ACT) The table below defines the common data class of protection activation information. Table 7.3.3.4-1 Protection activation information (ACT) ACT class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.5. Directional protection activation information (ACD) The table below defines the common data class of directional protection activation information. Table 7.3.3.5-1 Directional protection activation information (ACD) ACD class Attribute Attribute TrgOp...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.3.3.7-1 Binary counter reading (BCR) (Continued) BCR class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments Quality qchg Supported TimeStamp Supported Configuration, Description and Extension units...
Page 76
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.3.3.8-1 Measured value (MV) (Continued) MV class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments Substitution subEna BOOLEAN PICS_SUBST Not Supported subVal AnalogueValue PICS_SUBST Not Supported...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.9. Complex measured value (CMV) The table below defines the common data class of measured value. Table 7.3.3.9-1 Complex measured value (CMV) CMV class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Different variants of the type exist based on the connectivity package short address information (sAddr). Underlined information indicates the basic type. 7.3.3.10. Sampled value (SAV) The table below defines the common data class of sampled value.
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.11. The table below defines the common data class of WYE. Table 7.3.3.11-1 WYE SAV class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.12. Delta (DEL) The table below defines the common data class of delta. Table 7.3.3.12-1 Delta (DEL) SAV class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.13. Sequence (SEQ) The table below defines the common data class of sequence. Table 7.3.3.13-1 Sequence (SEQ) SAV class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments...
Page 82
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.3.3.14-1 Harmonic value (Continued) HMV class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments TimeStamp Not Supported Harmonics and Interharmonics ARRAY[0..numHar] OF dchg, Not Supported Vector...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.15. Harmonic value for WYE (HWYE) The table below defines the common data class of harmonic value for WYE. Table 7.3.3.15-1 Harmonic value for WYE (HWYE) HWYE class Attribute Attribute TrgOp...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.3.3.15-1 Harmonic value for WYE (HWYE) (Continued) HWYE class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments rmsTim INT32U AC_RMS_M Not Supported VISIBLE STRING255 Text Not Supported...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.3.3.16-1 Harmonic value for DEL (Continued) HDEL class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments angRef ENUMERATED Va | Vb | Vc | Aa | Ab | Ac |...
Page 86
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.3.3.17-1 Controllable single point (SPC) (Continued) SPC class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments Substitution subEna BOOLEAN PICS_SUBST Not Supported subVal BOOLEAN FALSE | TRUE...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.18. Controllable double point (DPC) The table below defines the common data class of controllable double point. Table 7.3.3.18-1 Controllable double point (DPC) SPC class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.3.3.18-1 Controllable double point (DPC) (Continued) SPC class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments VISIBLE STRING255 Text Supported cdcNs VISIBLE STRING255 AC_DLNDA_M Not Supported...
Page 89
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.3.3.19-1 Controllable integer status (INC) (Continued) INC class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments subQ Quality PICS_SUBST Not Supported subID VISIBLE STRING64 PICS_SUBST Not Supported...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.20. Binary controlled step position information (BSC) The table below defines the common data class of binary controlled step position information. Table 7.3.3.20-1 Binary controlled step position information (BSC) BSC class...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.3.3.20-1 Binary controlled step position information (BSC) (Continued) BSC class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments minVal INT8 Not Supported maxVal INT8 Not Supported...
Page 92
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.3.3.21-1 Integer controlled step position information (ISC) (Continued) ISC class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type Value range Comments Substitution subEna BOOLEAN PICS_SUBST Not Supported subVal ValWithTrans...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.22. Controllable analogue set point information (APC) The table below defines the common data class of controllable analogue set point information. Table 7.3.3.22-1 Analogue set point (APC) APC class Attribute Attribute...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.23. Single point setting (SPG) The table below defines the common data class of single point setting. Table 7.3.3.23-1 Single point setting (SPG) APC class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.26. Setting curve (CURVE) The table below defines the common data class of setting curve. Table 7.3.3.26-1 Setting curve (CURVE) ASG class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/ Name Type...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual 7.3.3.27. Device name plate (DPL) The table below defines the common data class of device name plate. Table 7.3.3.27-1 Device name plate (DPL) ASG class Attribute Attribute TrgOp Value/ M/O/C SPA-ZC 400/...
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual Table 7.3.3.28-1 Logical node name plate (LPL) (Continued) lnNs VISIBLE STRING255 AC_DLD_M Supported cdcNs VISIBLE STRING255 AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 AC_DLN_M Not Supported For InNs the value (val) needs to be set after specific short address (sAddr).
SPA-ZC 400 1MRS755347 Ethernet Adapter Installation and Commissioning Manual The additional MMS services, defined table below, must be supported if support for SCL.2 or SCL.3 is declared. Table 7.4.-3 Additional MMS services for SCL.2 and SCL.3 SCL conformance Client-CR Server-CR...