ABB SPA-ZC 402 Installation And Commissioning Manual

ABB SPA-ZC 402 Installation And Commissioning Manual

Spa/ethernet adapter spa to iec 61850 gateway
Table of Contents

Advertisement

Quick Links

SPA/ Ethernet Adapter
SPA-ZC 402
SPA-ZC 402
SPA to IEC 61850 Gateway
Installation and Commissioning Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB SPA-ZC 402

  • Page 1 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual...
  • Page 3: Table Of Contents

    Uninstalling Connectivity Packages....25 5.5. Connecting to SPA-ZC 402........25 5.5.1. Changing computer's IP address ....25 5.5.2. Checking connection to SPA-ZC 402 ....26 6. Engineering ............29 6.1. Overview of engineering ........... 29 6.2. Creating project ............30 6.3. Restarting............... 30 6.4.
  • Page 4 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual 6.6. Configuring by using imported CID file ......38 6.7. Configuring communication parameters ....... 38 6.7.1. SPA Communication parameters ....39 6.8. Downloading configuration and exporting CID file..41 6.8.1.
  • Page 5 1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.2.4. Protection activation information (ACT) .......... 76 11.2.2.5. Directional protection activation information (ACD)......77 11.2.2.6. Security violation counting (SEC) ..78 11.2.2.7. Binary counter reading (BCR)..79 11.2.2.8.
  • Page 7: Copyrights

    This document and parts thereof must not be reproduced or copied without written permission from ABB Oy, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose.
  • Page 9: Introduction

    SPA-ZC 402 Ethernet is used for connecting any Intelligent Electronic Devices (IED), which provides fibre-optic SPA bus, to the IEC 61850 Station bus. In the manual you find information on SPA-ZC 402 and its components, an introduction to engineering tasks and a description of the basic operations.
  • Page 10: Product Documentation

    Plastic-core fibre-optic cables, Features and 1MRS752089 instructions for mounting Connectivity Packages, User's Guide 1MRS755312 The Connectivity Packages can be downloaded on the ABB web site http://www.abb.com/ substationautomation. Related IEC 61850 standards: IEC 61850-6: Configuration description language for communication in electrical substations related to IEDs...
  • Page 11: Revision History

    Variables are shown using lowercase letters: sequence name 1.6. Revision history Version Date History 23.11.2004 Document created 30.12.2004 Ordering information updated 31.01.2005 Table 8.2.-2 Surge immunity updated 30.06.2006 SPA-ZC 402 2.0 additions 16.2.2007 SPA-ZC 402 2.1 additions 20.05.2009 SPA-ZC 402 2.1.2 additions...
  • Page 13: Safety Information

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Safety information Non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation.
  • Page 15: Quick Start

    Installation and Commissioning Manual Quick start 1. Install Communication Engineering Tool (CET) for SPA-ZC 40x and Connectivity Packages. Download the latest Connectivity Packages on the ABB web site http://www.abb.com/substationautomation. 2. Activate the appropriate Connectivity Package by using Connectivity Package Manager, see Fig. 3.-1.
  • Page 16 9. Rename the IED, for example REF545_F1. 10.Adjust IED SPA Communication parameters in the Object Properties panel. 11.Adjust network adapter's IP address to same subnet as SPA-ZC 402. To perform the operation, open Windows XP Network Connections in Control Panel.
  • Page 17: Product Overview

    Installation and Commissioning Manual Product overview SPA-ZC 402 is used to connect one IED with the fibre-optic SPA bus to the IEC 61850 Station bus. The IEC 61850 standard defines the IEC 61850 communication and engineering specifications. SPA-ZC 402 offers also the possibility to access the device with the SPA protocol over the TCP/IP network using the same Ethernet link.
  • Page 18: Features

    Easy-to-use configuration tool for the IEC 61850 data mapping Support of communication over TCP/IP All relay data can be routed through SPA-ZC 402. The process data (status, measurements and commands) is routed through the IEC 61850 bus and the rest of the available data can be routed through SPA over TCP/IP.
  • Page 19: Iec 61850 Standard

    SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040157B Fig. 4.1.-1 Parts of SPA-ZC 402 1 Ethernet connector 2 Fibre-optic SPA bus connectors 3 Auxiliary power supply connector 4 SPA TX and RX LEDs 5 LAN and diagnostics LEDs 4.2.
  • Page 20 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual The IEC 61850 standard provides: Standardized information models for all kinds of protection relays, controllers, circuit-breakers, transformers, and so on. Information exchange methods to access the information models' data: report sequences-of-events, log historical data, control devices, sampled value distribution, fast peer-to-peer process data exchange, and so on.
  • Page 21: Installation

    Connect the fibre-optic SPA bus cable between IED and SPA-ZC 402. Connect the LAN cable to the LAN connector of SPA-ZC 402. The other end of the cable is connected to the IEC 61850-8 station bus through the Ethernet switch.
  • Page 22: Installing Communication Engineering Tool For Spa-Zc 40X

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual 5.3.2. Installing Communication Engineering Tool for SPA-ZC 40x 1. Uninstall the previous version. 2. Close all the open programs and insert the Communication Engineering Tool (CET) for SPA-ZC 40x installation CD to the CD-ROM drive of your PC.
  • Page 23: Uninstalling Communication Engineering Tool For Spa-Zc 40X

    Detailed instructions for upgrading the software are provided when the upgrade is available. 5.4. Installing Connectivity Packages 1. Close all the open programs and insert the SPA-ZC 402 configuration CD to the CD-ROM drive of your PC. The Connectivity Packages can be downloaded on the ABB web site http://www.abb.com/substationautomation.
  • Page 24: Enabling Connectivity Packages

    Only one version of each Connectivity Package can be enabled at a time. 1. Double-click the icon on the computer's desktop to start the Connectivity Package Manager. 2. Select the corresponding Connectivity Package to enable it for SPA-ZC 402. 3. Click OK to apply the selection, see Fig. 5.4.1.-1.
  • Page 25: Uninstalling Connectivity Packages

    Communication Engineering Tool (CET) for SPA-ZC 40x. 5.5.1. Changing computer's IP address To connect SPA-ZC 402, the used computer and SPA-ZC 402 must use the same address space. To change the computer's IP address space to be the same as in SPA-ZC 402:...
  • Page 26: Checking Connection To Spa-Zc 402

    You must have system administration rights to perform the task. A060241 Fig. 5.5.1.-1 Changing IP address 5.5.2. Checking connection to SPA-ZC 402 Check the connection to SPA-ZC 402 by using the ping command: 1. Open the Run dialog. 2. Type cmd to the Open box, see Fig. 5.5.2.-1.
  • Page 27 4. Type ping 192.168.2.10, see Fig. 5.5.2.-2. Fig. 5.5.2.-2 Pinging SPA-ZC 402 SPA-ZC 402responds to the ping command if the computer and SPA-ZC 402 are on the same network. 5. If SPA-ZC 402 responds with the IP address, the connection is established...
  • Page 29: Engineering

    6.1. Overview of engineering The engineering and maintenance of SPA-ZC 402 is done by using CET for SPA-ZC 40x functions or by importing the existing SPA-ZC 40x CID file. The device's communication structure is described in the Project Explorer dialog. The structure is built by using device objects.
  • Page 30: Creating Project

    Fig. 6.2.-2 Creating a new project 6.3. Restarting Use this function to restart the SPA-ZC 402 at runtime. 1. Select IED and Tools > Restart SPAZC40x to open the restart panel, see Fig. 6.3.-1 2. Click Reset. The results are reported to the UI text box.
  • Page 31: Building Object Tree

    Fig. 6.4.-1 shows an example of the object tree when it has been built. In the example tree you can see the SPA-ZC 402 object and its child objects as devices and data objects. Indentation is used to indicate the parent-child relationship...
  • Page 32 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040137B Fig. 6.4.-1 Example view of the SPA-ZC 40x Communication Engineering Tool Add objects to the object tree in the communication structure by right-clicking the object to which you want to add a child object.
  • Page 33: Adding Device Object

    3. Select New > IEC 61850 > SPAZC40x_v2x, see Fig. 6.4.1.-1. Normally, the SPAZC40x_v2x template from the menu is used. Only if the connected SPA-ZC 402 is an older version 1.1.1, you have to select its own IED template SPAZC40x_v1x from the menu. This is illustrated in the following figure.
  • Page 34 Adding a new Logical Device object (for example REX 521, see Fig. 6.4.2.-1) is possible only after you have installed Connectivity Packages to your computer. The IED's data model behind SPA-ZC 402 is described in the logical device LD1. For more information about installing Connectivity Packages, refer to Section 5.4.
  • Page 35: Importing Iec 61850 Data Object Model Of Ied

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual When the actual IEC 61850 data model is created, the logical device name has two parts: Device Object name Logical Device name For example, REF543_F1LD0.
  • Page 36: Using Dataset Editor

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040026B Fig. 6.4.3.-1 Project Explorer dialog in the Communication Engineering Tool window 6.5. Using Dataset Editor The dataset groups selected data so that a client can access it easily with a single read operation.
  • Page 37 1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual groups, and functional constraint defines the data attributes. This is MMS protocol's naming feature, which is the basic part of naming and protocol definition in the IEC 61850 standard.
  • Page 38: Configuring By Using Imported Cid File

    6.6. Configuring by using imported CID file If you have to configure several SPA-ZC 402 with the similar IEC 61850 data object model, it is possible to import a previously generated CID file and change the communication addresses, typically by changing the IP address.
  • Page 39: Spa Communication Parameters

    SPA Communication parameters SPA Address SPA-ZC 402 needs also an IED SPA address to access the SPA data. Every logical device has SPA Communication Parameters Object properties except LD0, which describes the SPA-ZC 402. The SPA address object property has to be the same as the configured SPA unit number in IED.
  • Page 40 IED. IED gets the time from external source. Event poll If the parameter is disabled, SPA-ZC 402 does not poll events from IED and the IEC 61850 events are based on a continuous data poll. This feature could be used in systems where, for example the other REF 543 port is already used for the SPA communication.
  • Page 41: Downloading Configuration And Exporting Cid File

    Fig. 6.7.1.-1 SPA Communication Parameters Locally, SPA-ZC 402 uses UTC (Coordinated Universal Time) time, which is received from the SNTP time synchronization by default. This time format does not use Daylight Saving Time. If you want that the IED and SPA communication uses this time format, the IEC 61850 client has to be programmed to write the minute offset of the UTC time to the LD0.LLN0.
  • Page 42 1. Select the IEC 61850 Device object and right-click to select the CID Export. 2. If you download configuration to SPA-ZC 402 the first time, change the IP address from default address (192.168.2.10) to new IP address according to the planned network structure.
  • Page 43: Ied Application Changes

    If a new functionality is added to the IED application, the new IED application (AR file) import is needed. In this case, there are two options: Communication Engineering Tool (CET) for SPA-ZC 402 asks either the old SPA-ZC 402 application is overwritten or only the new functionality is added.
  • Page 44 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040131B Fig. 6.9.-1 LN wizard 5. Select the new logical node in the project tree. 6. Right-click the logical node and select DO Wizard to start the DO Wizard, see Fig.
  • Page 45 1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040132B Fig. 6.9.-2 DO Wizard 10.Start with the mandatory data objects and then add the process data. Mandatory data objects are Mod, Beh, Health and NamPlt.
  • Page 46 The SPA point data is written to the sAddr in the CID file for the selected data object. SPA-ZC 402 uses this field to poll data and events from the IED. In order to get automatic updating of the process objects, you should add those data objects of interest to the dataset group.
  • Page 47: Configuring Report Control Blocks

    The default value for Integrity Period is 0 ms. If this attribute has a value > 0 ms, SPA-ZC 402 sends a report with all data listed in a linked data set with this period. By default, this feature is not enabled, because it generates an unnecessary load to the server and network.
  • Page 48 SPA to IEC 61850 Gateway Installation and Commissioning Manual By default, this attribute is empty and SPA-ZC 402 uses it for RCB MMS address. If this string is left empty, a default report control block MMS path name is used.
  • Page 49 1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040134B Fig. 6.10.-2 Report Control Block Buffered reporting needs mandatory Report Client definitions. Report Client definitions link a certain RCB to a certain client. The client can import the CID file to check which RCB instance it has to use.
  • Page 50: Scales

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual 6.11. Scales To create a scale: 1. If a Scales object does not exist in the object tree, add the object by right-clicking the project and selecting New >...
  • Page 51 1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual A060132 Fig. 6.11.-2 Configuring properties 5. Create reference to scale at DO level in object tree, see Fig. 6.11.-3...
  • Page 52: Using Disturbance Recorder Files

    A relay with compatible MEDREC16 function block notifies SPA-ZC 402 when it has new recordings ready. SPA-ZC 402 reads the actual data from the relay as a background process and stores the data as COMTRADE files in its own file system...
  • Page 53 When the IEC 61850 client has been notified of the incoming record, the client should read the COMTRADE files from SPA-ZC 402 by using FTP or IEC 61850 File Transfer connection. The client must remove the files after successful reading to maintain free space for forthcoming records.
  • Page 55: Commissioning

    You can see how the configuration process is progressing from the diagnostic LEDs. When the SPA-ZC 402 configuration is completed, the green LED is on. If SPA-ZC 402 is online with the IEC 61850 client, you can check the general configuration status of SPA-ZC 402 from the data model LD0.LLN0.Health.stVal: 1.
  • Page 56: Checking Spa Communication

    If the configuration is completed successfully, you can check the resettable diagnostic counters through the IEC 61850 data model. SPA-ZC 402 Diagnostic counters are part of the LD0.CDGGIO1 logical node. The data object type is ABB-specific extension in IEC 61850 data model and contains the counters as data attributes.
  • Page 57 The q attribute reflects the status of data. If the data is properly updated, the data object's quality value is GOOD. If this is not the case, configurations between SPA-ZC 402 and IED are not identical. If all the data objects have INVALID quality, the SPA communication is not...
  • Page 59: Technical Data

    See fibre-optic guides: SPA-ZF Optical glass fibres, multimode graded index type Plastic-core fibre-optic cables, features and instructions for mounting For more information, see Section 1.4. Product documentation. Diagnostic LEDs SPA-ZC 402 common diagnostic LEDs Power Diagnostic Green Yellow LAN diagnostic LEDs...
  • Page 60: Test And Conditions

    Fig. 8.1.-1 Dimensions of the SPA-ZC 402 module Table 8.1.-1 Dimensions and weight Type Dimensions [mm] Weight [g] SPA-ZC 402 190 x 115 x 35 8.2. Test and conditions SPA-ZC 402 fulfills IEC 61850-3 Communication networks and systems in substations.
  • Page 61: General Requirements

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual General requirements Table 8.2.-1 Environmental test and conditions Recommended service temperature range -10...+55˚C (continuous) Limited temperature range (short-term) -40...+85˚C Transport and storage temperature range -40...+70˚C according to the IEC 60068-2-48...
  • Page 62 According to the IEC 60255-21-1, class I Shock and bump test According to the IEC 60255-21-2, class I Table 8.2.-4 Auxiliary power supplies Type SPA-ZC 402 xxxA SPA-ZC 402 xxxC Input voltage AC 110/120/220/240 V Input voltage DC 110/125/220 V...
  • Page 63: Maintenance And Service

    Installation and Commissioning Manual Maintenance and service If the SPA-ZC 402 module or a part of it is found to be faulty, the normal service operation is to replace the entire module. For more details, refer to Section 13. Ordering information.
  • Page 64: Ip Query

    The following IED-specific settings have to be checked when setting up REF 541/3/5, REM 543/5 or RET 541/3/5: SPA baud rate and SPA slave number in IED Baud rate and slave number have to be according to the SPA-ZC 402 configuration in X3.2/Communication 2. 9.3.
  • Page 65: Identification

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual A060128 Fig. 9.3.-2 Selecting Network adapter 3. Click Start to start the query. 4. Click Stop to stop the query. Connected devices are displayed in the Output pane, Fig. 9.3.-2.
  • Page 66: Obtaining Error Logs

    Installation and Commissioning Manual Select Help > About to view the version information. SPA-ZC 402 version information The version information can be read from the device's label. If the device is updated afterwards, use CET's IP query to get the correct version information from the device memory.
  • Page 67: Troubleshooting

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Troubleshooting Communication to SPA-ZC 40x is not working If communication problems occur, check the firewall configurations. Table 10.-1 shows the ports that have to be open in firewall.
  • Page 69: Technical Reference

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Technical reference This chapter defines the compliance to IEC 61850 in terms of service, modeling, engineering interfaces and also exceptions and local adaptations. The information gives you a detailed explanation of the IEC 61850 capabilities of a product.
  • Page 70: Acsi Conformance Statement

    . It is also possible to export the information in MICS to a CID file. The CID file can be used in the system tool, see Safety information. Some of the data cannot be retrieved from the IED, but it is the default value in the SPA-ZC 402. 11.2.1.
  • Page 71: Quality

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.1.1. Quality Table 11.2.1.1.-1 Quality Quality Type Definition Value/ Value SPA-ZC 402/ Attribute Name AttributeType M/O/C Range Comments PACKED LIST validity CODED ENUM good | invalid |...
  • Page 72: Analogue Value

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.1.2. Analogue value Table 11.2.1.2.-1 Analogue value AnalogueValue Type Definition SPA-ZC 402/ Attribute Name AttributeType Value/ Value Range M/O/C Comments INT32 integer value...
  • Page 73: Originator

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.1.6. Originator Table 11.2.1.6.-1 Step position with transient indication OriginatorType Definition SPA-ZC 402/ Attribute Name AttributeType Value/ Value Range M/O/C Comments orCat ENUMERATED...
  • Page 74: Vector Definition

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.1.8. Vector definition Table 11.2.1.8.-1 Vector Vector Type Definition SPA-ZC 402/ Attribute Name AttributeType Value/ Value Range M/O/C Comments AnalogueValue Supported AnalogueValue Not Supported 11.2.1.9.
  • Page 75: Double Point Status (Dps)

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.2.2. Double point status (DPS) The table 11.2.2.2.-1 defines the common data class of double point status. Table 11.2.2.2.-1 Double point status (DPS)
  • Page 76: Protection Activation Information (Act)

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual INS class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments Substitution subEna BOOLEAN PICS_SUBST Not Supported subVal CtxInt PICS_SUBST...
  • Page 77: Directional Protection Activation Information (Acd)

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual ACT class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments Different variants of the type exist based on the connectivity package short address information (sAddr).
  • Page 78: Security Violation Counting (Sec)

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual ACD class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments cdcNs VISIBLE AC_DLNDA_M Not Supported STRING255 cdcName VISIBLE AC_DLNDA_M Not Supported...
  • Page 79: Binary Counter Reading (Bcr)

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.2.7. Binary counter reading (BCR) Table 11.2.2.7.-1 defines the common data class of binary counter reading. Table 11.2.2.7.-1 Binary counter reading (BCR) BCR class...
  • Page 80: Complex Measured Value (Cmv)

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual MV class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments range ENUMERATED dchg normal | high | Supported low | high-high | low-low | …...
  • Page 81 1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.9.-1 Complex measured value (CMV) CMV class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
  • Page 82: Wye

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.2.10. Table 11.2.2.10.-1 defines the common data class of WYE. Table 11.2.2.10.-1 WYE SAV class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type...
  • Page 83: Sequence (Seq)

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.11.-1 Delta (DEL) SAV class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
  • Page 84: Harmonic Value (Hmv)

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual SAV class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments A | B | C | … phsRef ENUMERATED...
  • Page 85: Harmonic Value For Wye (Hwye)

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual HMV class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments cdcNs VISIBLE AC_DLNDA_M Not Supported STRING255 cdcName VISIBLE AC_DLNDA_M Not Supported...
  • Page 86: Harmonic Value For Del (Hdel)

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual HWYE class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments resHar ARRAY[0.. dchg, dupd Not Supported numHar] OF Vector...
  • Page 87: Controllable Single Point (Spc)

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual HDEL class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments phsBCHar ARRAY[0.. dchg, dupd Not Supported numHar] OF Vector phsCAHar ARRAY[0..
  • Page 88: Controllable Double Point (Dpc)

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual SPC class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments stVal BOOLEAN dchg FALSE | TRUE AC_ST Supported Quality...
  • Page 89 1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.17.-1 Controllable double point (DPC) SPC class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments DataName Inherited from Data Class (see IEC 61850-7-2)
  • Page 90: Controllable Integer Status (Inc)

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual Different variants of the type exist based on the connectivity package short address information (sAddr). Underlined information indicates the basic type. 11.2.2.18. Controllable integer status (INC) Table 11.2.2.18.-1 defines the common data class of controllable integer status.
  • Page 91: Binary Controlled Step Position Information (Bsc)

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual INC class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments maxVal INT8 Not Supported stepSize INT8U 1 ... (maxVal -...
  • Page 92: Integer Controlled Step Position Information (Isc)

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual BSC class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments subID VISIBLE PICS_SUBST Not Supported STRING64 Configuration, Description and Extension...
  • Page 93 1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.20.-1 Integer controlled step position information (ISC) ISC class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments DataName...
  • Page 94: Controllable Analogue Set Point Information (Apc)

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual Status-only is supported for the ctlModel. 11.2.2.21. Controllable analogue set point information (APC) Table 11.2.2.21.-1 defines the common data class of controllable analogue set point information.
  • Page 95: Integer Status Setting (Ing)

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.22.-1 Single point setting (SPG) APC class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
  • Page 96: Analogue Setting (Asg)

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.2.24. Analogue setting (ASG) Table 11.2.2.24.-1 defines the common data class of analogue setting. Table 11.2.2.24.-1 Analogue setting (ASG) ASG class Value/ Value...
  • Page 97: Device Name Plate (Dpl)

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual ASG class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments setParF FLOAT32 SG SE AC_NSG_O Not Supported setCharact ENUMERATED...
  • Page 98: Logical Node Name Plate (Lpl)

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual ASG class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments cdcNs VISIBLE AC_DLNDA_M Not Supported STRING255 cdcName VISIBLE AC_DLNDA_M Not Supported...
  • Page 99: Curve Shape Description (Csd)

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.3.1. Curve shape description (CSD) Table 11.2.3.1.-1 defines the common data class of curve shape description. Table 11.2.3.1.-1 Curve shape description (CSD) CSD class...
  • Page 100 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual SCL conformance Client-CR Server-CR SPA-ZC 402/ Base Value/Range Base Comments SCL.1 SCL File for Supported, CID Implementa- file export tion Available (offline) SCL.2...
  • Page 101: Scl Control Block

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.3.-3 Additional MMS services for SCL.2 and SCL.3 SCL conformance Client-CR Server-CR SPA-ZC 402/ Base Value/Range Base Comments MMS Services Not Supported...
  • Page 102: Mms Conformance

    SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.5.1.-1 A-profile support SPA-ZC 402/ Client Server Comments Client/Server A- Supported Profile GOOSE/GSE Not Supported Management A- Profile GSSE A-Profile Not Supported...
  • Page 103 1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Subscriber Publisher SPA-ZC 402/Comments GSENotSupported Not Supported GOOSE Control Block (GoCB) Not Supported Must be m if support is declared within ACSI basic conformance.
  • Page 105: Kema Certificate

    1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual KEMA certificate A060010...
  • Page 107: Ordering Information

    SPA-ZC 402 configuration CD Engineering tool, Communication Engineering Tool (CET) for SPA-ZC 40x Order at least one SPA-ZC 402 configuration CD with your delivery to get the Communication Engineering Tool. The SPA-ZC 402 package does not include the configuration CD by default.
  • Page 109: Terminology

    Furthermore, they can be used as IED internal identification for the attribute. Snap-in Connector type for plastic fibre cable Data communication protocol developed by ABB...
  • Page 111: Abbreviations

    Supervision, control and data acquisition Substation configuration description language (defined by IEC 61850) SNTP Simple Network Time Protocol Data communication protocol developed by ABB Structured query language Straight-tip; a connector type for fibre optic cable Shielded twisted pair Universal time clock...
  • Page 112 ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa FINLAND +358 10 2211 +358 10 224 1080 www.abb.com/substationautomation...