General Cabling Requirements; D.20 Link - GE D20MX Instruction Manual

Hide thumbs Also See for D20MX:
Table of Contents

Advertisement

CHAPTER 3: CONNECTING TO DEVICES AND NETWORKS

General cabling requirements

Serial

D.20 Link

D20MX INSTRUCTION MANUAL
Table 12 lists the cables required to connect to the D20MX:
Table 12: Connection cables
Media
Serial
D.20 Link
Twisted Pair Ethernet
(GE part number 526-3001 only)
Fiber optic
(GE part number 526-3003 and
526-3005LF only)
To provide higher EMC immunity and maintain CE Mark radiated emission compliance, the
serial cables used for permanent serial and D.20 Link connections must comply with the
following requirements:
Cables must be shielded
D-type connector covers must provide EMC shielding (e.g. metallized plastic or die cast
metal covers).
Seven serial communications ports are brought out to the backplane connector P2. These
serial ports are five-signal (TXD, RXD, RTS#, CTS#, DCD#) DTE serial ports, compliant to
ANSI/TIA-232 and TIA/EIA-694 specifications and are hosted by UARTs.
The D20MX is tested with all 7 serial ports running at 19200 baud with 20% CPU utilization.
Refer to application configuration guides for supported baud rates and for data bits.
To avoid burning out the WESTERM or D20MX mainboard when directly connecting a rear-
panel serial port on one D20MX chassis to another rear-panel serial port on any type of
D20 chassis, jumper the WESTERM of both chassis' to not provide a power connection to
pin 4. Refer to the appropriate WESTERM module layout for jumper settings.
Communications between the D20 and the D20 peripheral I/O modules are carried over a
high-speed, high-level data link control (HDLC) protocol called the D.20 Link. The D.20 Link
has the following features:
RS-485 serial link, half duplex, 250 kbps
D.20 frame using HDLC protocol format with Manchester encoding
Supports up to 38 D20 I/O peripheral modules in a standard configuration
Designation
Cabling
RS-232
Shielded
RS-485
Shielded
2 wire
10/100/1000BASE-T UTP (Unshielded Twisted
Pair) – CAT 5 or better
100BASE-FX
1300 nm, 50/125 μm and
62.5/125 μm multimode
duplex fiber cable
GE INFORMATION
Connector
DB-9 female
DB-9 female
RJ-45
ST-style
connectors
43