ADEMCO VISTA-20SE Installation Instructions Manual
ADEMCO VISTA-20SE Installation Instructions Manual

ADEMCO VISTA-20SE Installation Instructions Manual

2-partitioned security system
Hide thumbs Also See for VISTA-20SE:
Table of Contents

Advertisement

VISTA-20
SE
2-PARTITIONED

SECURITY SYSTEM

INSTALLATION
INSTRUCTIONS
®
Principal changes between the VISTA-20SE and the
former VISTA-20 are indicated by margin lines.
N7526V4 Rev B 4/99
WWW.DIYALARMFORUM.COM

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VISTA-20SE and is the answer not in the manual?

Questions and answers

Summary of Contents for ADEMCO VISTA-20SE

  • Page 1: Security System

    VISTA-20 2-PARTITIONED SECURITY SYSTEM INSTALLATION INSTRUCTIONS ® Principal changes between the VISTA-20SE and the former VISTA-20 are indicated by margin lines. N7526V4 Rev B 4/99 WWW.DIYALARMFORUM.COM...
  • Page 2: Recommendations For Proper Protection

    RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations For The Location Of Fire And Burglary Detection Devices Help Provide Proper Coverage For The Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS Section 1. GENERAL DESCRIPTION ..................... 7 Section 2. INSTALLING THE CONTROL ..................10 Mounting the Cabinet......................10 Installing the Lock (if used) ..................... 10 Mounting the Control's Circuit Board Alone in the Cabinet........... 11 Mounting Control and RF Receiver Circuit Boards Together in the Cabinet ....11 Standard Phone Line Connections..................
  • Page 4 Section 8. 4285 PHONE MODULE ....................32 Installing the Phone Module ..................... 32 General Information ....................... 32 Mounting The Phone Module ..................32 Phone Module Wiring ..................... 33 Caller ID Units ....................... 33 Checking the Operation of the 4285 Phone Module............35 Section 9.
  • Page 5 Figure 20. Connection of AAV Unit When Not Using a 4285 Phone Module... 40 Figure 21. Connection of AAV Unit When Also Using a 4285 Phone Module . 40 Figure 22. VISTA-20SE Summary of Connections ....Inside Back Cover WWW.DIYALARMFORUM.COM...
  • Page 6: Conventions Used In This Manual

    These prompts are shown in a double-line box. ✱ When programming the system, data fields are ✱ indicated by a “star” ( ) followed by the data field number. PRODUCT MODEL NUMBERS: Unless noted otherwise, references to specific model numbers represent Ademco products. WWW.DIYALARMFORUM.COM –6–...
  • Page 7: Section 1. General Description

    Section 1. GENERAL DESCRIPTION The VISTA-20SE is a 2-partition control that supports up to 32 zones, using basic hard- wired, wired expansion, and/or wireless zones, plus 3 keypad activated zones. Basic Hardwired Zones Provides 8 basic hardwired zones having the following characteristics: •...
  • Page 8 1321 AC transformer. Optional Phone Module • Supports the Ademco 4285 Phone Module on Partition 1 only. • Provides access to the system via on premises or off-premises phones for arming, disarming, etc., plus control of relay outputs and Powerline Carrier devices.
  • Page 9 For programming from a keypad, a 5137AD or 6139 2-line Alpha keypad must be connected to partition 1 (but need not necessarily stay in the system). Communication Formats Supported • Ademco Low Speed (Standard or Expanded) • Sescoa/Radionics (Standard or Expanded) • Ademco Express • Ademco Contact ID...
  • Page 10: Section 2. Installing The Control

    LED in the receiver after it is operational (random flicker is OK). Installing the Lock (if used) Use an Ademco No. N6277 Cam Lock and No. N6277–1 Push-On Clip (Retainer Clip). Note: The cabinet can be closed and secured without a lock by using 2 screws in the cover's edge.
  • Page 11: Mounting The Control's Circuit Board Alone In The Cabinet

    Mounting The Control's Circuit Board Alone in The Cabinet (Fig. 2) 1. Hang two short Black mounting clips (provided) on the raised cabinet tabs (see Detail B in Fig. 2). 2. Insert the top of the circuit board into the slots at the top of the cabinet. Make sure that the board rests on the correct row (see Detail A ).
  • Page 12: Standard Phone Line Connections

    Standard Phone Line Connections The wiring connections shown here are not applicable if the 4285 Phone Module is used. Refer to the 4285 Phone Module section for information regarding phone line connections, which are different than those shown here. Incoming phone line and handset wiring is connected to the main terminal block (via a RJ31X jack) as follows (also see Figure 4): Term.
  • Page 13: Installing The Back-Up Battery

    b. Wire the other three terminals (Sync, Data, Com) on the 4300 transformer. Wires from these terminals must be connected to a 9-pin connector on the control board (using a 4142TR cable supplied with the 4300 transformer), as shown in Figure 5. These particular wires can be 24 gauge or larger, and can be run along with the AC and ground wires to the control panel.
  • Page 14: Installing Remote Keypads

    Section 3. INSTALLING REMOTE KEYPADS This section lists the wired keypads that may be used and provides instructions for wiring and mounting the keypads. A preliminary check-out procedure is also provided to ensure that the connected keypads are functioning properly in the system. Keypads That May Be Used •...
  • Page 15: Mounting The Keypads

    3. Connect remote Keypads for Partition 1 to terminals 4, 5, 6, and 7 on the control board, as shown in Figure 6. 4. Connect remote Keypads for Partition 2 to the 4-pin connector on the control board (see the Summary of Connections diagram for location of the 4-pin connector for partition 2).
  • Page 16: Preliminary Check-Out Procedure

    SUPPLEMENTARY CONTROL POWER SUPPLY TERMINAL STRIP – AUX AUX. DATA DATA – IMPORTANT: MAKE THESE CONNECTIONS DIRECTLY TO SCREW TERMINALS AS SHOWN. Figure 7. Using A Supplementary Power Supply For Keypads Preliminary Check-out Procedure If you want to check that the system is working before connecting field wiring from zones and devices, do the following: 1.
  • Page 17: Basic Hard-Wired Zones 1-8

    In UL installations, only zone 1 may be used as a Fire zone. In addition, an Ademco Model 610–7 must be used as an End-of -Line resistor at the last detector. The alarm current provided by zone 1 will support only one smoke detector in the alarmed state.
  • Page 18: Turning Off Fire Alarm Sounding

    Turning Off Fire Alarm You can turn off Fire alarm sounding by pressing the OFF key on any keypad or Sounding other arming/disarming device in that partition. To clear the "memory of alarm" and to reset the detector’s alarm, enter the security code plus OFF again. COMPATIBLE 2-WIRE SMOKE DETECTORS System Sensor System Sensor...
  • Page 19: Wiring 2-Wire Latching Type Glass Break Detectors On Zone 8

    COMPATIBLE 4-WIRE SMOKE/COMBUSTION DETECTORS 1412 System Sensor, 4-wire ionization products of combustion detector 2412 System Sensor, 4-wire photoelectric smoke detector 2412TH System Sensor, 4-wire photoelectric smoke detector w/135º F (57º C) heat detector A77–716B System Sensor, EOL relay module (supervisory module for wired 4-wire fire zone).
  • Page 20: Check-Out Procedure For Hard-Wired Zones

    Programming Hard-Wired Zones Each zone must be programmed into the system using the *56 Zone Programming mode, which assigns characteristics that define the way the system responds to faults on that zone. Refer to the Zone Response Type section and the Zone Programming section for specific instructions on programming hard-wired zones.
  • Page 21: Wired Zone Expansion (4219, 4229)

    Section 5. WIRED ZONE EXPANSION This section provides information regarding the use of expansion modules for expanding the number of wired zones in the system, the modules that can be used and their wiring connections. Installing Zone Expansion Units You can add an additional 8 wired EOLR zones to the basic control's 8 zones, for a total of 16 wired zones, by using a No.
  • Page 22: Check-Out Procedure For Wired Expansion Zones

    Programming Wired Expansion Zones Each zone must be programmed into the system using the *56 Zone Programming mode, which assigns characteristics that define the way the system responds to faults on that zone. Refer to the Zone Response Type section and the Zone Programming section for specific instructions on programming wired expansion zones.
  • Page 23: Wireless Zone Expansion (5800 System)

    Section 6. WIRELESS EXPANSION (5800 SYSTEM) This section provides instructions for installing 5800 series wireless receivers and transmitters. General Information In addition to its basic wired zones, the control supports up to 24 wireless zones using an appropriate 5881 (5882 in Canada) type RF receiver. The actual number of zones supported depends on whether you are using a wired zone expander module.
  • Page 24: Installation And Setup Of The 5881/5882 Receiver

    Installation and Setup of the 5881/5882 Receiver 1. Set the receiver's DIP switch for device address “0”, as described in its instructions (all switches to the right. . . “off”). 2. Mount the receiver. The RF receiver can detect signals from transmitters within a nominal range of 200 feet.
  • Page 25: Installing The 5800Tm Module

    YELLOW (Data from Control) Terminal 7 BLUE: Not Used Do not cut any of the jumpers on the 5800TM when using it with the Vista-20SE. For additional information, refer to the 5800TM’s instructions. 5800 Series Transmitters General 5800 series transmitters have built-in serial numbers that must be "enrolled"...
  • Page 26: Transmitter Input Types

    Transmitter Input Types All of the transmitters described have one or more unique factory assigned input (loop) ID codes. Each of the inputs requires its own programming zone (e.g., a 5803's three inputs require three programming zones). See APPENDIX A toward the end of this manual. Transmitters can be enrolled as one of the following types: Type Description...
  • Page 27: 5800 Series Transmitters Table

    5800 Series Transmitters Table Also refer to APPENDIX A near end of this manual for transmitter input loops/button locations. Model Description Input Type And Special Notes 5801 Wireless Panic • Unit has 4 pushbuttons, each with a unique Input (loop) code. Transmitter •...
  • Page 28 Installing 5800 Series Transmitters To be sure reception of the transmitter's signal at the proposed mounting location is adequate, perform a Go/No Go test. Go/No Go Test Mode The Go/No Go tests will verify adequate RF signal strength from the proposed transmitter location, and allow you to reorient or relocate transmitters if necessary, before mounting the transmitters permanently.
  • Page 29: Relay Outputs & Powerline Carrier Devices

    Section 7. RELAY OUTPUTS & POWERLINE CARRIER DEVICES Relay/Powerline Carrier Device Basics Relays and Powerline Carrier devices (ex. X-10 brand devices) are programmable switches that can be used to perform many different functions. They can be used to turn lights on and off, control sounders, or for status indications.
  • Page 30: Powerline Carrier Devices

    4229 RELAY DIP SWITCH RELAY CONNECTOR FOR SETTING ADDRESS AND ZONE “A” RESPONSE EITHER OR BOTH CAN BE USED TERMINALS ON RELAY CONTROL PANEL NO C NC 4-PIN CONSOLE PLUG GRN DATA OUT (TERM 6) TAMPER JUMPER POSITION TO CONTROL 4229 IN CABINET (–) GROUND (TERM 4)
  • Page 31: Wiring Connections

    Wiring Connections 1. Splice one end of a 3-conductor cable to the wire ends of the 4142TR cable supplied with the 4300 transformer. 2. Connect the 4142TR cable plug to the 9-pin connector on the control (see SUMMARY OF CONNECTIONS diagram for location of the 9-pin connector).
  • Page 32: Section 8. 4285 Phone Module

    Module Installing the Phone Module General Information The 4285 Phone Module is an add-on accessory for the VISTA-20SE that permits access to the security system via a Touch-tone phone (either on premises or by a call-in when away). The Phone Module can announce many of the same words that would normally be displayed on an Alpha keypad under the same system conditions.
  • Page 33: Phone Module Wiring

    Phone Module Wiring The 4285 is wired between the control panel and the premises handset(s). It listens for touch tones on the phone line and reports them to the control panel. During on-premises phone access, it powers the premises phones; during off-premises phone access, it seizes the line from the premises phones and any answering machines.
  • Page 34: Figure 16. 4285 Phone Module Wiring Connections

    4285 WIRING NOTES: 1. Wire the 4285 Phone Module exactly as shown, using a direct-connect cord and RJ31X jack. 2. If Touch-tones are not heard when pressing keys following phone access to the security system via an on-premises phone, try reversing the pair of wires connected to terminals 3 & 4 on the 4285, and the pair of wires connected to terminals 21 &...
  • Page 35: Checking The Operation Of The 4285 Phone Module

    Programming the 4285 Phone Module The system must be programmed for use with the 4285 Phone Module, including assigning a phone code and selecting words from the alpha vocabulary. Refer to the Programming sections for specific programming details. Checking the Operation of the 4285 Phone Module To Check Phone Module Operation From an On-Premises Phone: 1.
  • Page 36: Section 9. External Sounders

    Section 9. EXTERNAL SOUNDERS This section provides a list of compatible sounders and connection information for an external sounder. Compatible Sounders Ademco AB-12M 10” Motor bell & box. UL Grade A. 100 mA Motorized Bell & Box current draw. Ademco 1011BE12M Motor bell &...
  • Page 37: Sounder Connections

    Sounder Connections The VISTA-20SE provides a 12 VDC output which can power external alarm sounders (bells or sirens, see compatible sounders listed previously). This output will activate a sounder when an alarm occurs in partition 1 or 2. Make connections to alarm output terminals 3 (+) and 4 (–). See Figure 17.
  • Page 38: Section 10. Long Range Radio

    Section 10. LONG RANGE RADIO General Information Check availability of Models 7720 PLUS or 7820 long range radios. If output to long range radio is selected, all messages that are programmed to go to the primary telephone line receiver will also be sent to the 7720 PLUS or 7820 long range radio.
  • Page 39: Section 11. Audio Alarm Verification (Aav) Unit

    Section 11. AUDIO ALARM VERIFICATION (AAV) UNIT General Information An Audio Alarm Verification (AAV) module, such as the Eagle 1241 , is an add-on accessory that permits voice dialog between an operator at a central station and a person at the alarm installation, for the purpose of alarm verification.
  • Page 40: Figure 20. Connection Of Aav Unit When Not Using A 4285 Phone Module

    INCOMING TELCO LINE DIRECT CONNECT CORD RJ31X ➧ RING JACK PREMISES ANSWERING MACHINE AND PLUG PHONES ANSWERING TERMINALS MACHINE ➡ ON CONTROL EARTH GROUND ▲ REFER TO AAV MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE INPUT TRIGGER EAGLE SECURITY RING (TO TERM.
  • Page 41: Section 12. Final Power Up

    Section 12. FINAL POWER UP This section provides information about final power-up procedures and battery size calculations. Earth Ground Connections The designated earth ground terminal (25) must be terminated in a good earth ground for the lightning transient protective devices in this product to be effective.
  • Page 42: Making The Battery Connections

    Making the Battery Connections 1. Use the battery standby formula (above) to select the appropriate battery for the installation. Do not connect the battery until all devices have been wired to the control. 2. Attach the Red and Black wires on the battery connector cable as follows: a) Red to the positive (+) battery tab on the control board.
  • Page 43: Section 13. Mechanics Of Programming

    Section 13. MECHANICS OF PROGRAMMING This section provides information on how to use the system's programming modes. It will enable you to understand how to enter and exit programming mode, and how to program the data fields and how to use the user-friendly ✱...
  • Page 44: Reviewing A Data Field/Erasing An Entry In A Data Field

    3. If the number of digits that you need to enter in a data field is less than the maximum digits available (for example, the phone number field), enter ✱ ] and the next data field number to be the desired data, then press [ programmed.
  • Page 45: Section 14. Zone Response Type Definitions

    Section 14. ZONE RESPONSE TYPE DEFINITIONS General Information You must assign a zone type to each zone, which defines the way in which the system responds to faults in that zone. Zone types are defined below. Type 00 Program a zone with this zone type if the zone is not used. Zone Not Used Type 01 This zone type provides exit and entry delays whenever the zone is faulted if...
  • Page 46 Type 06 This zone type sends a report to the Central Station but provides no keypad display or sounding. This zone type is usually assigned to a zone containing 24-hour Silent Alarm an Emergency button. Type 07 This zone type sends a report to the Central Station, and provides an alarm sound at the keypad, and an audible external alarm.
  • Page 47: Section 15. Data Field Descriptions

    Section 15. DATA FIELD DESCRIPTIONS Descriptions of System Data Fields THE BLANK PROGRAMMING FORM SHOULD BE USED TO RECORD THE DATA FOR THIS INSTALLATION Defaults (where applicable) Are Indicated In Text The following pages list all data fields in this control (in numerical order). If you have performed the programming instructions that were included with the installation of each of the various peripheral devices covered in previous sections, this table will simply serve as a reference for all data fields in the system.
  • Page 48 ✱ POWERLINE CARRIER DEVICE (X-10) HOUSE ID Powerline Carrier devices require a House ID. This field identifies this House ID to the control. ✱ If Powerline Carrier devices are used, they are selected in field House ID is entered in following manner: 0 = A, 1 = B, 2 =C, 3 = D, 4 = E, 5 = F, 6 = G, 7 = H, 8 = I, 9 = J, # + 10 = K, # + 11 = L, # + 12 = M, # + 13 = N, # + 14 = O, # + 15 = P.
  • Page 49 ✱ ALARM BELL TIMEOUT 0 = No timeout 1 = 4 min 2 = 8 min 3 = 12 min 4 = 16 min This field determines whether the external sounder will shut off after time allotted, or continue until manually turned off. UL installations: must be set for a minimum of 4 min (option 1) ✱...
  • Page 50 0 in the subscriber account number, ✱ REPORT FORMAT and do not use digits A-F 0 = 3+1; 4+1 ADEMCO Low Speed Standard Prim. Sec. anywhere in the number. Some paging systems provide 1 = 3+1; 4+1 Radionics Standard...
  • Page 51 Alarms, Open/Close for users 5-25 ‡ , All reports except Open/Close Troubles † Can only be used is primary reporting format is Ademco Contact ID. See explanation of pager report format below. ‡ Will report users 5-16, and, if using wireless button-type devices, will report the zone number of the arm or disarm button (10-25).
  • Page 52 An entry of "0" in the second box will eliminate the expanded message for that report. With Ademco Contact ID Reporting: Enter a digit in the first box to enable the zone to report. Use a different digit for each zone until you have used up available digits.
  • Page 53 SYSTEM STATUS ✱ EXIT ERROR REPORT CODE (See box on previous page) REPORT CODES If the system is armed and an Entry/Exit or Interior zone is still open ✱ ✱ 59– after the exit delay time has expired, an alarm will sound at the keypad and external sounder (keypad also displays “Exit Alarm”).
  • Page 54 ✱ RF XMTR LOW BATTERY REPORT CODE 0 | 0 This is sent in the event that a wireless transmitter low battery condition exists. (See box) ✱ CANCEL REPORT CODE (See box on previous page.) 0 | 0 This is sent upon disarming of the system after an alarm condition was reported.
  • Page 55 The default of “3” = alarm/alarm restore (1) plus trouble/trouble restore (2). The VISTA-20SE system has the ability to record various events in a history log (48-event capacity). The types of events to be logged can be selected as indicated. At any time, the downloader operator can then upload the log and view or print out all or selected categories of the log.
  • Page 56 ✱ RING DETECTION COUNT FOR DOWNLOADING 0-15 = number of rings before control picks up phone line Refer to the chart below and program this field accordingly. NOTE: If "15" is Phone Answering Field ✱ 95 entered in field *95 to Module Machine Downloading...
  • Page 57: Section 16. Zone Programming (*56 Menu Mode)

    Section 16. ZONE PROGRAMMING (*56 Menu Mode) ✱ While in program mode, press 56 to enter Zone Programming Menu Mode. Refer to the zone assignment table for 56 on the separate programming form . This is an interactive menu mode that is used to program zone numbers, zone types, partition numbers, alarm and report codes, and to identify the type of loop input device.
  • Page 58 Zone Number (Zn): Enter the zone number that you wish to Enter Zn Num. ✱ program (or 00 to exit zone programming). Press [ ] to continue. (00 = Quit) ↑ Zone 20 entered A summary display appears, showing the status of that zone's Zn ZT P RC In: L programming.
  • Page 59 Loop number (LP#): Enter the loop number (1-4) for the zone of the 10 INPUT DEV: LP# transmitter being enrolled. The default is loop "1." To accept this, RF TRANS. RF: 1 ✱ press [ ]. If a different loop number is being used on this transmitter, ✱...
  • Page 60 The summary screen for the zone will appear. Note that an "s" ZN ZT P RC IN: L indicates that a serial number has, in fact, been enrolled. The cursor 10 03 1 00 RF: 1 s ✱ will be flashing above the loop number. Press [ ] to accept the zone information.
  • Page 61: Section 17. Output Devices (*80 Menu Mode)

    Section 17. OUTPUT DEVICES (*80 Menu Mode) Programming Options Defined The following will help you understand the programming of Output Devices ✱ ✱ when using 80 and 81 modes. The options used to start and stop these devices are described below, followed by the actual screen prompts and available entries.
  • Page 62 If a "SYSTEM OPERATION" is chosen (e.g., End of Exit Time), that operation will cause the device to activate as selected in "ACTION.” The different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in “Programming Output Relays & Powerline Carrier devices” later in this section, and in the Programming Form.
  • Page 63 Programming Output Relays and Powerline Carrier Devices While in program mode, press ✱ 80 to enter Output Device Menu Mode. This mode is used to program all output devices used in the system (4229 or 4204 Relay modules, or Powerline Carrier devices). Refer to the output device table for 80 on the separate programming form when...
  • Page 64 Enter (if applicable) the partition number 1 or 2 (or 0 for any). 02 Start: Part ✱ Press the [ ] key to continue. Any Partition If a zone list will be used to STOP, or restore, the device action, enter the zone 02 Stop: Zn List ✱...
  • Page 65: Section 18. Zone Lists (*81 Menu Mode)

    Section 18. ZONE LISTS (*81 Menu Mode) While in program mode, press ✱ 81 to enter Zone List Menu Mode. This ✱ mode is used to program zone lists for output devices (programmed in menu mode) and/or for defining a common zone. Refer to the Programming ✱...
  • Page 66: Section 19. Alpha Description Programming (*82 Menu Mode)

    . The Phone Module will not provide annunciation of the other words. If a 4285 Phone Module is added to an existing VISTA-20SE system, the Alpha descriptors presently in the system should be re-programmed, selecting from those words shown in boldface type in the Alpha Vocabulary list. The Phone Module will not provide annunciation of any other words.
  • Page 67 Summary Mode Display If a descriptor was not entered Default Descriptor previously for zone 1, the default ✳ ZN 0 1 ZO NE 0 1 descriptor for zone 1 will be displayed. Note that this a “summary mode”, and that no entries can be made. Entries can be made only when the display contains a flashing cursor, which signifies the “entry mode”.
  • Page 68 9. Press “6” to accept the selected ✳ ZN 0 1 B A CK word. DO O R NOTE: If these are the only words are using for the descriptor, press “8 ” instead of “6 ” to save them Flashing Cursor if “6”...
  • Page 69: Adding Custom Words

    Adding Custom Words (will not be annunciated by 4285 Phone Module) You can add up to 10 installer-defined words to the built-in vocabulary. Each of the 10 "words" can actually consist of a "word string" of one or more words, but no more than ten characters can be used for each word or word string.
  • Page 70: Alpha Vocabulary List (For Entering Zone Descriptors)

    ALPHA VOCABULARY LIST (For Entering Zone Descriptors) NOTE: The list below is a revised vocabulary list which differs from earlier versions of the VISTA-20. Use only this list when programming VISTA-20SE zone descriptors. (Word Space) LOOP SHOCK • 227 • 170 SHOP •...
  • Page 71: Section 20. Using Sequential Mode (*83 Menu Mode)

    Section 20. USING 83 SEQUENTIAL MODE ✱ ✱ 83 Sequential mode when a wireless transmitter is to be physically added, removed, or simply changed (as when replacing a unit that has a non-removable battery). By using this mode, you can add, delete, or change the serial number of a transmitter in a zone, but retain all other existing data that has been programmed for that zone.
  • Page 72 5. This prompt is displayed when the system has found the next zone 10 INPUT S/N: L which needs to be enrolled. The system will respond to the first serial Axxx xxxx ✱ number transmitted after the [ ] key on the keypad is pressed. A serial number may be enrolled by one of two methods: a) Enter the 7 digit serial number printed on the transmitter b) Activate the transmitter by faulting or restoring the input you wish...
  • Page 73 When the system sees activity on the appropriate input, it will beep 10 CONFIRMED ✱ three times and display the confirmation message. Press [ ] or the A022-4064 3 upper left-hand button of the program tool to when you are ready to enroll the next transmitter.
  • Page 74: Section 21. Remote Programming And Control (Downloading)

    Section 21. REMOTE PROGRAMMING AND CONTROL (DOWNLOADING) General Information The VISTA-20SE can be remotely programmed from an IBM compatible Personal Computer (PC), a HAYES Modem, and Ademco's V-LINK® Software (as specified below). Downloading may only be performed if a technician is at the site.
  • Page 75: Remote Programming Information

    Remote Programming Information The downloading system can perform many functions when in communication with the control unit. Besides uploading and downloading, the status of the system can be observed and various commands can be initiated, as follows: • Arm the System in the Away Mode; Disarm the System. •...
  • Page 76: Section 22. System Communication

    Section 22. SYSTEM COMMUNICATION This section provides an explanation of formats this system accommodates for reporting alarms and other system conditions to the central station. The process of a successful transmission consists of both the method of communication between the control panel and the central station receiver and the actual way the information is sent and displayed at the central station.
  • Page 77 This is the “expanded” digit. 4+2 Format Comprises a 4-digit subscriber number and 2-digit report code. Ademco Contact ID Comprises a 4-digit subscriber number, 1-digit event qualifier Reporting Format ("new" or "restore"), 3-digit event code, 2-digit Partition No., and 3-digit zone number, user number, or system status number (see the following page).
  • Page 78: Table Of Contact Id Codes

    Ademco Contact ID Reporting takes the following format: CCCC Q EEE GG ZZZ where: CCCC = Customer (subscriber) ID Q = Event qualifier, where: E = new event , and R = restore EEE = Event code (3 hexadecimal digits) Note: For a complete list of event codes, refer to the central office receiver manual.
  • Page 79: Section 23. System Operation

    Section 23. SYSTEM OPERATION Security Codes Installer Code The installer programs the 4-digit Installer Code initially as part of the programming procedure. The factory default Installer code is " 4-1-1-2 ", but ✱ may be changed in field The Installer code is the only code that can enter programming mode and also, in normal operation mode, is used to enter the Master code for each partition, which allows access to the normal functions of the system.
  • Page 80: Keypad Functions

    Keypad Functions ✱ General Information Note that if you enabled QUICK ARM for the partition (field 21), the [#] key can be pressed instead of entering the partition's security code, for any of the arming procedures (Away, Stay, Instant, Maximum, etc.). The security code is always required, however, when disarming the system.
  • Page 81 Panic Keys There are three panic key pairs or (on some keypads) lettered keys that, if programmed, can be used to manually initiate alarms and send a report to the central station. Each can be individually programmed for 24-hour Silent, Audible, Personal or Fire Emergency responses.
  • Page 82: Trouble Conditions

    Trouble Conditions (See Troubleshooting Guide also) General Information The word "CHECK" on the Keypad's display, accompanied by a rapid "beeping" at the Keypad, indicates that there is a trouble condition in the system. The audible warning sound can be silenced by pressing any key. Instruct users to call for service immediately upon seeing any of the following messages.
  • Page 83: Section 24. Testing The System

    Section 24. TESTING THE SYSTEM Test Procedure After installation is completed, each partition of the Security System should be carefully tested, as follows. 1. With the System in the disarmed state, check that all zones are intact. If a ✱ NOT READY message is displayed, press the [ ] key to display the faulted zone(s).
  • Page 84: To The Installer

    • When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter are cleared. This also applies to 5816 and 5817 transmitters which have multiple loops (zones). • Any transmitter that is not “enrolled” will not turn off its zone number. Exit this mode by keying Installer code + OFF.
  • Page 85: Section 25. Troubleshooting Guide

    1a. Transmitter or 5881/5882 not properly Check or change transmitter's battery. received at 5881/5882. powered. Check VISTA-20SE's AC power. 1b. If Transmitter is 5827/5827BD , house code 1b. Check code switches inside transmitter. not set in field * 24, or transmitter not set Must match with RF House Code programmed in VISTA-20SE.
  • Page 86 2d. Program prefix or access code into the prefix or access code. VISTA-20SE. 2e. Telephone call to central monitoring 2e. VISTA-20SE system cannot work in this station requires operator assistance. situation. Does not arm properly. 3a. Ready light not on.
  • Page 87: Contacting Technical Support In The Event Of Problems

    • Note the proper model number of this product, and the version level (if known) along with any documentation that came with the product. • Note your ADEMCO customer number and/or company name. Having this information handy will make it easier for us to serve you quickly and effectively.
  • Page 88: Regulatory Agency Statements

    REGULATORY AGENCY STATEMENTS UL NOTICE: This is a "Grade A" residential system. FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for your information: This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, may cause interference to radio and television reception.
  • Page 89: Section 26. Specifications & Accessories

    12-1/2" W x 14-1/2" H x 3" D (318mm x 368mm x 76mm) SECURITY 2. Electrical: CONTROL VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No. 1321 (in U.S.A.) RECHARGEABLE BACK-UP BATTERY: 12VDC, 4AH (Gel type). Charging Voltage: 13.8VDC. ALARM SOUNDER: 12V, 2.0 Amp output can drive 12V BELLS or can drive one or two 702 (series connected) self-contained 20-watt sirens.
  • Page 90 200ft (60m) nominal indoors from wireless transmitters (the actual range to be determined with system in TEST mode). 5. Zones: (With the Ademco VISTA-20SE) 5881L/5882L: accepts up to 8 transmitters 5881M/5882M: accepts up to 16 transmitters 5881H/5882H: accepts up to 24 transmitters 5800TM 1.
  • Page 91: Accessories (Compatible Devices)

    No. 1321 16.5VAC, 25VA Plug-In Transformer No. 4300 Powerline Carrier device Interface AC Transformer Sounders Ademco AB-12M 10” Motor bell & box. UL Grade A. 100 mA current Motorized Bell & Box draw. Ademco 1011BE12M 10” Motor bell & box. UL Listed. 100 mA current Motorized Bell &...
  • Page 92: Appendix A. 5800 Rf System Wireless Transmitters, Input Loop Identification Diagrams

    APPENDIX A. 5800 RF System Wireless Transmitters Transmitter Input Loop Identification 5800 Series Transmitter Input Loop Identification • All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5803's three inputs require three programming zones).
  • Page 93: Index

    Ademco 745X ............... 3 36 3+1 and 4+1 Standard Formats ........77 Ademco 747 ..............36 Ademco AB-12M 10” Motorized Bell & Box ....36 3+1 or 4+1 Standard Format ........52 3-digit number ............66, 67 Ademco Contact ID ........... 9, 77 4+2 Format ..............
  • Page 94 Power Up In Previous State ........49 Hard-Wired Zones ............17 Powerline Carrier device ..........64 HAYES modem specified by Ademco ......9 Powerline Carrier Device (.I.X-10) House Id ....48 HAYES Modem, ............74 Powerline Carrier devices ....8, 9, 29, 30, 63, 81 House ID ..............
  • Page 95 Primary Subs Account. No........... 50 Trouble Condition ............82 Program Upload or Download Time ......75 Trouble Report Code ............ 53 Programming Information ........... 43 Trouble Restore Report Code ........54 Pulse Dialing, ..............32 UL ........13, 15, 25, 36, 38, 42, 88, 89 Quick Arm ............
  • Page 96 – NOTES – WWW.DIYALARMFORUM.COM – 96 –...
  • Page 97 – NOTES – WWW.DIYALARMFORUM.COM – 97 –...
  • Page 98: Limitations Of This Alarm System

    WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: •...
  • Page 99: Summary Of Connections

    Figure 22. VISTA-20SE SUMMARY OF CONNECTIONS WWW.DIYALARMFORUM.COM – 99 –...
  • Page 100: Limited Warranty

    24 months from the date stamp control on the product or, for products not having an Ademco date stamp, for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply.

This manual is also suitable for:

Vista-20hwse

Table of Contents

Save PDF