ADEMCO VISTA-128FBP Programming Manual

ADEMCO VISTA-128FBP Programming Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-128FBP:

Advertisement

K0376PR 8/02
9
9
9
9
&RPPHUFLDO)LUHDQG%XUJODU\
3DUWLWLRQHG6HFXULW\6\VWHP
AR ME
RE AD Y
OFF
ON
,
6
7
$
,
6
7
$
,
6
7
$
,
6
7
$
3URJUDPPLQJ*XLGH
D




)




)




)




)
ZLWK6FKHGXOLQJ
®
%
3

%
3

%
3

%
3




Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VISTA-128FBP and is the answer not in the manual?

Questions and answers

Summary of Contents for ADEMCO VISTA-128FBP

  • Page 1 &RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ 3URJUDPPLQJ*XLGH AR ME RE AD Y ® K0376PR 8/02...
  • Page 2: Table Of Contents

    Multiple-Partition System You must enter the number of partitions you are using in data field 2*00 to set the system for multiple partitions. Use the VISTA-128FBP/VISTA-250FBP SINGLE PARTITION and the PARTITION-SPECIFIC PROGRAM FORMS when programming the system for multiple partitions.
  • Page 3: Recommended Programming Procedure

    VIP module, as well as the Custom Index section for custom word substitutes. 11. Use #80 Mode for programming schedules. Refer to the Scheduling Menu Prompts in the VISTA-128FBP/VISTA-250FBP Installation and Setup Guide to program open/close schedules, temporary and holiday schedules, limitation of access schedules, and time- driven events.
  • Page 4: Program Field Index

    Program Field Index On the following pages, the programming fields have been arranged in numerical order. Use this index to cross-reference the fields on the programming form. Field Group Field Group Field Group System-Wide 1*22 System-Wide 2*46 Communications System-Wide 1*23 System-Wide 2*47 Communications...
  • Page 5: Vista-128Fbp/Vista-250Fbp Programming Form

    VISTA-128FBP/VISTA-250FBP Programming Form Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system, see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets [ ];...
  • Page 6 FIRST TEST REPORT TIME SECONDARY FORMAT [Day 00; hour 12; min 00]. Days 01-07, Hours 00-23, Min 00- 0=Low Speed; 1=Contact ID; 2= ADEMCO High Speed; 59; 00 in all boxes = instant (Day 01= Monday) 3= ADEMCO Express SWINGER SUPPRESSION [01] LOW SPEED FORMAT (Sec.)
  • Page 7 1*26 ENABLE DIALER REPORTS FOR PANICS & DURESS PANIC BUTTON OR SPEEDKEY 1=enable; [0=disable] [00, 00, 00, 00] 995 996 999 Duress Enter speedkey macro # (01-35) to use keys A-C for macro. ENTRY WARNING Otherwise enter 00 to use as panic. For D key, enter macro # or 00 to select macro when key is pressed.
  • Page 8: System-Wide

    1*49 1*77 SUPPRESS TX SUPERVISION SOUND LOG FIRST MAINTENANCE SIGNAL 1=disable; 0=enable. 0=No Log; 1=Log first maintenance signal from each smoke Must be "0" for UL Commercial Burglary and Fire installs. detector. 1*52 3rd Page Programming Fields SEND CANCEL IF ALARM + OFF (press *94) 1=no restriction;...
  • Page 9 2*21 2*40 ENABLE SUPERVISION PULSES FOR LRR PAGER 2 PHONE NUMBER TRIGGER OUTPUTS [00000] Used for supervised connection to 7920SE. Enter 0 to disable or 1 to enable the listed outputs. Enter 0-9 for each digit. Enter #11 for *, #12 for #, F= Fire;...
  • Page 10 2*53 2*66 PAGER 3 TRIGGER EVENT ENABLES PAGER 5 PARTITION ENABLE Alarm Trbl Syst Test 1=enable; [0=disable] 1=enable; [0=disable] 2*54 PAGER 4 PHONE NUMBER 2*67 PAGER 5 TRIGGER EVENT ENABLES Alarm Trbl Syst Test 1=enable; [0=disable] 2*68 PAGER 6 PHONE NUMBER Enter 0-9 for each digit.
  • Page 11 2*79 3*16 PAGER 7 DELAY 2 [000] DELAY FOR ZONE TYPE 17 & 18 [00] Enter the delay time 000-060 seconds. The delay occurs Enter 00-15 times 2 seconds between the pager ID and the event information. 3*17 ALTERNATE FUNCTION (TAMPER) NOTE: Program only if using numeric format.
  • Page 12: Partition-Specific Fields

    Partition-Specific Fields (Duplicate this page for each partition in the installation.) To program these fields, 1. Press *91 to select a partition. 2. Enter a partition-specific field number (ex. *09). 3. Make the required entry. 4. Repeat steps 1-3 for each partition in the system. PARTITION #____ PROGRAM FIELDS 1st Page Fields SWINGER SUPPRESSION...
  • Page 13: System-Wide

    1*52 2*22 SEND CANCEL IF ALARM + OFF DISPLAY FIRE ALARMS OF 1=no restriction; 0=within Bell Timeout period only. OTHER PARTITIONS Must be enabled “1” for SIA installations. 0=disable; 1=enable 1*76 ACCESS CONTROL RELAY FOR PART.[00] 2*23 DISPLAY BURG/PANIC ALARMS OF Relay will be pulsed for 2 seconds whenever code + [0] is OTHER PARTITIONS pressed.
  • Page 14: Programming With #93 Menu Mode

    NOTE: All references in this manual for number of zones, number of user codes, number of access cards, and the event log capacity, use the VISTA-250FBP’s features. See page 2 of this manual for the table listing the differences between the VISTA-128FBP and the VISTA-250FBP control panels. For UL installations, verify that the audio alarm verification feature is disabled.
  • Page 15: Zone Programming

    PROMPT EXPLANATION For defining output relay functions. OUTPUT PGM? 1 = YES 0 = NO For entering voice descriptors for relays to be used with the 4285/4286 VIP Module. RLY VOICE DESCR? 1 = YES 0 = NO For creating custom word substitutes for VIP Module annunciation. CUSTOM INDEX ? 1 = YES 0 = NO...
  • Page 16: Vistakey Modules 8

    Each zone must be assigned a zone type, which defines the way in which the system responds to faults in 010 ZONE TYPE that zone. Refer to the Zone Type Definitions section in the VISTA-128FBP/VISTA-250FBP Installation and PERIMETER Setup Guide for detailed definitions of each zone type. Enter the zone type desired (or change it, if Zone number 010 and necessary).
  • Page 17: Communications

    PROMPT EXPLANATION If you selected response type 1, 2, 3, 4, 5, or 10, this prompt will appear. Enter 1 to enable. The zone 010 Silent ? follows all the selected response type’s characteristics, except in the alarm condition, the alarm output and 1 = YES 0 = NO the keypad sounder do not sound and the keypad does not display the alarm condition.
  • Page 18 PROMPT EXPLANATION If input type 3 or 6 was selected, this prompt will be displayed. Enter 1 for devices that monitor maintenance 010 SMART CONTACT signals (ex. 5192SD, 5192SDT, 5808), otherwise enter 0. 1 = YES 0 = NO NOTE: The Smart Contact option must ONLY be selected for devices that support the feature, otherwise unpredictable results may occur.
  • Page 19: 5800 Series Transmitters Loop Designations

    5800 Series Transmitters Loop Designations LOOP 3 LOOP 2 LOOP 1 (REED) (PRIMARY) LOOP 2 LOOP 2 (AUX. CENTER) LOOP 1 LOOP 1 LOOP (TERMINALS) LOOP 3 LOOP 4 (AUX. RIGHT) ALTERNATE YOU MUST POSITION 5 8 1 7 ENROLL THIS 5 8 1 6 M N FOR LOOP 2 BUTTON...
  • Page 20: Expert Mode Zone Programming

    PROMPT EXPLANATION The system now returns to the “ENTER ZONE NO.” prompt for the next zone. ENTER ZONE NO. When all zones have been programmed, enter “000” to quit. 000 = QUIT After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in the appropriate column on the worksheets provided later in this Programming Guide ;...
  • Page 21 PROMPT EXPLANATION Enter all zone information except for Loop number, or press “C” to copy the zone information on this screen ZT P RC from the last saved zone (including Loop). 010 03 ZT = Zone Type = Partition RC = Report Code In = Input Device Type = Loop number to which the sensor is connected.
  • Page 22 PROMPT EXPLANATION The prompt to confirm appears. This prompt only appears if you answered “Yes” at the “SET TO XMIT TO CONFIRM CONFIRM?” prompt. PRESS TO SKIP The system enters a confirmation mode so that the operation of the actual programmed input can be confirmed.
  • Page 23 PROMPT EXPLANATION If you entered YES previously at the SET TO CONFIRM prompt (see first prompt following entry into the XMIT TO CONFIRM Expert Programming Mode), the display on the left appears. PRESS TO SKIP To confirm, activate the button on the wireless key that corresponds to this zone. If the serial number transmitted does not match the serial number entered, a display similar to the one Entd A022-4063...
  • Page 24: Report Code Programming

    All report codes are entered using #93 Menu Mode Programming , either through Report Code Programming , or through Zone Programming while entering other zone information. In the VISTA-128FBP/VISTA-250FBP, reports are divided into six categories. These categories represent the main menu options in Report Code Programming . Reports and the categories in...
  • Page 25 Restore/Supervisory Codes PROMPT EXPLANATION Press [1] (Y) to enter Restore and Supervisory Codes for zones. RESTR, SUPV. CODE 1 = YES 0 = NO Enter one zone for each group of 16 zones (001-016, 017-032, etc.). ENTER ZN FOR GRP 000 = QUIT Enter the first digit of the Alarm Restore Report Code for this group of zones (double-digit entry).
  • Page 26 PROMPT EXPLANATION Enter the rest of the codes in the same manner. Other report codes in System Group #1 are: • Opening (Disarm) Also, enable this if you desire Callback Requested reports (the panel answers a phone call from the downloader). •...
  • Page 27: Alpha Descriptors Programming

    PROMPT EXPLANATION Enter the rest of the codes in the same manner. Other codes in System Group #3 are: • Early Close • Late Open • Late Close • Failed to Open • Failed to Close • Auto-Arm Failed • Schedule Change Once you have entered these report codes, the system prompts you with the Quit menu.
  • Page 28 Press [0] to display the next mode available. The alpha menu selections are: ZONE DESCRIP? For entering zone descriptors. DEFAULT SCREEN? For creating custom message; displayed when system is ready. CUSTOM WORD? For creating custom words for use in descriptors. PART DESCRIP? For creating 4-character partition names.
  • Page 29 Exit Zone Description Mode: enter 000. Default Screen (Custom Message Display) Normally, when the system is in the disarmed state, the following display is present on the keypad. ****DISARMED**** READY TO ARM Part or all of the above message can be modified to create a custom installer message for each partition. For example, “****DISARMED****”...
  • Page 30 Repeat step 3 to create the desired custom word (or words). Press [4] to move the cursor to the left if necessary. Press [7] to enter a blank (or to erase an existing character). Each word or word string cannot exceed 10 characters. Save the word by pressing [8].
  • Page 31: Alpha Descriptor Vocabulary

    Alpha Descriptor Vocabulary (For entering alpha descriptors. To select a word, press [#] followed by the word's 3-digit number.) NOTE: This vocabulary is not to be used for relay voice descriptors. See the Relay Voice Descriptors section when programming relay voice descriptors. 000 (Word Space) 058 DIALER 2 112 JEWELRY...
  • Page 32: Device Programming

    Device Programming This menu is used to program keypads, receivers, and relay modules, etc. Device Address 00 is always set as an alpha keypad assigned to Partition 1 with no sounder suppression options, and these settings cannot be changed. From Data Field Programming mode, press #93 to display "ZONE PROG?" Press [0] repeatedly to display "DEVICE PROG?" PROMPT EXPLANATION Press [1] to enter Device Programming .
  • Page 33 RF Expander PROMPT EXPLANATION If you selected device type 03 (RF receiver), this prompt appears. Enter the 2-digit House ID (00-31). This 01 RF EXPANDER is required if you are using a wireless keypad (5827/5827BD). HOUSE I Press [ ] to accept entry. Output Relay Module PROMPT EXPLANATION...
  • Page 34 The 6139/6160 Keypad displays the following prompts, which are sent by the Long Range Radio transmitter to the control. Note: These prompts are for the 7820 Radio only. If you are using a different radio, refer to the radio’s instructions for the correct prompts.
  • Page 35: Output Programming

    VIP Module and VISTA Gateway Module PROMPT EXPLANATION If you selected device type 05 (VIP Module) or type 09 (VGM), this prompt appears. Enter the partition 01 MODULE PART. number 1-8 in which the module is located. Press [ ] to accept entry. Press 00 + [ ] to exit Menu mode.
  • Page 36 STOP (STP): The "STOP" programming determines when and under what conditions the device is de-activated. The following options are available: 1). RESTORE ZONE LIST (ZL). If a "ZONE LIST" is used as the “Stop” event, the device de-activates when all the zones in that list restore from a previous fault, trouble, or alarm condition. This occurs regardless of what is programmed to "START"...
  • Page 37: Communications

    Choices for Start/Stop Zone Types and System Operations: 00 = No Response (Not Used) 23 = No Alarm Response 42 = System Battery Low 01 = Entry/Exit #1 27 = Access Point (allows more than one 43 = Communication failure 02 = Entry/exit #2 relay to be controlled by activation if 44 = RF Low Battery...
  • Page 38 PROMPT EXPLANATION Relays may be grouped for common activation by time-driven events (commands 06-10). Enter 00 (no 02 RELAY GROUP group) or 01-15 for a specific group number. Press [ ] to continue. The system may have some devices that are not intended to be under end user control, such as relays 02 RESTRICTION activating fire doors or machinery.
  • Page 39: Relay Voice Descriptors

    PROMPT EXPLANATION Enter each zone number to be deleted from the zone list, pressing [ ] after each number. 01 Zn to DELETE ? 000=QUIT This display appears if you pressed 00 at the “Enter Zone LIST” prompt. Enter the zone list number that you VIEW Zn LIST ? wish to view.
  • Page 40: Relay Voice Descriptors And Custom Word Substitutes Vocabulary

    Relay Voice Descriptors and Custom Word Substitutes Vocabulary Word Index Word Index Word Index Word Index Word Index Air ......116 Device ......060 Gas ......138 Off......011 Smoke ..... 024 Alarm ....... 255 Dim ......163 Glass......139 Office ....... 147 South.......
  • Page 41: Scheduled Check-In

    Scheduled Check-in The system can be programmed to call the downloader automatically, at a scheduled time. Once the connection is made, the downloader can perform any and all functions (arm, disarm, upload, etc.). The downloader determines the functions it performs. To enter scheduled check-in, do the following: From Data Field Programming mode, press #93 to display the "ZONE PROG?"...
  • Page 42: System Layout Worksheets

    NOTE: All references in this manual for number of zones, number of user codes, number of access cards, and the event log capacity, use the VISTA-250FBP’s features. See page 2 of this manual for the table listing the differences between the VISTA-128FBP and the VISTA-250FBP control panels. All other features are identical. PARTITIONS Descriptor Prim.
  • Page 43 PRINTER OPTIONS EVENT LOG TYPES Parallel or Serial printer Option 12- or 24-hour Time format Alarm Printer On-Line (yes/no) Trouble 1200 or 300 baud Printer Baud Rate Bypass Open/Close System Test DEVICES (keypads, 4204, rf receivers, vip module, lrr, vgm, plm) Sound Supv House...
  • Page 44 ACCESS CODES & USER DEFINITIONS FOR PARTITIONS 3 & 4 4-digit Access Partition 3 Partition 4 Security Group 3-Digit Auth. Open/ Group Global 3-Digit Auth. Open/ Group Global Code 0; 1-8 User # Level Close Bypass User # Level Close Bypass ACCESS CODES &...
  • Page 45 — 45 —...
  • Page 46 — 46 —...
  • Page 47 — 47 —...
  • Page 48 — 48 —...
  • Page 49 — 49 —...
  • Page 50 — 50 —...
  • Page 51 — 51 —...
  • Page 52 — 52 —...
  • Page 53 — 53 —...
  • Page 54 — 54 —...
  • Page 55 ZONE DEFINITIONS FOR KEYPAD PANIC ZONES 995, 996, & 999 Enter yes/no for each partition-field *22 Zone Zone Bell/Relay Report Zone Information & Type Activation Code Alpha Descriptor (3 words max.) ZONE DEFINITIONS FOR SYSTEM ZONES; 970 − 975, 988; 990 & 997 Zone Information Zone Zone...
  • Page 56 ZONE DEFINITIONS FOR RELAY SUPERVISORY ZONES 601-632 Zone Information Zone Information Zone Zone Report Zone Zone Report & & Type Code Type Code Alpha Descriptor (3 words max.) Alpha Descriptor (3 words max.) NOTE: Only the relays on 4204CF modules may be supervised. If supervision is programmed for other types of Output Devices, unpredictable results may occur.
  • Page 57 ZONE DEFINITIONS FOR SUPERVISORY OF ECP DEVICE ZONES 800-830 Zone Information Zone Information Zone Zone Report Zone Zone Report & & Type Code Type Code Alpha Descriptor (3 words max.) Alpha Descriptor (3 words max.) Zone Types 00=zone not used 06=24-hour silent 16=fire w/verification 22=disarm...
  • Page 58: Output Devices Worksheets

    Output Devices Worksheets Applicable only if relays (4204/4204CF), FSA Modules, or V-Plex are used. Output Devices – Programmed in the #93 Menu Mode in the Output Programming Section. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
  • Page 59 OUTPUT DEVICES WORKSHEET (cont’d) S T A R T S T O P V-Plex Zone # Relay # for 0=V-Plex OUTPUT Relay 4204 or Restrict 1=4204 DEV # Group Dev Add 4204 LED # for EV/ZL Zone ZT / P ZT / P 3=FSA or FSA...
  • Page 60 OUTPUT DEVICES WORKSHEET (cont’d) S T A R T S T O P V-Plex Zone # Relay # for 0=V-Plex OUTPUT Relay 4204 or Restrict 1=4204 DEV # Group Dev Add 4204 LED # for EV/ZL Zone ZT / P ZT / P 3=FSA or FSA...
  • Page 61 OUTPUT DEVICES WORKSHEET (cont’d) S T A R T S T O P V-Plex Zone # Relay # for 0=V-Plex OUTPUT Relay 4204 or Restrict 1=4204 DEV # Group Dev Add 4204 LED # for EV/ZL Zone ZT / P ZT / P 3=FSA or FSA...
  • Page 62: Communications

    DEVICE ACTION 0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off; 4 = Toggle alternately between START and STOP events EV = EVENT 0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble; 4 = Restore ZL = ZONE LIST 01-15, 00 = Not Used...
  • Page 63 Zone List 5: Started or stopped by zone numbers (enter 000 to end entries). Zone List 6: Started or stopped by zone numbers (enter 000 to end entries). Zone List 7: Started or stopped by zone numbers (enter 000 to end entries). Zone List 8: Started or stopped by zone numbers (enter 000 to end entries).
  • Page 64: Scheduling Menu Prompts

    Scheduling Menu Prompts To program schedules, enter Scheduling program mode by pressing [User Code] + # + 80 to display the first choice of the menu driven programming functions. NOTE: Only users with an Installer or Master level user code may enter the #80 mode. Press 0 (NO) or 1 (YES) in response to the displayed menu selection.
  • Page 65: Scheduling Worksheets

    Scheduling Worksheets Time Windows Definitions Worksheet. The system provides 20 time windows that are defined with start and stop times. They are programmed in the #80 Menu Mode. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
  • Page 66 Holiday Schedule Worksheet: The system provides up to 16 holidays that can be assigned for the system. Each holiday can be assigned to any combination of partitions. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
  • Page 67 Automatic Refresh: The system automatically updates the status of all Time-Driven Events upon any of the following occurrences: • Changing of the time or date via #63 mode • Exiting #80 Scheduling Menu mode • Exiting Program mode • After a disconnect from the downloader •...
  • Page 68 Activation time: Refers to when the action is to take place relative to the time window. Beginning of time window Beginning and end of time window End of time window Random Start of the time window During time window active period only (On at Random End of the time window beginning of window, off at end).
  • Page 69 Partition/Windows Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window Start Time HH:MM Stop Time HH:MM Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window Start Time HH:MM Stop Time HH:MM Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window Start Time...
  • Page 70: Vista-128Fbp Summary Of Connections Diagram70

    VISTA-128FBP Summary of Connections Diagram — 70 —...
  • Page 71: Vista-250Fbp Summary Of Connections Diagram71

    VISTA-250FBP Summary of Connections Diagram — 71 —...
  • Page 72 165 Eileen Way, Syosset, New York 11791 © Copyright 2002 PITTWAY CORPORATION ¬.351l K0376PR 8/02 Edited by Technical Support 9/04...

This manual is also suitable for:

Vista-250fbp

Table of Contents

Save PDF