(5) Operation data during emergency operation
During emergency operation, no communication is performed with the indoor unit, so the data items needed for operation
are set to the following values:
Operation data
Intake temperature (TH1)
Indoor pipe temperature (TH2)
Indoor 2-phase pipe temperature (TH5)
Set temperature
Pressure saturation temperature (T
Liquid temperature (TH3)
Discharge pipe temperature (TH4)
2-phase pipe temperature (TH6)
Ambient temperature (TH7)
Temperature difference code (intake temperature - set temperature) (Tj)
Discharge superheat (SHd)
Sub-cool (SC)
1: If the thermistor temperature data is normal (not open/short), that data is loaded into the control as valid data.
When the unit enters emergency operation and TH values are mismatched, set the thermistors
to open/short. And the unit runs emegency operation with the values listed above.
2: If one thermistor is set to open/short, the values for each will be different from the list above.
[Example] When pipe temperature thermistor (TH3) has an open or short circuit.
Thermistor
TH3
TH6
TH4
TH5
TH2
T
63HS
OCH526
)
63HS
COOL
HEAT
5
45
Tb
Ta
Regard normal figure as effective data.
Tc
Td
Regard normal figure as effective data.
50
5
5
45
Tf
Te
Regard normal figure as effective data.
Operation mode
COOL
HEAT
27
20.5
5
45
5
50
25
22
50
50
45
5
80
80
50
5
35
7
5
5
30deg
30deg
5deg
5deg
Discharge superheat (SHd)
Cooling = TH4 - T
63HS
Heating = TH4 - T
63HS
Degree of subcooling (SC)
Cooling = T
- TH3 = Te - 45
63HS
Heating = T
- TH2 = Tf - 45
63HS
53
Remarks
( 1)
( 1)
( 1)
( 1)
( 1)
( 2)
( 2)
= Tc - Te
= Td - Tf