INSTALLATION MANUAL

For safe and correct use, read this manual and the indoor unit installation manual thoroughly before installing
the air-conditioner unit.
INSTALLATIONSHANDBUCH
Aus Sicherheitsgründen und zur richtigen Verwendung vor der Installation die vorliegende Bedienungsanleitung
und die Installationsanleitung der Innenanlage gründlich durchlesen die Klimaanlage.
MANUEL D'INSTALLATION
Avant d'installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d'installation de l'appareil
intérieur pour une utilisation sûre et correcte.
INSTALLATIEHANDLEIDING
Lees deze handleiding en de installatiehandleiding van het binnenapparaat zorgvuldig door voordat u met het
installeren van de airconditioner begint.
MANUAL DE INSTALACIÓN
Para un uso correcto y seguro, lea detalladamente este manual y el manual de instalación de la unidad interior
antes de instalar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente il presente manuale ed il manuale d'installazione dell'unità
interna prima di installare il condizionatore d'aria.
MANUAL DE INSTALAÇÃO
Para uma utilização segura e correcta, leia atentamente este manual e o manual de instalação da unidade
interior antes de instalar o aparelho de ar condicionado.
INSTALLATIONSMANUAL
Læs af sikkerhedshensyn denne manual samt manualen til installation af indendørsenheden grundigt, før du
installerer klimaanlægget.
INSTALLATIONSMANUAL
Läs bruksanvisningen och inomhusenhetens installationshandbok noga innan luftkonditioneringen installeras
så att den används på ett säkert och korrekt sätt.
Emniyetli ve doğru kullanım için, klima cihazını monte etmeden önce bu kılavuzu ve iç ünite montaj kılavuzunu
tamamıyla okuyun.
HA4
KA
FOR INSTALLER
FÜR INSTALLATEURE
POUR L'INSTALLATEUR
VOOR DE INSTALLATEUR
PARA EL INSTALADOR
PER L'INSTALLATORE
PARA O INSTALADOR
TIL INSTALLATØREN
FÖR INSTALLATÖREN
English
Deutsch
Français
Nederlands
Español
Italiano
Eλληνικά
Português
Dansk
Svenska
Türkçe

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric PUHZ-RP-HA4

  • Page 1: Installation Manual

    Air-Conditioners PUHZ-RP • PUHZ-RP • INSTALLATION MANUAL FOR INSTALLER English For safe and correct use, read this manual and the indoor unit installation manual thoroughly before installing the air-conditioner unit. INSTALLATIONSHANDBUCH FÜR INSTALLATEURE Deutsch Aus Sicherheitsgründen und zur richtigen Verwendung vor der Installation die vorliegende Bedienungsanleitung und die Installationsanleitung der Innenanlage gründlich durchlesen die Klimaanlage.
  • Page 2: Table Of Contents

    This symbol mark is according to the directive 2002/96/EC Article 10 Information for users and Annex IV. Your MITSUBISHI ELECTRIC product is designed and manufactured with high quality materials and components which can be recycled and reused. This symbol means that electrical and electronic equipment, at their end-of-life, should be disposed of separately from your household waste.
  • Page 3: Before Starting The Test Run

    1. Safety precautions 1.2. Before installation (relocation) Caution: • Be extremely careful when transporting or installing the units. Two or • The base and attachments of the outdoor unit must be periodically more persons are needed to handle the unit, as it weighs 20 kg or more. checked for looseness, cracks or other damage.
  • Page 4 2. Installation location ■ ■ 2.2. Choosing the outdoor unit installation location RP35, 50 RP60, 71 • Avoid locations exposed to direct sunlight or other sources of heat. • Select a location from which noise emitted by the unit will not inconvenience neighbors.
  • Page 5: Installing The Outdoor Unit

    3. Installing the outdoor unit (mm) • Be sure to install the unit in a sturdy, level surface to prevent rattling noises during peration. (Fig. 3-1) <Foundation specifi cations> Foundation bolt M10 (3/8") Thickness of concrete 120 mm Length of bolt 70 mm Weight-bearing capacity 320 kg...
  • Page 6 4. Installing the refrigerant piping 4.2. Connecting pipes (Fig. 4-1) • When commercially available copper pipes are used, wrap liquid and gas pipes with commercially available insulation materials (heat-resistant to 100 °C or more, thickness of 12 mm or more). •...
  • Page 7 4. Installing the refrigerant piping 4.4. Refrigerant pipe airtight testing method (Fig.4-5) (1) Connect the testing tools. • Make sure the stop valves A B are closed and do not open them. • Add pressure to the refrigerant lines through the service port C of the liquid stop valve A .
  • Page 8 4. Installing the refrigerant piping When length exceeds 70 m When the total length of the piping exceeds 70 m, calculate the amount of additional charge based on the following requirements. Note: If the calculation produces a negative number (i.e. a “minus” charge), of if calculation results in an amount that is less than the “Additional charage amount for 70 m”, perform the additional charge using the amount shown in “Additional charge amount for 70 m”.
  • Page 9: Drainage Piping Work

    4. Installing the refrigerant piping 4.7. Precautions when reusing existing R22 refrigerant pipes • Refer to the fl owchart below to determine if the existing pipes can be used and if it is necessary to use a fi lter dryer. •...
  • Page 10: Electrical Work

    6. Electrical work ■ ■ 6.1. Outdoor unit (Fig. 6-1, Fig. 6-2) RP35, 50 RP35, 50 1 Remove the service panel. 2 Wire the cables referring to the Fig. 6-1 and the Fig. 6-2. * Except PEA-RP200, 250, 400, 500GA * With Heater model only For Heater...
  • Page 11 6. Electrical work 6.2. Field electrical wiring Outdoor unit model RP35, 50V RP60, 70V RP100,125V RP140V RP100, 125, 140Y RP200, 250 ~/N (single), 50 Hz, ~/N (single), 50 Hz, ~/N (single), 50 Hz, ~/N (single), 50 Hz, 3N~ (3 ph 4-wires), 3N~ (3 ph 4-wires), Outdoor unit power supply 230 V...
  • Page 12: Test Run

    7. Test run 7.1. Before test run • The insulation resistance drops due to accumulation of refrigerant in the com- pressor. The resistance will rise above 1 M" after the compressor is warmed ► After completing installation and the wiring and piping of the indoor and up for four hours.
  • Page 13: Special Functions

    9. Special Functions 9.1. Low noise mode (on-site modifi cation) (Fig. 9-1) By performing the following modifi cation, operation noise of the outdoor unit can be CNDM Orange reduced by about 3-4 dB. Brown The low noise mode will be activated when a commercially available timer or the Fig.
  • Page 14 • Electromagnetic Compatibility Directive EU regulations: 2004/ 108/ EC HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Authorized representative in EU: MITSUBISHI ELECTRIC EUROPE B.V. HARMAN HOUSE, 1 GEORGE STREET, UXBRIDGE, MIDDLESEX UB8 1QQ, U.K. BH79D132H01 Printed in Japan...