Func.
Name
Code
C146
Terminal [12] ON delay R/W Range is 0.0 to 100.0 sec.
C147
Terminal [12] OFF
delay
C148
Output relay ON delay
C149
Output relay OFF delay R/W Range is 0.0 to 100.0 sec.
Note 1:
Assume that the inverter current rating is 10000 (for C041).
The following table lists the holding registers for the "H" Group Motor Constants.
Func.
Name
Code
H003
Motor capacity
H203
Motor capacity, 2nd
setting
H004
Motor poles setting
H204
Motor poles setting, 2nd
motor
H006
Motor stabilization
constant
H206
Motor stabilization
constant, 2nd motor
H007
Motor voltage select
H207
Motor voltage select,
2nd motor
"C" Group Intelligent Terminal Functions
R/W
Description
R/W Range is 0.0 to 100.0 sec.
R/W Range is 0.0 to 100.0 sec.
"H" Group Motor Constants
R/W
Description
R/W Thirteen selections:
0..... 0.20 kW
R/W
1..... 0.37 kW
2..... 0.40 kW
3..... 0.55 kW
4..... 0.75 kW
5..... 1.10 kW
6..... 1.50 kW
7..... 2.2 kW
8..... 3.0 kW
9..... 3.7 kW
10... 4.0 kW
11... 5.5 kW
12... 7.5 kW
R/W Four selections:
2 / 4 / 6 / 8
R/W
R/W Motor constant (factory set),
range is 0 to 255
R/W
R/W Two selections, option codes:
00... 200V
R/W
01... 400V
B–39
SJ200 Inverter
Network Data
Reg.
Range
Res.
00F4h
0 to 1000 0.1 sec
00F5h
0 to 1000 0.1 sec
00F6h
0 to 1000 0.1 sec
00F7h
0 to 1000 0.1 sec
Network Data
Reg.
Range
Res.
00D9h
0 to 12
00DAh
0 to 12
00DBh
2, 4, 6,
1 pole
8
00DCh
2, 4, 6,
1 pole
8
00DDh 0 to 255
1
00DEh 0 to 255
1
00DFh
0, 1
00E0h
0, 1

Advertisement