Connecting The Inverter To Modbus; Cable Wiring; Keypad Removal; Modular Interconnect Removal - Hitachi SJ200 Series Instruction Manual

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for SJ200 Series:
Table of Contents

Advertisement

Connecting the Inverter to ModBus

Follow the steps in this section to connect the inverter to the ModBus network.
1. Keypad Removal - The inverter keypad uses the serial communications interface
connector on the front of the inverter. To access the RJ45 modular connector, you will
need to remove the keypad. Refer to
page 2–3
for detailed instructions.
2. Modular Interconnect Removal - With the keypad removed, locate the RJ45
modular interconnect, the clear plastic connector in the opening as shown below.
Press downward on the locking tab at the top of the connector, releasing it for
removal. Be sure to keep it in a secure place; you may need it in the future for placing
the keypad on the inverter again. The RJ45 modular jack that remains will new accept
the serial communication cable.
3. Cable Wiring - The inverter communications
port uses RS485 differential transceiver. The
pinout is shown to the right and listed below. Be
sure the cable connection you make matches the
diagram.
Pin
Symbol
1
2
3
4
5
SP
6
SN
7
8
"Inverter Keypad Removal and Installation" on
RJ45 modular
interconnect /
communications
connector
Keypad bay
Description
Not used. Do not connect
Not used. Do not connect
Not used. Do not connect
Not used. Do not connect
Send/Receive data Positive
Send/Receive data Negative
Not used. Do not connect
Not used. Do not connect
SJ200 Inverter
SJ200
8
7
6
5
4
S
S
Not used
N
P
Not used
B–3
3
2
1

Advertisement

Table of Contents
loading

Table of Contents