B–34
ModBus Data Listing
Func.
Code
B085
Country code for initial-
ization (not accessible
to ModBus)
B086
Frequency scaling
conversion factor
B087
STOP key enable
B088
Restart mode after FRS
B090
Dynamic braking usage
ratio
B091
Stop mode selection
B092
Cooling fan control
B095
Dynamic braking
control
B096
Dynamic braking
activation level
"B" Group Fine Tuning Functions
Name
R/W
Select default parameter values
for country on initialization.
Note: Write not allowed from
network.
R/W Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.1 to 99.9
R/W Select whether the STOP key
on the keypad is enabled, two
option codes:
00... enabled
01... disabled
R/W Selects how the inverter
resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00... Restart from 0Hz
01... Restart from frequency
detected from real speed of
motor (frequency matching)
R/W Selects the rate of use (in %) of
the regenerative braking
resistor per 100 sec. intervals,
range is 0.0 to 100.0%
0% . Dynamic braking disabled
>0% Enabled, per value
R/W Selects how the inverter stops
the motor, two option codes:
00... DEC (decelerate and stop)
01... FRS (free run to stop)
R/W Selects when the fan is ON per
inverter operation, two options:
00... Fan is always ON
01... Fan is ON during run,
delay from ON to OFF)
02... Fan is temperature
controlled
R/W Three option codes:
00... Disable
01... Enable during RUN only
02... Enable always
R/W Range is:
330 to 380V (200V class),
660 to 760V (400V class)
Description
OFF during stop (5 min.
Network Data
Reg.
Range
Res.
009Bh
009Ch
1 to 999
0.1
009Dh
0, 1
009Eh
0, 1
009Fh
0 =
0.1 %
disabled
, 1 to
1000
enabled
00A0h
0, 1
00A1h
0, 1, 2
00A2h
0, 1, 2
00A3h
330 to
1 V
380, 660
to 760