4.3 Communication with Dedicated Instructions

4.3.1 Writing/reading of device data from QCPU to Motion CPU

The QCPU can write/read device data to/from the Motion CPU with the multiple CPU transmission dedicated
instruction and multiple CPU high-speed transmission dedicated instruction.
(Writing/reading from the Motion CPU to other CPU modules including the Motion CPU is not allowed.)
(Example) Using the S.DDWR instruction
The QCPU device data can be written to the Motion CPU devices.
(1) Multiple CPU transmission dedicated instruction
The QCPU can write/read device data to/from the Q172CPUN(-T), Q173CPUN(-T), Q172HCPU(-T), and
Q173HCPU(-T) with the multiple CPU transmission dedicated instruction shown on Table4.15.
Instruction
name
S.DDWR
Writes host CPU device data into other CPU
SP.DDWR
devices.
S.DDRD
Reads other CPU device data into the host
SP.DDRD
CPU devices.
S.GINT
Requests start up of other CPU interrupt
SP.GINT
programs.
4 - 49
QCPU
S.DDWR instruction
Reading device
Device
Figure 4.46 Operation of S.DDWR instruction
Table4.15 List of multiple CPU transmission dedicated instructions
Description
Motion CPU
Writing device
Basic model
QCPU/High
Performance
model QCPU/
Process CPU
Device
CPU module
Universal model QCPU
Q03UD(E)CPU
Q04UD(E)HCPU
Q00UCPU
Q06UD(E)HCPU
Q01UCPU
Q10UD(E)HCPU
Q02UCPU
Q13UD(E)HCPU
Q20UD(E)HCPU
Q26UD(E)HCPU
: Available,
: Not Available