Mitsubishi Electric MELSEC Q Series User Manual page 132

Programmable controller multiple cpu system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

2) Output(Y) loading is performed for the modules shown in Table3.9, which are mounted to the main base unit
or extension base unit(s).
I/O allocation type
None
Output
I/O mix
Intelli.
3) Output data cannot be loaded from empty slots and remote stations on MELSECNET/H or CC-Link
networks being controlled by the other CPU.
Use auto refresh of CPU shared memory and send the ON/OFF output data for remote stations from control
CPU to non-controlled CPU to use the ON/OFF output data for remote stations on MELSECNET/H or CC-
Link in non-controlled CPU.
By enabling "ALL CPUs can real all outpus" setting, input data controlled by other CPUs can be loaded into the host CPU.
In this case, if the forced ON/OFF of external I/O is activated for the output data loaded from other CPUs to the host CPU,
the data will be set into the specified forced ON/OFF status.
For the forced ON/OFF of external I/O, refer to the following manual.
User's Manual (Function Explanation, Program Fundamentals) for the CPU module used
(b) When "Not all CPUs can read all outputs" has been set
It is not possible to load ON/OFF data output to output modules and intelligent function modules by other CPUs
into the host CPU's output (Y) (remains at OFF.)
CHAPTER3 CONCEPT FOR MULTIPLE CPU SYSTEM
Table3.9 Modules that can load outputs
Output module
I/O composite module
Intelligent function module
Input module
Output module
I/O composite module
Intelligent function module
Mounted module
1
2
3
4
5
6
7
8
3 - 27

Advertisement

Table of Contents
loading

Table of Contents