Motorola MOSCAD 68P02958C00-B User Manual page 363

Toolbox version 5.50
Table of Contents

Advertisement

## 1410
The number of times the following operations were executed
LEVEL : 10
(zeros the counters after diagnostics)
LEVEL : 11
(does not zero the counters)
ocomm key error counters
--------------------------------
How many times did getting buffer fail ?
How many times was a frame transmitted ?
How many times did transmission fail ?
How many times did warmup fail ?
How many times was control frame received ?
How many times was a frame received ?
How many times was invalid frame received ?
How many times was a frame with error status byte received
How many times was a frame with invalid crc received ?
How many times was a frame with irrelevant address received?
How many times was received frames ignored ?
How many times was received frames flushed ?
How many times was transmit frame as a repeater failed
1. The transmission was not carried out because there were no buffers in the transmission heap.
2. The number of times the frame was transmitted (to line/radio or piggyback).
3. The number of times the transmission failed.
4. The number of times warmup failed.
5. The number of times ACK (configuration/diagnostics) message or error was received from
piggyback.
6. The number of times frame was received from radio/line.
7. The number of times invalid frame was received from radio/line.
8. The number of received frames with hardware error.
9. The number of received frames without hardware error but with invalid CRC.
10. The number of received invalid frames with addresses out of range (which were erased).
11. The number of received frames with valid addresses that were erased, because the application did not
try to receive before that time.
12. The number of received frames with valid addresses, but were erased after timeout because the
application did not try to receive during this time.
13. The number of times the transmission of a received frame (in repeater mode) failed because the heap
was empty.