Remote Error Notification - Mitsubishi Electric MN converter Operating Manual

Electric air-conditioner network system
Hide thumbs Also See for MN converter:
Table of Contents

Advertisement

3.12 Remote error notification

The "Remote error notification" has been located starting from Ver4.20.
* Items Performed Here
- The MN Converter (CMS-MNG-E) has a built-in remote error notification function.
When an error occurs in an air conditioning unit, the remote error notification function allows previously
registered destinations to be automatically notified of the error via telephone lines.
To use the remote error notification function in the MN Converter (CMS-MNG-E), you must first specify
the remote error notification settings from the Maintenance Tool.
The MN Converter (CMS-MNG-E) has the following 2 modes:
(1) Maintenance mode
In this mode, the MN Converter can only be used as a normal converter.
(2) Remote error notification mode
This mode allows both the normal MN Converter functions and the remote error notification
function to be used.
Use the Maintenance Tool to switch between these 2 modes.
To use the remote error notification function, connect the MN Converter (CMS-MNG-E) to a modem via the
RS-232C port and then connect the modem to the telephone outlet, as shown in the figure below.
For details, refer to the Installation Manual of MN Converter (CMS-MNG-E).
The dedicated server software or other dedicated software tools run on the remote monitoring PC.
RS-232C
Remote monitoring PC
(Runs dedicated server software
or other dedicated software tools.)
To specify the remote error notification function settings using the Maintenance Tool, connect the MN
Converter (CMS-MNG-E) to the Maintenance Tools PC via USB, as shown in the figure below.
RS-232C
Remote monitoring PC
(Runs dedicated server
software or other
dedicated software
tools.)
NOTE:
• When setting remote error notification, connect to the MN Converter via USB.
MODEM
Public
network
MODEM
Maintenance
Tools PC
Public
RS-232C
network
straight
MODEM
MN Converter
(CMS-MNG-E)
RS-232C
straight
MODEM
USB
MN Converter
(CMS-MNG-E)
51
M-NET
M-NET