Figure A-1 Adjusting the off-load tap changer (to level 1 for example)
----End
A.1.2 Releasing Gas in the Gas Relay
When you see the oil level surface through the glass window of the gas relay, you
need to release the gas.
Step 1 Open the cover of the gas relay.
Step 2 Remove the nut from the bleeder plug.
Step 3 Loosen the bleeder plug bolt. The gas gradually runs out until the oil overflows.