Alarm List - Huawei JUPITER-3000K-H1 Smart User Manual

Transformer station
Hide thumbs Also See for JUPITER-3000K-H1 Smart:
Table of Contents

Advertisement

JUPITER-(3000K, 6000K, 9000K)-H1 Smart
Transformer Station
User Manual
Powering On Inverters and PCSs (Applicable to LV Coupling Scenarios Where
the Inverter and PCS Are Connected to the Same MCCB)
For details, see
Coupling Scenarios Where the Inverter and PCS Are Connected to the Same
MCCB).

6.7 Alarm List

Alar
Alarm
m ID
Name
2300
Fault-
induced
ACB
Tripping in
Low-
Voltage
Cabinet A
2301
IMD Alarm
in Low-
Voltage
Cabinet A
Issue 02 (2023-09-30)
Powering On Inverters, PCSs, and the DTS (Applicable to LV
Alarm
Possible Cause
Severity
Major
1. A short circuit
occurs in the low-
voltage cabinet A.
2. Low-voltage
cabinet A
experiences
overcurrent.
Major
The 800 V cable or DC
side is grounded or the
impedance is low.
Copyright © Huawei Technologies Co., Ltd.
6 System Maintenance
Suggestion
1. Check whether the low-voltage
power loop is short-circuited. If
yes, locate and rectify the fault.
2. Check whether overcurrent occurs
in the low-voltage power loop. If
yes, rectify the fault.
3. Rectify the fault before turning on
the switch.
4. If the fault persists, contact your
dealer or technical support.
1. Disconnect the MCCB and inverter
in sequence, observe the IMD
impedance change, locate the
faulty loop, and rectify the fault.
2. Check whether condensation or
contaminant particles accumulate
on the surface of the bus subrack
or insulator. If yes, disconnect the
power supply and then perform
dehumidification or clean up
foreign matters.
3. Check whether the insulation
resistance of the low-voltage loop
cable is normal. If no, rectify the
fault.
4. If the fault persists, contact your
dealer or technical support.