6.4 TVOC Calibration Standard (According to Ethanol
Volatilization)
TVOC sensor is already calibrated in manufacture. It can also continuously correct
after initial baseline stabilization when powered on. TVOC sensor value will be
stable to more accuracy at least 48 hours power on.
TR50 offers manual TVOC sensor correction options. After the TR50 device is
powered on for more than 30 mintues, record the TVOC value continuously for the
next 30 minutes, then use the synchronous average value for correction with offset
parameters.
6.5 PM1.0, PM2.5, and PM10 Calibration Standard
(According to GRIMM Technology)
The manufacturer already calibrates the PM sensor; it doesn't need re-calibration
in its life year.
TR50 offers manual PM sensor correction options. After the TR50 device is
powered on for more than 30 mintues, record the PM1.0, PM2.5 and PM10 value
continuously for the next 30 minutes, then use the synchronous average value for
correction with offset parameters.
75
TR50 - User Guide