1.2 Dimensions
All the dimensions shown are in inches (mm).
1.3 Intended audience and assumed knowledge
This User Guide provides information about the Getting Started, Configuration
details, and Operations of the TR50 IAQ Sensor to the system integrator,
technicians, and end-users. All the electrical engineers and technicians working
with the product must have basic training on HVAC Sensors, Smart sensors, and
Room Controllers and their application.
1.4 Specification
Parameter
Detection Parameters
Power Supply
Operating Temperature
Operating Humidity
Storage Temperature
Communication
Net weight
Power Consumption
Dimensions
2
0.89" (23 mm)
3.54" (90 mm)
Description
- Temperature (T)
- Relative Humidity (RH)
- Carbon Dioxide (CO
)
2
- Particular Matter (PM1.0, PM2.5 and PM10)
- Total Volatile Organic Compound (TVOC)
Direct : 24 VAC/VDC ± 20 %
TM
Sylk
Bus : Honeywell Sylk
32 to 122 °F (0 to 50 °C)
0-95 % RH, non-condensing
-40 to 150 °F (-40 to 65.5 °C)
BACnet MSTP, Modbus over RS-485, or Sylk
189 grams (0.42 lbs.)
TR50-5D : 24 VAC 3.8 VA, 24 VDC, 1.5 W
TR50-5N : 24 VAC 3.8 VA, 24 VDC, 1.4 W
TR50-3D : 24 VAC 3.2 VA, 24 VDC/Sylk
TR50-3N : 24 VAC 3.2 VA, 24 VDC/Sylk
3.54 inches (90 mm) x 4.45 inches (113 mm) x 0.89 inches (23 mm)
TM
Bus Technology
TM
Bus
TM
Bus, 0.9 W
TM
Bus, 0.8 W
TR50 - User Guide