SS_MV_OutofRange_Temp
CfgTempSensorOffset
CfgAlarmTempLimitEnable
cfgDisplayUnitTemp
4.4.5.3 Humidity Configuration Points
CfgAlarmHumiLowLimit
CfgAlarmHumiHighLimit
CfgAlarmHumiDeadband
CfgAlarmHumiTimeDelay
SS_MV_OutofRange_Humi
cfgAlarmHumiLimitEnable
cfgHumiSensorOffset
TR50 - User Guide
BACnet
Point Name
Instance
1
281
21
101
BACnet
Point Name
Instance
51
52
53
54
2
22
282
Read/
Default
Type
Write
Value
R/W
Multi
1
State
Value
R/W
Analog
0
Value
R/W
Multi
4
State
Value
R/W
Multi
1
State
Value
Read/
Type
Write
R/W
Analog
Value
R/W
Analog
Value
R/W
Analog
Value
R/W
Analog
Value
R/W
Multi State
Value
R/W
Multi State
Value
R/W
Analog
Value
Range
1: Normal
2: Off normal
o
-9 to 9 (
F)
o
-5 to 5 (
C)
1:Temp Low Limit And High
Limit Disable
2:Temp Low Limit Enable
3:Temp High Limit Enable
4:Temp Low Limit And High
Limit Enable
1: Degrees Fahrenheit (
o
2: Degrees Celsius (
Default
Range
Value
10(%)
0
<= PRESENT VALUE of
cfgAlarmHumiLowLimit
<= PRESENT VALUE of
cfgAlarmHumiHighLimit
80(%)
PRESENT VALUE of
cfgAlarmHumiLowLimit
<= PRESENT VALUE of
cfgAlarmHumiHighLimit
<=100
2
0 <= PRESENT VALUE
ofcfgAlarmHumiDead
band
60(s)
0 <= PRESENT VALUE of
cfgAlarmHumiTimeDelay
1
1: Normal
2: Off normal
4
1:Humidity Low Limit
And High Limit Disable
2:Humidity Low Limit
Enable
3:Humidity High Limit
Enable
4:Humidity Low Limit
And High Limit Enable
0
-10 to 10
o
F)
C)
19