Huawei PAC2000S12-B1 PSU Technical Manual page 29

Table of Contents

Advertisement

PAC2000S12-B1 PSU
Parameter
Time for switching to HVDC
in the case of intermittent
AC disconnection (MV12
mode)
Technical Manual
Min.
Typ.
11.0
-
8
-
16
-
30
-
40
-
Max.
Unit
Notes & Conditions
-
V
In 2+2 active/standby
power supply scenarios (AC
+AC, AC+HVDC, or HVDC
+HVDC), when the
following faults occur, the
PSU output voltage is
greater than 11.4 V, and
the PSU 12 V bus voltage is
greater than or equal to 11
V and the time when the
bus voltage is lower than
11.4 V does not exceed 100
µs.
1. One power input fails
(2+2 backup, one power
input for two PSUs).
2. One PSU becomes faulty
(such as input
undervoltage, input
overvoltage, fan fault,
overtemperature, and
output overvoltage).
Note: The 12 V output of
parallel PSUs is equipped
with 1500 µF capacitors.
-
ms
Active: AC; standby: HVDC;
PSU load: 70%; valid HVDC
input current: ≤ 1 A within
20 ms
-
ms
Active: AC; standby: HVDC;
PSU load: 35%; valid HVDC
input current: ≤ 1 A within
20 ms
-
ms
Active: AC; standby: HVDC;
PSU load: 20%; valid HVDC
input current: ≤ 1 A within
20 ms
-
ms
Active: AC; standby: HVDC;
PSU load: 10%; valid HVDC
input current: ≤ 1 A within
20 ms
24