Device for insulation permanent control for isolated networks it

Advertisement

Quick Links

IN STR UC T I O N M AN UA L
ISL-A 24/ ISL-A 48
DEVICE FOR INSULATION PERMANENT CONTROL FOR ISOLATED NETWORKS (IT)
GENERAL
In IT electrical distribution networks with isolated neutral, the high insulation impedance prevents earth faults
from generating currents that would dangerously elevate the potential of exposed conductive parts.
Therefore, in case of earth leakage in an IT network, it is not necessary to interrupt the supply, but it is still
essential to continually monitor the insulation level in order to detect faults and restore optimal functioning
of the system.
The ISL-C 230 is an Insulation Monitoring Device for IT networks with voltages of 24 to 48 V ac/dc. These de-
vices measure the potential variation of two polarities in reference to earth, to signal when the insulation is
decreasing below a fixed value.
Auxiliary supply is taken from the under-control network. On the front panel, there is signaling for the device
being ON, TEST and RESET push-buttons, and three LEDs for signaling a tripping (TRIP) and to indicate the
polarity of the line under control that has low insulation.
The threshold for trip is regulated by a series of micro-switches. There is a changeover contact relay available
to transfer the information of the low insulation signaling to a remote panel.
INSTALLATION
The installation must be carried out by qualified and authorized personnel and in the absence of voltage.
Make sure that the instrument is O.K. and has not been damaged during transport.
Make sure that the voltage supply is compatible with the operating voltage of the instrument.
For each independent line, it's possible to use only one control device.
The device is a 3 modules (17.5mm) DIN version with snap on 35mm DIN rail.
It has a sealable transparent front protection cover.
The green LED ON will light up after the connections are set and the instrument is powered on.
DESCRIPTION
2024-01-24
1.
Green LED ON, signaling the instrument is working.
2.
Red LED TRIP, signaling a trip for low insulation; in manual reset
mode, it is necessary to press the RESET to cancel the signaling.
3.
Red LED TRIP (+ / -), in low insulation status, signals the polarity
under the trip threshold in a direct line, while both LEDs will be on in
an alternating line, functioning in automatic reset.
4.
TEST button to test the instrument's functionality.
5.
RESET button to cancel the trip signaling (manual reset).
6.
Micro-switches to select the threshold for trip.
1/4

Advertisement

loading

Summary of Contents for ABB ISL-A 24

  • Page 1 — IN STR UC T I O N M AN UA L ISL-A 24/ ISL-A 48 DEVICE FOR INSULATION PERMANENT CONTROL FOR ISOLATED NETWORKS (IT) — GENERAL In IT electrical distribution networks with isolated neutral, the high insulation impedance prevents earth faults from generating currents that would dangerously elevate the potential of exposed conductive parts.
  • Page 2 — MICRO-SWITCHES SETTING The front micro-switches allow to set the threshold of trip between 10 and 60 kΩ as it’s showed in the follow- ing figure: — WIRING CONNECTION INSULATED NETWORK 24-48Vac/dc 2024-01-24...
  • Page 3 — LEGEND Auxiliary power supply Terminals 1-3 The auxiliary power supply can be the same as the network to control. Earth reference connection Terminal 11 Connection to the earth or the protection conductor for measurement reference. Relay output connections Terminals 7-8-9 Changeover contact to indicate there is a fault, max 5A 250V on resistive load.
  • Page 4 DIMENSIONS Snap on DIN rail 35mm (DIN 50022) 3 modules 17,5 mm — TECHNICAL FEATURES Auxiliary voltage supply 24-48V 50-60Hz/d.c. ± 20% Maximum consumption 3 VA-3W Measure current max 0,5 mA Internal impedance 50 kΩ Threshold tripping Settable 10 ÷ 60 kΩ (5 levels with micro-switches) Tripping delay About 0.2 seconds Signalling and button...