Multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)

Pr. 4 "3-speed setting (high speed)"
Pr. 5 "3-speed setting (middle speed)"
Pr. 6 "3-speed setting (low speed)"
Pr. 24 to Pr. 27 "multi-speed setting
(speeds 4 to 7)"
Pr. 232 to Pr. 239 "multi-speed setting
(speeds 8 to 15)"
Used to preset the running speeds in parameters and switch between them using terminals.
Any speed can be selected by switching on-off the contact signal (RH, RM, RL or REX signal).
z
By using these functions with jog frequency (Pr. 15), maximum frequency (Pr. 1) and minimum frequency
z
(Pr. 2), up to 18 speeds can be set.
Valid in the external operation mode or PU/external combined operation mode (Pr. 79 = 3 or 4).
z
Parameter
Factory Setting
Number
4
60Hz
5
30Hz
6
10Hz
24 to 27
9999
232 to 239
9999
RH
RM
RL
REX
<Setting>
·
Set the running frequencies in the corresponding parameters.
·
Each speed (frequency) can be set as desired between 0 and 400Hz during inverter operation.
After the required multi-speed setting parameter has been read, the setting can be changed by pressing
the [UP/DOWN] key. (In this case, when you release the [UP/DOWN] key, press the [SET] key to store the
set frequency. When using the FR-PU04 (option), press the [WRITE] key.)
·
Use any of Pr. 180 to Pr. 186 to assign the terminal used to input the REX signal.
Note: 1. The multi-speed settings override the main speeds (across terminals 2-5, 4-5).
2. The multi-speeds can also be set in the PU or external operation mode.
3. For 3-speed setting, if two or three speeds are simultaneously selected, priority is given to the
frequency setting of the lower signal.
4. Pr. 24 to Pr. 27 and Pr. 232 to Pr. 239 settings have no priority between them.
5. The parameter values can be changed during operation.
6. When terminal assignment is changed using Pr. 180 to Pr. 186, the other functions may be
affected. Check the functions of the corresponding terminals before making setting.
Setting Range
0 to 400Hz
0 to 400Hz
0 to 400Hz
0 to 400Hz, 9999
0 to 400Hz, 9999
Speed 1
(high speed)
Speed 2
Speed 5
(middle speed)
Speed 6
Speed 4
Speed 3
(low speed)
Speed 7
ON
ON ON ON
ON
ON
ON
ON
ON
ON
ON
Pr. 1 "maximum frequency"
Pr. 2 "minimum frequency"
Pr. 15 "jog frequency"
Pr. 28 "multi-speed input compensation"
Pr. 29 "acceleration/deceleration
Pr. 79 "operation mode selection"
Pr. 180 to Pr. 186 (input terminal
Remarks
9999: Not selected
9999: Not selected
Speed 10
Speed 11
Speed 9
Speed 8
Time
ON ON ON ON
RH
ON ON
RM
ON
ON
RL
ON
ON
ON ON ON ON ON ON
REX
66
PARAMETERS
Related parameters
pattern"
function selection)
Speed 12
Speed 13
Speed 14
Speed 15
Time
ON ON
ON
ON