( 3 ) Monitoring the offline tuning status
When the parameter unit (FR-PU04) is used, the Pr. 96 value is displayed during tuning on the main
monitor as shown below. When the operation panel (FR-DU04) is used, only the same numerical value as
on the PU is displayed:
·
Parameter unit (FR-PU04) main monitor
Display
·
Operation panel (FR-DU04) display
Displayed
value
·
Reference: Offline auto tuning time (factory setting)
Offline Auto Tuning Setting
1: No-rotation mode
2: Rotation mode
(4) Ending the offline auto tuning
1) Confirm the Pr. 96 value.
·
Normal end: "3" or "103" is displayed.
·
Error-activated end: "9", "91", "92" or "93" is displayed.
·
Forced end ... "8" is displayed.
2) When tuning ended normally.
For PU operation, press the [STOP] key. For external operation, switch off the start signal (STF or STR).
This operation resets the offline auto tuning and the PU's monitor display returns to the ordinary indication.
(Without this operation, next operation cannot be done.)
3) When tuning was ended due to an error.
Offline auto tuning did not end normally. (Motor constants have not been set.) Reset the inverter and start
tuning all over again.
4) Error display definitions.
Error Display
9
91
92
93
No connection with motor will result in 93 error.
2. Tuning in
1. Setting
progress
TUNE
1
STF
STOP
PU
TUNE
101
STOP
PU
STF
2. Tuning in
1. Setting
progress
1
101
Approximately 25 seconds
Approximately 40 seconds
(Offline auto tuning time varies with acceleration and deceleration time settings as
indicated below:
Offline auto tuning time = acceleration time + deceleration time + approximately 30
seconds)
Error Cause
Inverter trip
Current limit (stall prevention) function was
activated.
Inverter output voltage reached 75% of rated
value.
Calculation error
3. Completion
TUNE
2
COMPLETION
FWD
PU
STF
STOP
TUNE
102
COMPLETION
FWD
PU
STF
STOP
3. Completion
2
3
102
103
Time
Re-set.
Increase acceleration/deceleration time.
Set "1" in Pr. 156.
Check for fluctuation of power supply voltage.
Check the motor wiring and re-set.
108
PARAMETERS
(For inverter trip)
4. Error-activated end
3
PU
TUNE
9
ERROR
STF
STOP
103
PU
(For inverter trip)
4. Error-activated end
9
Remedy
PU