Mitsubishi Electric FR-A520-0.4K-NA Instruction Manual page 119

Transistorized inverter
Hide thumbs Also See for FR-A520-0.4K-NA:
Table of Contents

Advertisement

Parameter details
Parameter
Number
9
71 (Note 1)
83
0 to 1000V
84
50 to 120Hz
90
0 to , 9999
91
0 to , 9999
92
0 to , 9999
93
0 to , 9999
94
96 (Note 2)
Note: 1. The electronic overcurrent protection characteristics are also selected simultaneously.
2. Select "101" to increase tuning accuracy.
( 2 ) Tuning execution
·
For PU operation, press the [FWD] or [REV] key.
·
For external operation, switch on the run command.
Note: 1. When "101" is set in Pr. 96, guard against hazards because the motor rotates.
2. To force tuning to end
·
Switch on the MRS or RES signal or press the [STOP] key to end.
·
Switch off the tuning start command or make a forced stop.
3. During offline auto tuning, the following I/O signals are only valid:
·
Input signals
STOP, OH, MRS, RT, CS, RES, STF, STR
·
Output signals
RUN, OL, IPF, FM, AM, A, B, C
4. Special caution should be exercised when a sequence has been designed to open the
mechanical brake with the RUN signal.
Setting
0 to 500A
Set the rated motor current (A).
Electronic overcurrent protection thermal characteristics suitable for general-purpose
0
motor
Electronic overcurrent protection thermal characteristics suitable for Mitsubishi's
1
constant-torque motor
Electronic overcurrent protection thermal characteristics suitable for general-purpose
2
motor
5-point flexible V/F characteristics
Mitsubishi's SF-JR4P general-purpose motor (1.5kW (2HP) or less), Electronic
20
overcurrent protection thermal characteristics for advanced magnetic flux vector
control
3
Standard motor
13
Constant-torque motor
Mitsubishi's SF-JR4P standard motor
23
(1.5kW (2HP) or less)
4
Standard motor
14
Constant-torque motor
Mitsubishi's SF-JR4P standard motor
24
(1.5kW (2HP) or less)
5
Standard motor
15
Constant-torque motor
6
Standard motor
16
Constant-torque motor
7
Standard motor
17
Constant-torque motor
8
Standard motor
18
Constant-torque motor
Set the rated motor voltage (V).
Set the rated motor frequency (Hz).
Tuning data
(Values measured by offline auto tuning are set automatically.)
9999
0 to 100%
0
Offline auto tuning is not performed.
1
Offline auto tuning is performed without motor running.
101
Offline auto tuning is performed with motor running.
Description
Select "offline auto tuning setting"
Auto tuning read or change setting
enabled
Star connection
Delta connection
Star connection
Delta connection
107
PARAMETERS
Direct input of
motor constants
enabled
Direct input of
motor constants
and offline auto
tuning

Advertisement

Table of Contents
loading

Table of Contents