Layout of modules on several racks

Overview
With the SIMOTION C, a 2-tier layout is possible.
Interface modules
Interface modules are required for the 2-tier layout which route the backplane bus from one
rack to the other. The SIMOTION C is always located on rack 0.
Table 5-3
IM 365 SEND
IM 365 RECEIVE
IM 365 interface modules
The two IM 365 interface modules have a fixed connection via a 1-meter long connecting
cable.
The total power consumption of the inserted I/O modules of both racks must not exceed 1.2
A; the power consumption from rack 1 is limited to 800 mA.
Rules
The following rules apply with respect to the layout of the modules on two racks:
● The interface module always occupies Slot 3 and is always left of the first signal module.
● No more than eight modules may be inserted per rack. These modules are always to the
right of the interface modules.
● The number of inserted modules is limited by the permissible power consumption from the
backplane bus. Total power consumption must not exceed 1.2 A (see Technical data table
for each module in the manual
SIMOTION C
Operating Instructions, 11/2016, A5E33441428B
Interface modules
Interface module
5.2 Configuring an installation using SIMOTION C modules
Usable for ...
Rack 0
Rack 1
S7-300 Automation System, M7-300 Module Data ).
Configuring and installing
Article number
6ES7 365-0BA01-0AA0
81