[2-1 System Configurations ]

2-1

System Configurations

2 Restrictions
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
Outdoor units
HP200
YNW-A
HP250
YNW-A
HP400
YSNW-A
HP500
YSNW-A
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
BS_02_M
Composing units
-
-
-
-
-
-
HP200
HP200
-
HP250
HP250
-
Maximum total
Maximum
capacity of con-
number of
nectable indoor
connect-
units
able indoor
units
100 - 260
20
125 - 325
25
200 - 520
40
250 - 650
50
Types of connectable
indoor units
P10 - P250 models
R410A series indoor units
chapter 2 -
1