[2-1 System Configurations ]

2 Restrictions
2-1

System Configurations

1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
Outdoor
Composing units
units
72
-
96
-
120
-
144
-
144
72
72
168
-
168
96
72
192
120
72
216
120
96
240
120
120
264
120
72
288
120
96
312
120
120
336
120
120
360
144
120
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
HWE14080
Maximum total capacity
of connectable indoor
units
-
-
36 - 93
-
-
48 - 124
-
-
60 - 156
-
-
72 - 187
-
72 - 187
-
-
84 - 218
-
84 - 218
-
96 - 249
-
108 - 280
-
120 - 312
72
132 - 343
72
144 - 374
72
156 - 405
96
168 - 436
96
180 - 468
- 17 -
Maximum number
Types of connectable in-
of connectable in-
door units
door units
15
P06 - P96models
R410A series indoor units
20
26
31
31
36
36
41
46
50
GB