Download Print this page

Error Code [6602]; Error Code [6603] - Mitsubishi Electric PUHY-HP200YNW-A Service Handbook

Advertisement

[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
7-8-4
Error Code [6601]
1. Error code definition
Polarity setting error
2. Error definition and error detection method
The error detected when transmission processor cannot distinguish the polarities of the M-NET transmission line.
Detail code 001: Detection of polarity setting error in centralized control system
Detail code 002: Detection of polarity setting error in indoor unit system
3. Cause, check method and remedy
(1)
No voltage is applied to the M-NET transmission line
that AE-200E/AG-150A/GB-50ADA/PAC-
YG50ECA/BAC-HD150 are connected to.
(2)
M-NET transmission line to which AE-200E/AG-
150A/GB-50ADA/PAC-YG50ECA/BAC-HD150 are
connected is short-circuited.
(3)
When two or more power supplies are connected to
the M-NET
44
- chapter 7
Cause
Check method and remedy
Check if power is supplied to the M-NET transmission
line of the AE-200E/AG-150A/GB-50ADA/PAC-
YG50ECA/BAC-HD150, and correct any problem found.
BS_07_L