Error Code [6601]

1. Error code definition
Polarity setting error
2. Error definition and error detection method
The error detected when transmission processor cannot distinguish the polarities of the M-NET transmission line.
3. Cause, check method and remedy
(1)
No voltage is applied to the M-NET transmission line
that AG-150A/GB-50ADA/PAC-YG50ECA/BAC-
HD150 are connected to.
(2)
M-NET transmission line to which AE-200/AG-150A/
GB-50ADA/PAC-YG50ECA/BAC-HD150 are con-
nected is short-circuited.
(3)
When two or more power supplies are connected to
the M-NET
HWE18220_GB
Cause
Check method and remedy
Check if power is supplied to the M-NET transmission
line of the AG-150A/GB-50ADA/PAC-YG50ECA/BAC-
HD150, and correct any problem found.