Change of position of the
If the circuit-breaker is supplied equipped with terminals of the horizontal/rear type, it is possible at
vertical/horizontal terminals
any moment to switch from horizontal to vertical and vice versa. (see Figure 62 and Figure 63). Lock the
screws with tightening torque 20 Nm - 177 lb in.
Figure 62
Figure 63
24 | © 2022 ABB | 1SDH000999R0002 - ECN000297030