1 Fiber network module FN2013 / FN2014
The fiber network module multi-mode (MM) and the fiber network module single-mode
(SM) can be used for the exclusive purpose of networking fire detection panels to the
HNET, XNET, SNC, or HUB-4 over large distances using fiber-optic cable.
The fiber network modules have the following features:
Fiber network module (SM) FN2013: Single-mode transmission up to
131,000 ft/40,000 m
Fiber network module (MM) FN2014: Multi-mode transmission up to
13,100 ft/4,000 m
SC connections for fiber-optic cable
Trouble signaling via LED
Mounting in panel
In Desigo/Cerberus PRO Modular systems, the fiber network module is installed on a
COM-BRK bracket that can be mounted to the CAB-1, CAB-2 or CAB-3 back box or to
the optional CAB-MP.
The COM-BRK takes up the same space as a CC-2 card cage. The fiber network
module should first be secured to the COM-BRK using the three screws provided with
the module, then installed in the back box or mounting plate using the four screws
provided with the bracket.
Once the bracket and module are secured to the cabinet, wire the module and connect
the optical fiber cable as described later in this document.