Huawei JUPITER-3000K-H1 User Manual page 46

Transformer station
Hide thumbs Also See for JUPITER-3000K-H1:
Table of Contents

Advertisement

JUPITER-(3000K, 6000K, 9000K)-H1 Smart
Transformer Station
User Manual
Feature Specifications
Technical
JUPITER -3000K-H1
Specification
s
Transformer
Oil-immersed
type
Transformer
ONAN
cooling type
Transformer
Mineral oil
oil type
Transformer
Dy11
winding
connection
MV
SF
, 12–40.5 kV, 600/630 A, three feeders (CVC/CCV or DVC/DCV), 20 kA/3s, 50BF
6
switchgear
(Optional), 50G/51G (Optional)
LV Room
ACB (2900 A/800 V/3P)
and MCCB (400 A/800
V/3P, 17 PCS)
Auxiliary
Part Specifications
transformer
● 5 kVA,Ii0,800 V/230 V
● 50 kVA, Dyn11, 800 V/400 V
● 50 kVA, Dyn11, 800 V/220 V
Supported device specifications
● 5 kVA,Dyn11,800 V/230 V:2 kW
● 50 kVA, Dyn11, 800 V/400 V: L1 ≤ 15 kW, L2 ≤ 15 kW, L3 ≤ 15 kW
● 50 kVA, Dyn11, 800 V/220 V: L1 ≤ 15 kW, L2 ≤ 15 kW, L3 ≤ 15 kW
Issue Draft A
(2022-09-07)
JUPITER -6000K-H1
Dy11-y11
ACB (2900 A/800 V/
3P), MCCB (400 A/800
V/3P, 2 x 11 PCS)
Copyright © Huawei Technologies Co., Ltd.
5 Technical Specifications
JUPITER-9000K-H1
ACB (4000 A/800 V/3P),
MCCB (400 A/800 V/3P, 2
x 15 PCS)