Table 8.1 Short circuit current rating
15
High Fault
Current
Soft-starter
440-
550-
Type
480V
600V
PSTX30
Iq:
65kA
35kA
PSTX37
PSTX45
PSTX60
PSTX72
PSTX85
PSTX105
PSTX142
PSTX170
PSTX210
PSTX250
PSTX300
PSTX370
PSTX470/
65
PSTX570
High Fault Current
Soft-starter
Type
550-600V
PSTX30
Iq: 100kA
PSTX37
PSTX45
PSTX60
PSTX72
PSTX85
PSTX105
PSTX142
PSTX170
PSTX210
PSTX250
PSTX300
PSTX570
256 Softstarters Type PSTX30...PSTX570 User Manual short form 1SFC132082M9901
High breaker
Iq:
T4H250PR221DS-LS/I In100
T4H250PR221DS-LS/I In100
T4H250PR221DS-LS/I In100
T4H250PR221DS-LS/I In100
T4H250PR221DS-LS/I In150
T4H250PR221DS-LS/I In150
T4H250PR221DS-LS/I In250
T4H250PR221DS-LS/I In250
T5H400PR221DS-LS/I In300
T5H400PR221DS-LS/I In300
T5H400PR221DS-LS/I In400
T5H600PR221DS-LS/I In600
T6H800PR221DS-LS/I In600
50
T7H1200PR231DS-LS/I In1200
Breaker
T4V250PR221DS-LS/I In100
T4V250PR221DS-LS/I In100
T4V250PR221DS-LS/I In100
T4V250PR221DS-LS/I In100
T4V250PR221DS-LS/I In150
T4V250PR221DS-LS/I In150
T4V250PR221DS-LS/I In250
T4V250PR221DS-LS/I In250
T5V400PR221DS-LS/I In300
T5V400PR221DS-LS/I In300
T5V400PR221DS-LS/I In400
T5V600PR221DS-LS/I In600
T5V600PR221DS-LS/I In600
Breaker
High Fault
Current
440-
550-
480V
600V
Iq:
Iq:
100kA
65kA
Iq:
94.4kA
65
65
Very high breaker
Limiting breaker
T4L250 PR221DS-LS/I In100
T4L250 PR221DS-LS/I In100
T4L250 PR221DS-LS/I In100
T4L250 PR221DS-LS/I In100
T4L250 PR221DS-LS/I In150
T4L250 PR221DS-LS/I In150
T4L250 PR221DS-LS/I In250
T4L250PR221DS-LS/I In250
T5L400PR221DS-LS/I In300
T5L400PR221DS-LS/I In300
T5L400PR221DS-LS/I In400
T5L600PR221DS-LS/I In600
T5L600PR221DS-LS/I In600
-
T6L800PR221DS-LS/I In600
T7L1200PR231DS-LS/I In1200