Table 6.7: Parameter list for operational function
This is a selection of the most commonly used parameters.
For complete parameter list and setting range, see:
1SFC132081M0201 - Softstarters type PSTX30...PSTX570, Installation and Commissioning Manual
available on: http://www.abb.com/lowvoltage
Parameter name
1.1 Motor rated current Ie
2.1 Start mode
2.2 Stop mode
2.3 Start ramp initial level
2.4 Start ramp time
2.5 Stop ramp end level
2.6 Stop ramp time
3.1 Current limit type
3.2 Current limit level
Kick start
1
Slow speed
1
Motor heating
1
Motor braking
1
Sequence start
1
Automatic restart
1
26.12 Faulty connection operation
28.5 Step down level
28.41 System mode
28.43 Mains connection
28.42 Limp mode
For full parameter list, see I1SFC132081M0201
1
- Softstarters Type PSTX30...PSTX570, Installation and Commissioning Manual
available on: http://www.abb.com/lowvoltage
Operation functions
Setting range
PSTX30: 9 ... 30 A
Voltage ramp, Torque ramp,
Full voltage start
Voltage ramp, Torque ramp,
10 ... 99 %
10 ... 99%
Off, Normal, Dual, Ramp
1.5 ... 7.5 xIe
Stop-Manual,
Stop-Automatic
10 ... 100%
Normal, Demo, Small motor
Auto, In line, Inside delta UI,
Inside delta IU,
Two phase (L1 Shorted),
Two phase (L2 Shorted),
Two phase (L3 Shorted)
Softstarters Type PSTX30...PSTX570 User Manual short form 1SFC132082M9901 15
1
No ramp
1 ... 120s
1 ... 120s
On/Off
On/Off
Default value
30 A
Voltage ramp
No ramp
30%
10s
30%
10s
Normal
4.0 xIe
Off
Stop-Manual
80%
Normal
Auto
Off