6 Softstarter settings
6.1: First start-up
When the softstarter is powered up for the first time the HMI will enter the
Basic set-up assistant **. See figure 6, graphics 14.
After the set-up is complete you will enter the Home view.
6.2: Assistants menu
For an initial configuration of the softstarter it is recommended to use the
Assistants. An Assistant is a step-by-step wizard which guides the user
through a group of tasks to set-up and configure the softstarter.
Menu u Assistants
Push
, Menu, to enter the menu. Use
and push
Assistants menu
Basic set-up
1. Language
2. Date and time
3. Motor data **
4. System configuration
5. Set-up complete
Use
,
values.
See table 6.3 for a list of the parameters, and their recommended values,
which can be configured through the Application set-up assistant.
** All PSTX softstarters must be configured to the rated current of the
motor. If the motor is connected In Line, set the parameter "01.01 Mo-
tor rated current Ie" to the value found on the rating plate of the motor.
If the motor is connected Inside Delta, set the parameter "01.01 Motor
rated current Ie" to (1 /(√3))=58 % of the rated motor current.
, Select.
and
, to navigate through the steps and change the
Softstarters Type PSTX30...PSTX570 User Manual short form 1SFC132082M9901 11
or
to highlight Assistants
Application set-up
1. Application set-up
2. Keep/Change values
3. Tune settings
4. Set-up complete