Hitachi Relion REB670 Commissioning Manual page 95

Table of Contents

Advertisement

1MRK 505 372-UEN Rev. K
Calculated settings
Valid configuration diagram for the IED
Valid terminal diagram for the IED
Technical reference manual
Single phase test equipment
The technical reference manual contains application and functionality summaries, function blocks,
logic diagrams, input and output signals, a list of setting parameters and technical data for the
function.
The test equipment should be able to provide a single phase supply of currents. The magnitude of
currents should be possible to vary.
Make sure the IED is prepared for test before starting the test session. Consider the logic diagram of
the function when performing the test. The response from a test can be viewed in different ways:
Binary output signals
Service values in the local HMI (logical signal or phasors)
A PC with PCM600 (configuration software) in debug mode
10.4.7.1
Function revision history
Document
revision
A
B
C
D
E
F
G
H
10.4.7.2
Checking the phase current operate value IP>
Procedure
1.
Apply the fault condition, including START of CCSRBRF, with a current value below set IP>.
2.
Repeat the fault condition and increase the current in steps until a trip occurs.
3.
Compare the result with the set IP>.
4.
Disconnect the AC and start input signals.
10.4.7.3
Checking the re-trip and back-up times
The check of the set times can be made in connection with the check of operate values above.
Choose the applicable function and trip mode, such as FunctMode = Current and RetripMode =
UseFunctionMode.
Busbar protection REB670
Commissioning manual
Product
History
revision
2.2.1
I>BlkCBPos setting functionality correction.
2.2.1
-
2.2.2
-
2.2.3
Setting StartMode is added to choose how retrip and backup trip timers can run. The
choices are; to run the timers by external start signal which is latched, to follow the
external start signal only or to follow the external start signal and the selected
FunctionMode.
2.2.3
-
2.2.4
-
2.2.4
-
2.2.5
-
If RetripMode is set to Off and FunctionMode is set current, only back-up trip can be
used to check set IP>.
© 2017 - 2022 Hitachi Energy. All rights reserved
Section 10
Testing functionality by secondary injection
GUID-324748A0-9D6C-4950-898E-88524827FF94 v2
SEMOD128582-25 v7
SEMOD128582-54 v6
89