UPS5000-S-1200 kVA User Manual Issue Date 2023-05-26 HUAWEI DIGITAL POWER TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei Digital Power Technologies Co., Ltd. and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
UPS5000-S-1200 kVA User Manual About This Document About This Document Purpose This document describes the UPS5000-S-1200 kVA in terms of its features, performance specifications, working principles, appearance, structure, installation, and operation and maintenance (O&M). Intended Audience This document is intended for: ●...
Output capacity 1200 kVA Solution FusionPower The maximum capacity of UPS5000-S-1200 kVA-FP is 1200 kVA and it is compatible with a capacity of 1100 kVA, 990 kVA, 880 kVA, 770 kVA and 660 kVA. 2.2 Working Principle NO TE ●...
3.2.6 Remote EPO NO TICE ● Huawei does not provide the EPO switch or cable. If the cable is required, the recommended cable is 22 AWG. ● Equip the EPO switch with a protective cover to prevent misoperations, and cover the cable with protective tubing.
(that is, the green indicator is blinking) and then maintain the ECM. Bus capacitor life forecast If the service life of a capacitor is about to end, that is, Power unit X bus capacitor life (y) is less than 1.0, contact Huawei technical support to replace the power unit. 4.1.3.5 About On the About screen, you can view the model, manufacturer, monitoring version, and power version.
Step 5 Turn on mains input circuit breaker 1 (Q1-1), mains input circuit breaker 2 (Q1-2), and bypass input switch (Q2). After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar.
1 Hz or is steady on. Then, press and hold down the BATT START button on the bypass module for at least 2 seconds. The system automatically enters the battery cold start status. The LCD displays the Huawei logo and an initialization progress bar.
Customers are not allowed to maintain components behind protective covers that can be removed only using tools. If the components are to be maintained, contact Huawei technical support. ● Only maintenance engineers can maintain power modules and bypass modules.
UPS5000-S-1200 kVA User Manual C Alarm List Alarm List NO TE This table lists only common alarms. For more information, contact Huawei technical support. Alarm ID Alarm Name Severity Cause Solution (Alarm ID- Cause ID) 0001-1 Mains voltage Minor ● Cable 1.