Mitsubishi Electric FR-E720-0.1 K Instruction Manual page 32

Table of Contents

Advertisement

(3)
Total wiring length
The overall wiring length for connection of a single motor or multiple motors should be within the value in the table
below.
Pr. 72 PWM frequency selection
Setting
(carrier frequency)
100V class,
1 (1kHz) or less
200V class
400V class
100V class,
2 to15
200V class
(2kHz to 14.5kHz)
400V class
When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the
motor terminals, deteriorating the insulation of the motor.(Refer to page 92)
NOTE
Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray
capacitances of the wiring, leading to a malfunction of the overcurrent protective function, fast response current limit
function, or stall prevention function or a malfunction or fault of the equipment connected on the inverter output side.
If malfunction of fast-response current limit function occurs, disable this function. If malfunction of stall prevention
function occurs, increase the stall level. (Refer to page 88 for Pr. 22 Stall prevention operation level and Pr. 156 Stall prevention
operation selection )
Refer to page 169 for details of Pr. 72 PWM frequency selection. Refer to the manual of the option for details of surge voltage
suppression filter (FR-ASF-H/FR-BMF-H).
When using the automatic restart after instantaneous power failure function with wiring length exceeding 100m,
select without frequency search (Pr. 162 = "1, 11"). ( Refer to page 157)
0.1K
0.2K
0.4K
200m
200m
300m
-
-
200m
30m
100m
200m
-
-
30m
Total wiring length (3.7K or more)
300m+300m=600m
Main circuit terminal specifications
0.75K
1.5K
2.2K
500m
500m
500m
200m
300m
500m
300m
500m
500m
100m
200m
300m
500m or less
300m
300m
3.7K
or More
500m
500m
500m
500m
21
2