mA Output Parameters (P200 to P203, P210 to P215,
P219)
If LU AO mA outputs are to be used, alter the following parameters as required.
Otherwise, proceed to Operation.
When a mA Output Parameter is accessed, the mA symbol is displayed in the Point Type
field and the mA Output Number (corresponding to the LU AO terminals) is displayed in
the Point Number field.
P200
mA RANGE
Enter the desired range of the mA output displayed.
value:
P201
mA FUNCTION
Use this feature to alter the automatic mA output/measurement relationship, if
desired.
The mA Function automatically corresponds to "level", "space", or "distance"
based upon Operation (P001). If a Tank Shape (P050) is programmed, the mA
Function automatically corresponds to volume (unless the mA Allocation has
been altered).
values: 1 = level
7ML19985AN02
0 = OFF
1 = 0 to 20 mA
20 mA = high level (unless P001 = 2 or 3, then 20
mA = low)
2 = 4 to 20 mA
(preset)
3 = 20 to 0 mA
20 mA = low level (unless P001 = 2 or 3, then 20
4 = 20 to 4 mA
mA = high)
2 = space
3 = distance
4 = volume
SITRANS LU10 – INSTRUCTION MANUAL