WARNING
Usage
Stay away from the equipment after using the retry function in this product as the equipment will restart suddenly after
the output shutoff of this product.
Depending on the function settings of this product, the product does not stop its output even when the STOP/RESET
key on the operation panel is pressed. To prepare for it, provide a separate circuit and switch (to turn OFF the power of
this product, or apply a mechanical brake, etc.) for an emergency stop.
Be sure to turn OFF the start (STF/STR) signal before clearing the fault as this product will restart the motor suddenly
after a fault is cleared.
Do not use a PM motor for an application that the motor may be driven by the load and run at a speed higher than the
maximum motor speed.
Use only a three-phase induction motor or PM motor as a load on this product. Connection of any other electrical
equipment to the output of this product may damage the equipment.
Performing pre-excitation (by using the LX or X13 signal) during torque control (under Real sensorless vector control)
may rotate a motor at a low speed even though a start command (STF or STR) is not given. This product with the start
command ON may also rotate the motor at a low speed when the speed limit value is set to zero. Confirm that the motor
running does not cause any safety problems before performing pre-excitation.
Do not modify this product.
Do not remove any part which is not instructed to be removed in the Instruction Manuals. Doing so may lead to a failure
or damage of this product.