QUICK START GUIDE
SPS -48V Slimline Power Shelf
Models: J2007003L005 - alpha suffixes per Slimline Power System
Brochure
No vertical spacing is required, allow a minimum 2", inch clearance at back of shelf for rectifier airflow.
Tools required:
Wire cutters and strippers
Cable crimpers
Step 1 - Mount Shelf
1.
Reposition mounting ears as required - 3 screws each. (Reverse ears for 5" setback.) Torque to 10 in-lb.
(1.2 Nm) - Phillips screwdriver.
2. Attach shelf to the frame using a minimum of four screws (two on each side) - 12-24 (provided). Torque to 35
in-lb. (4 Nm) - 5/16" socket.
Step 2 - Connect Chassis Ground and DC Reference (CO) Ground
Lug Landings: #10 double-hole on 5/8-inch center (lugs not provided)
Some applications may rely on frame mounting screws for chassis ground, omitting the chassis ground wire.
Some applications may use the Chassis Ground strap, using a single wire for both chassis ground and DC
reference ground.
Minimum 10 AWG wire is recommended.
Torque 10-32 screws to 30 in-lb. (3.4 Nm) - 5/16" socket.
Page 1
© 2023 ABB. All rights reserved.
Torque wrench - 0-65 in-lb (0-10 Nm)
Sockets - 5/16", 7/16, etc.
SPS -48V Shelf_QSG
Screwdrivers - Philips #1 and #2,
Flat small
Rev. 2.0

Advertisement

loading

Summary of Contents for ABB J2007003L005

  • Page 1 QUICK START GUIDE SPS -48V Slimline Power Shelf Models: J2007003L005 - alpha suffixes per Slimline Power System Brochure No vertical spacing is required, allow a minimum 2”, inch clearance at back of shelf for rectifier airflow. Tools required: Screwdrivers - Philips #1 and #2,...
  • Page 2 5. Torque to 6.5 in-lb. (0.75 Nm). 6. Pull wires to verify. 7. Insert detachable terminal block fully. 8. Repeat from 1 for each Battery, Breaker Load, and Fuse Load. Page 2 © 2023 ABB. All rights reserved. SPS -48V Shelf_QSG Rev. 2.0...
  • Page 3 Verify that all AC, DC and Alarm connections are complete and secure. Turn on AC input breakers. If there are no alarms, make required adjustments to the default settings on the controller for this installation. Page 3 © 2023 ABB. All rights reserved. SPS -48V Shelf_QSG Rev. 2.0...
  • Page 4 N/A & 200 – 240 7.5 1600 Output Current at 54.5v. Outputs are power limited, not current limited. Set rectifier current limit to avoid possible nuisance tripping Page 4 © 2023 ABB. All rights reserved. SPS -48V Shelf_QSG Rev. 2.0...
  • Page 5 Input: External Fan Fail Output: R4 = Rtn1,2 1. Only with 6 relay controller (..6R..). 2. Returns for R1 and R4 are bridged. Other returns are isolated. Page 5 © 2023 ABB. All rights reserved. SPS -48V Shelf_QSG Rev. 2.0...
  • Page 6 CC848836981 Pulsar Edge Controller Family Product Manual Temperature: North America – 50°C Max. with no derating. 2% / °C derating above 50°C to 75°C. CE – 50°C Max. Page 6 © 2023 ABB. All rights reserved. SPS -48V Shelf_QSG Rev. 2.0...
  • Page 7: Safety Statements

    Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the cabinet AC service ground bus. In huts, vaults, and central offices connect to the system bonding network. Page 7 © 2023 ABB. All rights reserved. SPS -48V Shelf_QSG Rev. 2.0...
  • Page 8 AC de l’armoire. Dans les cabanes, les coffres et les bureaux centraux se connectent au réseau de liaison du système. Page 8 © 2023 ABB. All rights reserved. SPS -48V Shelf_QSG Rev. 2.0...
  • Page 9 Personnel with electronic medical devices need to be aware that proximity to DC power and distribution systems, including batteries and cables, typically found in telecommunications utility rooms, can affect medical electronic devices, such as pacemakers. Effects decrease with distance. Page 9 © 2023 ABB. All rights reserved. SPS -48V Shelf_QSG Rev. 2.0...
  • Page 10 électroniques médicaux, tels que les stimulateurs cardiaques. Les effets diminuent avec la distance. Page 10 © 2023 ABB. All rights reserved. SPS -48V Shelf_QSG Rev. 2.0...
  • Page 11 QUICK START GUIDE Notes: Page 11 © 2023 ABB. All rights reserved. SPS -48V Shelf_QSG Rev. 2.0...
  • Page 12 QUICK START GUIDE Notes: Page 12 © 2023 ABB. All rights reserved. SPS -48V Shelf_QSG Rev. 2.0...
  • Page 13 QUICK START GUIDE Notes: Page 13 © 2023 ABB. All rights reserved. SPS -48V Shelf_QSG Rev. 2.0...
  • Page 14 – in whole or in does accept responsibility whatsoever parts – is forbidden without prior written consent of ABB. for potential errors or possible lack of information in this document. Copyright© 2023 ABB All rights reserved Page 14 ©...

This manual is also suitable for:

Sps-48v