QUICK START GUIDE
SPS –48V Slimline Power Shelf
Models: J2007003L011 - alpha suffixes per Slimline Power System
Brochure
No vertical spacing is required, allow a minimum 2 inch clearance at back of shelf for rectifier airflow.
Refer to Slimline Power System Brochure for details and accessories.
Wire cutters and strippers
Cable crimpers
Torque wrench - 0-65 in-lb (0-10 Nm)
1.
Reposition mounting ears as required - 1 screw each. Torque to 25 in-lb (2.8 Nm) - Phillips screwdriver.
2.
Attach shelf to the frame using a minimum of four screws (two on each side) - 12-24 (provided). Torque to 35 in-lb
(4 Nm) - 5/16" socket.
L004 - C13 cords (1 or 2). Secure cord with the AC cord retainer (furnished).
L014 - wire to AC terminal blocks. Strip 0.3" (8 mm). Torque to 10 in-lb (1 Nm).
Danger: If blunt cut cords are used ensure AC power is OFF and use appropriate lock-out tag-out procedures
before continuing with ac connections. Follow all local and national wiring rules when connecting to ac mains.
Page 1
© 2021 ABB. All rights reserved.
Sockets - 5/16", 7/16, etc.
Screwdrivers - Philips #1 and #2, Flat small

Advertisement

loading

Summary of Contents for ABB SPS-48V

  • Page 1 Danger: If blunt cut cords are used ensure AC power is OFF and use appropriate lock-out tag-out procedures before continuing with ac connections. Follow all local and national wiring rules when connecting to ac mains. Page 1 © 2021 ABB. All rights reserved.
  • Page 2 Insert small flat screwdriver to open clamp.. Battery DC Aux Output DC Reference (CO) Ground DC Outputs 1-6 GMT style fused GMT style fuses DC Outputs 7-12 GMT style fused 15A max fuses Page 2 © 2021 ABB. All rights reserved.
  • Page 3 Verify that all AC, DC and Alarm connections are complete and secure. Turn on AC input breakers. If there are no alarms, make required adjustments to the default settings on the controller for this installation. Verify and edit controller basic configuration parameters per site engineering instructions. Page 3 © 2021 ABB. All rights reserved.
  • Page 4 Change alarm descriptions via LAN port (Web pages) or Craft port (EasyView2) when required. Connector J1 - Controller Variants J2 - All Controllers 0I5R_D - 5 Alarm 3C3R - 3 Alarm Controller Color 9C0R_USB - 9 Inputs Color Relays Re- lays Input: SPD Fail Page 4 © 2021 ABB. All rights reserved.
  • Page 5 QUICK START GUIDE abbpowerconversion.com abbpowerconversion.com These documents are available at Document Title 850035894 Galaxy Pulsar Edge Quick Start Guide CC848815341 Pulsar Edge Controller Family Product Manual Slimline Power System Brochure Page 5 © 2021 ABB. All rights reserved.
  • Page 6: Safety Statements

    Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the cabinet AC service ground bus. In huts, vaults, and central offices connect to the system bonding network. Page 6 © 2021 ABB. All rights reserved.
  • Page 7 Personnel with electronic medical devices need to be aware that proximity to DC power and distribution systems, including batteries and cables, typically found in telecommunications utility rooms, can affect medical electronic devices, such as pacemakers. Effects decrease with distance. Page 7 © 2021 ABB. All rights reserved.
  • Page 8 With regard to and illustrations contained therein. Any reproduction, disclosure purchase orders, the agreed particulars shall prevail. ABB AG does to third parties or utilization of its contents–in whole or in not accept any responsibility whatsoever for potential errors or parts –...