A B B M E A S U R E M E N T & A N A L Y T I C S | O P E R A T I N G I N S T R U C T I O N
EAS822, EBS852, EBS862
Electronic unit for rack mount installation (Contrac)
Introduction
EAS822
EBS852
The electronic unit builds the interface between
EBS862
the actuator and the control system.
During continuous positioning, the electronic unit
varies the motor torque continuously until the
actuator force and the control valve force are
balanced.
High response sensitivity and high positioning
accuracy with short positioning time ensure an
excellent control quality and a long actuator life.
| O I / E A S 8 2 2 / E B S 8 5 2 / E B S 8 6 2 - E N R E V . D
For the control of Contrac control
actuators series PME, LME, RHD
and RSD
Additional Information
Additional documentation on EAS822, EBS852,
EBS862 is available for download free of charge at
www.abb.com/actuators.
Alternatively simply scan this code:

Advertisement

Table of Contents
loading

Summary of Contents for ABB EBS862

  • Page 1 The electronic unit builds the interface between Additional documentation on EAS822, EBS852, EBS862 the actuator and the control system. EBS862 is available for download free of charge at During continuous positioning, the electronic unit www.abb.com/actuators. varies the motor torque continuously until the...
  • Page 2: Table Of Contents

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Table of contents Change from one to two columns Safety ................3 Commissioning and operation ......30 General information and instructions ........3 General information .............. 30 Warnings ..................3 Engineering Software ECOM688 and ECOM700 ..30 Intended use ................
  • Page 3: Safety

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D 1 Safety hange from one to two columns General information and instructions Warnings The warnings in these instructions are structured as follows: These instructions are an important part of the product and must be retained for future reference.
  • Page 4: Intended Use

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D … 1 Safety Intended use Warranty provisions Using the device in a manner that does not fall within the scope The electronic units of type EAS822, EBS852, EBS862 of its intended use, disregarding this manual, using...
  • Page 5: Design And Function

    Figure 1: Presentation without cover for terminal compartment Figure 2: Presentation without cover for terminal compartment The EBS862 electronic unit is made up of two housing halves (electronic cover / electronic unit lower part) which can be separated for easier assembly.
  • Page 6: Principle Of Operation

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D … 2 Design and function Principle of operation The electronic unit builds the interface between the actuator and the control system. During continuous positioning, the electronic unit varies the motor torque continuously until the actuator force and the control valve force are balanced.
  • Page 7: Overview

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Overview Figure 3: Structure of the Contrac components (example)
  • Page 8: Device Designs

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D … 2 Design and function Device designs EAS822 IP rating IP 20 Humidity ≤ 75 % annual average; condensation not permitted Rack air inlet temperature 0 to 45 °C (32 to 113 °F) Transport and storage temperature −25 to 70 °C (−13 to 158 °F)
  • Page 9 EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D EBS862 IP rating IP 20 Humidity ≤ 75 % annual average; condensation not permitted Rack air inlet temperature 0 to 45 °C (32 to 113 °F) Transport and storage temperature −25 to 70 °C (−13 to 158 °F) Long-term storage temperature −25 to 40 °C (−13 to 104 °F)
  • Page 10: Product Identification

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D 3 Product identification Name plates Note In electronic units which can be separated for assembly, the name plate for the hardware is located on the lower part of the electronic unit (Figure 1). The name plate for the software (Figure 2) and an additional name plate for the hardware (Figure 3) are located on the electronic unit cover.
  • Page 11: Delivery Status

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D 4 Transport and storage Delivery status Inspection The individual actuator configuration may vary from the Check the devices immediately after unpacking for possible standard setup above. This information can be displayed via the damage that may have occurred from improper transport.
  • Page 12: Installation

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D 5 Installation Safety instructions EAS822 / EBS852 DANGER 1. Fasten the electronic unit to the vertical mounting rail of the Danger to life due to falling or toppling loads. mounting rack using grade 8.8 screws. Tensile strength 800...
  • Page 13: Assembly And Cable Routing In The Mounting Rack

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Assembly and cable routing in the mounting rack When installing the electronic units in a mounting rack (on site), we recommend laying the cables in accordance with the following illustrations. Front view...
  • Page 14: Dimensions

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D … 5 Installation Dimensions Electronic unit EAS822 (Contrac) Figure 8: Dimensions in mm (in)
  • Page 15: Electronic Unit Ebs852 (Contrac)

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Electronic unit EBS852 (Contrac) Figure 9: Dimensions in mm (in)
  • Page 16: Electronic Unit Ebs862 (Contrac)

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D … 5 Installation … Dimensions Electronic unit EBS862 (Contrac) 1 Front section open, rotated 90° 2 Rotational radius 3 Tap holes Figure 10: Dimensions in mm (in) Change from one to two columns...
  • Page 17: Electrical Connections

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D 6 Electrical connections Instructions on the use of Error Current Safety instructions Circuit Breakers (RCDs) WARNING If additional protection against accidental contact due to the Risk of injury due to live parts!
  • Page 18: Conductor Cross-Section On Universal Plug

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D … 6 Electrical connections Cable glands … Conductor cross-section on electronic unit The actuators and electronic units are supplied without cable glands. Suited cable glands must be installed on site. EBS852 – Clamping connection Tap holes for cable glands Suited for cable Ø...
  • Page 19 EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Scenario 3 Scenario 1 If the cable lengths specified in Actuator assignment and If the PE of the actuator is done only via the PE conductor of the maximum cable lengths on page 20 are fully utilized, an...
  • Page 20: Actuator Assignment And Maximum Cable Lengths

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D hange from two to one column … 6 Electrical connections Actuator assignment and maximum cable lengths Rotary actuators Electronic unit Actuator Cross-section of the motor cable / maximum permissible cable length* 1.5 mm...
  • Page 21: Electronic Unit Eas822 (Contrac) / Ebs852 (Contrac)

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Electronic unit EAS822 (Contrac) / EBS852 (Contrac) Note • The electrical connection is provided by a universal plug on the control actuator and the screw terminals on the electronic unit. •...
  • Page 22 EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D … 6 Electrical connections Electronic Unit EBN862 (Contrac) Note • The electrical connection is provided by a universal plug on the control actuator and the screw terminals on the electronic unit.
  • Page 23: Connection Examples

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Connection examples Operation following a continuous set point (standard) In the standard configuration, the binary inputs are configured as ‘MANUAL OPERATION’. To switch the actuator to automatic mode (AUT), the following conditions must be met: •...
  • Page 24 EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D … 6 Electrical connections … Connection examples Operation downstream from step controller Contrac actuators can be driven using step controller pulses instead of an analog setpoint. The following conditions must be fulfilled in order to implement the step controller pulses: •...
  • Page 25: Electrical Data For Inputs And Outputs

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Electrical data for inputs and outputs Power supply EAS822 Supply voltage (standard actuators) 115 V AC (94 to 130 V) or 230 V AC (190 to 260 V); 47.5 to 63 Hz; single-phase...
  • Page 26 EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D … 6 Electrical connections … Electrical data for inputs and outputs EBS862 Supply voltage (standard actuators) 230 V AC (190 to 260 V); 47.5 to 63 Hz; single-phase Supply voltage (Ex actuators) 230 V AC (190 to 253 V);...
  • Page 27: Connection Of The Power And Signal Cable On The Electronic Unit

    2.5 mm (AWG 14). 5 Power supply cable In addition to the internal fuses, the EBS862 electronic unit Figure 16: Terminal box requires two additional external fuses which are supplied separately with the assembly.
  • Page 28 EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D … 6 Electrical connections … Connection of the power and signal cable on the electronic unit EBS862 Connection of cable shielding 1 Cable clip 3 Shielding 2 Cable sheath 4 Housing Figure 18: Cable shielding 1.
  • Page 29: Connection Of The Power And Signal Cable On The Actuator

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Connection of the power and signal cable on the actuator Note 1. Remove the connector housing. A metal divider separates the two cable areas inside the 2. Cut the cable sheath to the required length.
  • Page 30: Commissioning And Operation

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D 7 Commissioning and operation Engineering Software ECOM688 and ECOM700 Note It is imperative that you observe the operating instruction of the Using the ECOM688 / ECOM700 engineering software, the user corresponding actuator for the commissioning of the electronic...
  • Page 31: Commissioning And Service Field

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Commissioning and service field Operating element Description Write protection switch Activates the hardware write protection. Factory setting: OFF – write protection deactivated. Refer to Hardware write protection on page 33. Potential switch Selection of reference potential.
  • Page 32: Meaning Of The Led Indicators

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D … 7 Commissioning and operation … Commissioning and service field Meaning of the LED indicators The LEDs 100 % / 0 % on the commissioning and service field (Figure 20, Pos.
  • Page 33: Hardware Settings

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Hardware settings Hardware write protection Defining the initial position (0 % or 100 %) If write protection is active, the device parameterization cannot 2. Use one of the travel buttons to move to the desired be changed.
  • Page 34: Manual (Man)- And Automatic Operation (Aut)

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D … 7 Commissioning and operation Manual (MAN)- and Automatic Operation (AUT) Signaling on the commissioning and service field Software version 2.00 and higher In the manual operating mode (MAN), the actuator solely reacts...
  • Page 35: Diagnosis / Error Messages

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D 8 Diagnosis / error messages Definition – Alarms and Errors Alarms The actuator / electronic unit is in a critical state (e.g., high temperature), which currently does not affect the actuator, electronic unit, process or persons.
  • Page 36: Error Diagram

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D … 8 Diagnosis / error messages Error Diagram Positioning loop monitoring Hardware monitoring Software monitoring Standstill Frequency converter end Error position transmitter memory positions Min. speed Flash Error Movement in incorrect direction...
  • Page 37: Hardware Errors

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Hardware Errors This chapter only covers hardware-related errors. For additional troubleshooting information, refer to the online help for the operator interface. Error Possible cause Troubleshooting the Instrument Valve cannot be moved by actuator.
  • Page 38: Maintenance

    All devices delivered to ABB must be free from any hazardous Contrac actuators feature a robust construction. As a result, materials (acids, alkalis, solvents, etc.).
  • Page 39: Fuses

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Fuses Type Fuse Installation location Design Rated current of fuse at 115 V AC at 230 V AC EBS852 External fuse External – 16 A, time-lag 16 A, time-lag Mains fuse...
  • Page 40: Recycling And Disposal

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D 11 Recycling and disposal 12 Approvals and certifications Note CE mark The version of the device as provided by us meets the Products that are marked with the adjacent symbol requirements of the following EU directives: may not be disposed of as unsorted municipal waste •...
  • Page 41: Appendix

    EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D 14 Appendix Return form Statement on the contamination of devices and components Repair and/or maintenance work will only be performed on devices and components if a statement form has been completed and submitted.
  • Page 42 EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Trademarks HART is a registered trademark of FieldComm Group, Austin, Texas, USA...
  • Page 43 EAS822, EBS852, EBS862 ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D Notes...
  • Page 44 We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.